Output Current Setting
Operation
The battery in this unit may not be fully charged. After electricity is connected to the unit for at least 24 hours, then normal
operation of this unit should take effect. During normal operation AC power is applied, the charging indicator light is
illuminated, indicating that the battery is being charged. When power fails, the emergency LED driver automatically
switches to emergency power (internal battery), operating the LED load for a minimum of 90 minutes. When AC power is
restored, the emergency driver returns to the charging mode.
In accordance with NFPA 101, your emergency lighting system must be tested monthly for a minimum of 30 seconds and
annually for 90 minutes. Refer to your local codes for any additional requirements that may apply.
Self-Testing Operation (-G2 and -G3/G3PRO models)
This unit automatically performs a 90
‐
second discharge test every month, and a full 90
‐
minute discharge test once a
year. During routine testing, the self
‐
testing emergency driver simulates an AC power failure causing the unit to
automatically switch to emergency mode. The unit will monitor the operation of the lighting fixture, internal battery
voltage, discharging current, and emergency duration. If the emergency system functions properly, then the unit will
return to normal mode. Should the unit detect any problems, the indicator light will flash continually until the condition
has been corrected and the unit passes the next test. Please refer to
Troubleshooting Guide
.
• If the unit pass the self
‐
diagnostic test successfully, the message will be cleared automatically after 24hrs. If the unit
fails during the test, the indicator light continues flashing until the condition has been corrected or cleared manually.
• If the condition has not been corrected by the next scheduled test, the unit will once again detect the failure and signal
the failure indicator.
• To cancel a test, press and hold the Multifunction Button ONCE for less than 1 seconds.
• To perform 90 seconds manual self
‐
test push and hold Multifunction button for a maximum 3 second. To perform 90
minutes manual self
‐
test push and hold multifunction button for a minimum 6 seconds. Once button is released,
emergency driver will perform the diagnostic test. After Self
‐
testing is completed, the indicator light will flash per
testing results.
Please refer to
Troubleshooting Guide
.
Maintenance
This self
‐
testing emergency driver automatically performs required routine testing. Results are reported to maintenance
personnel via the indicator lights. Although no routine maintenance is required to keep the emergency driver functional,
the indicator lights should be checked periodically. If the indicator lights are flashing, go through all steps of
Troubleshooting Guide
.
LEMD Series
Installation Instructions
10070337 P
1 - 11/23
4
800-533-3948 www.barronltg.com
Current Volts Pwr
A
Vdc
W SW1 SW2 SW3 SW4
440
16
7
on
---
---
---
290
24
7
---
on
---
---
195
36
7
---
---
on
---
145
48
7
---
---
---
on
Models: LEMD-7-LP & LEMD-7-HP
Micro-Switch
Current Volts Pwr
A
Vdc
W SW1 SW2 SW3 SW4
625
16
10
on
---
---
---
425
24
10
---
on
---
---
280
36
10
---
---
on
---
210
48
10
---
---
---
on
Models: LEMD-10-LP & LEMD-10-HP
Micro-Switch
Current Volts Pwr
A
Vdc
W SW1 SW2 SW3 SW4
875
24
21
on
---
---
---
580
36
21
---
on
---
---
500
42
21
---
---
on
---
435
48
21
---
---
---
on
Models: LEMD-21-LP & LEMD-21-HP
Micro-Switch
SW5: ON, SW6: ON