background image

900E Series

Installation Instructions

10070152  REV L  - 10/19

   1

800-533-3948 www.barronltg.com

Technical Support

 ■ (623) 580-8943 ■ [email protected]

IMPORTANT SAFEGUARDS

READ AND FOLLOW ALL SAFETY INSTRUCTIONS.

   When using electrical equipment, basic safety precautions should always be followed including the following:

•  

DISCONNECT AC POWER SUPPLY BEFORE SERVICING.

•  Installation and servicing of this equipment should be performed by qualified service personnel only.

   

 

•  Ensure that the electrical wiring conforms to the National Electrical Code NEC® and local regulations if 

       applicable.

   

•  For use with metal enclosed wiring systems. 

 

•  Do not mount near gas or electrical heaters.

   •  Do not use outdoors. 

 

•  Equipment should be mounted in locations and at heights where it will not be readily subjected to tampering 

 

    

by unauthorized personnel.

•  The use of accessory equipment not recommended by the manufacturer may cause an unsafe condition. 

•  Any modification or use of non-original components will void the warranty and product liability.

•  Do not use this equipment for other than intended use.

SAVE THESE INSTRUCTIONS!

Summary of Contents for Exitronix 900E Series

Page 1: ...rvice personnel only Ensure that the electrical wiring conforms to the National Electrical Code NEC and local regulations if applicable For use with metal enclosed wiring systems Do not mount near gas or electrical heaters Do not use outdoors Equipment should be mounted in locations and at heights where it will not be readily subjected to tampering by unauthorized personnel The use of accessory eq...

Page 2: ...he Self test Self diagnostics option do not require DIP switch adjustment 6 Connect the battery to the PCB Red goes to positive and black goes to negative Fig 2 7 Route the wires out through the canopy 8 Slide the homeplate assembly back into the housing 9 Slide the panel assembly into the housing 10 Install the test button and LED indicator in the end cap Fig 3 11 Secure the end cap assembly usin...

Page 3: ...lies flat Incorrect placement of the lock nut may result in failure 4 Guide the pendant canopy onto the extension rod in the orientation shown Once in place at the top of the extension rod tighten the set screw of the pendant canopy to secure 5 Thread a lock nut on the bottom end of the extension rod Tighten the lock nut so it is not able to spin freely 6 Punch out the center knockout of the J box...

Page 4: ...sing by inserting the tab of the J box into the bridge lance and securing with a 6 32 x 1 4 screw provided Attach the hanger bars to the sides of the recessed housing using 6 32 screws and wing nuts 6 Install the recessed assembly a If ceiling mounting position the recessed assembly between joists making sure the hanger bars are positioned correctly Use the adjusting slots to guide the hanger bars...

Page 5: ...te 10 Secure the trimplate panel assembly to recessed housing with 2 6 32 X 3 4 screws Electrical Connections All electrical connections should be made inside the junction box Make electrical connection as follows 120VAC 220 230VAC 277VAC White Common White Common White Common Black 120VAC Yellow 220 230VAC Orange 277VAC Note Cap unused leads to prevent shorting Panel Assembly Test Button and LED ...

Page 6: ...is turned off The red CHRG ON LED indicates that the battery is under full charge Note The STEADY STATE and CHRG ON LEDs will toggle faster with a discharged battery A fully charged battery will cause the yellow STEADY STATE LED to be illuminated longer than the red CHRG ON LED The green AC ON LED indicates that normal AC power is being supplied to the EXIT sign Test Button Features MANUAL TEST Pr...