Operation

The battery in this unit may not be fully charged. After electricity is connected to the unit for at least 24 hours, then normal 

operation of this unit should take effect. To check, press the “TEST” button. The EXIT sign should stay illuminated.

In accordance with NFPA 101, your emergency lighting system must be tested monthly for a minimum of 30 seconds and 

annually for 90 minutes. Refer to your local codes for any additional requirements that may apply.

Testing and Reporting Instructions (-G2 and -G3 models)

1. Dual color LED lamp indicator shows the following status:

      •  Green color: On / Ready

                              blinking: Testing

      •  Red color: (Service Alert)

      •  Service Alert LED Code (Red color LED lamp indicator)

      Note:

 After solving the fault of emergency equipment, please press test button for 2 seconds then release to 

      reset. LED indicator will show green.

2. “-G2” and “-G3” models also have a manual test function,  press test button as follows:

Networking Operations for “-G3” Models

Model with "-G3" suffix is our world winning design equipped with "wireless testing and reporting" features. Unit that 

has "-G3" suffix in its model number is capable of joining 

Guardian 

emergency lighting management system. It will be 

part of a large testing system to be tested and report result wirelessly. 

Once powered up and commissioning allowed, unit will automatically join 

Guardian

 network and get provisioned. Upon 

the completion of the commissioning,unit will perform testing and report based on set schedules. 

For more information about commissioning, configurations and testing, please visit website, 

https://www.barronltg.com 

for details.  

If you have problem to initiate provisioning or if you know the unit belongs to other 

Guardian

 network. Please follow the 

instructions below to reset the fixture and make it in a factory state: 

      •  

Press and hold the test button for over 8 seconds, and the fixture will leave the network and reset itself.

Press test button once

Press test button twice within 2 seconds

Press test button 3 times within 2 seconds

Press test button 4 times within 2 seconds

3 minutes 

discharge 

test

30 minutes 

discharge

 test

90 minutes 

discharge

 test

30 seconds 

discharge 

test

● ●

● ● ●

● ● ● ●

One blink,

Two blinks,
Three blinks,

Four blinks,

4 second pause

Battery is not connected
Battery voltage too low

Charger board circuit failure

Transfer function failure

4 second pause
4 second pause
4 second pause

● ● ● ● ● ● ●

Seven blinks, 4 second pause

LED strip failure 

 

Summary of Contents for EXITRONIX 400WX Series

Page 1: ...o not use outdoors Equipment should be mounted in locations and at heights where it will not be readily subjected to tampering by unauthorized personnel The use of accessory equipment not recommended by the manufacturer may cause an unsafe condition Any modification or use of non original components will void the warranty and product liability Do not use this equipment for other than intended use ...

Page 2: ...ith the housing Note The additional EXIT panel does not have any clips 4 Secure canopy to the housing using hole numbers 2 and 3 on the canopy with provided canopy screws 2 10 24 screws 5 Feed AC supply leads through top or side hole on the housing and the crossbar then make the proper supply lead connections If using 120VAC connect the black and white leads to the building utility If using 277VAC...

Page 3: ...e back plate Then remove the oblong knock outs on the back plate that correspond to the junction box holes to be used The knock out holes will be easily removed when it is removed from the outside of the back plate Fig 7 3 Feed AAC supply leads through the center hole on the back plate then make the proper lead connections If using 120VAC connect the black and white leads to the building utility I...

Page 4: ...ar screws not provided Fig 6 BACK MOUNTING 1 Housing 2 EXIT panel 3 Back plate 4 Red or Green diffuser 5 Housing screws 6 Wire nuts 7 Junction box Building utility 8 Crossbar screws not provided NOTE First remove the diffuser then knock out the chosen chevron frame from the EXIT panel gently 7 8 400WX Series Installation Instructions XXXXXXXX REV 1 07 23 4 800 533 3948 www barronltg com ...

Page 5: ...s Unit that has G3 suffix in its model number is capable of joining Guardian emergency lighting management system It will be part of a large testing system to be tested and report result wirelessly Once powered up and commissioning allowed unit will automatically join Guardian network and get provisioned Upon the completion of the commissioning unit will perform testing and report based on set sch...

Reviews: