START UP

IMPORTANT INSTALLER NOTE

For improved start up performance wash the indoor coil
with a dish washing detergent.

HIGH PRESSURE SWITCH

The YA484 and YA602 models are supplied with a
remote reset high pressure switch.  If tripped, this
pressure switch may be reset by turning the thermostat
off then back on again.

THREE PHASE SCROLL COMPRESSOR

START UP INFORMATION

Scroll compressors, like several other types of
compressors, will only compress in one rotational
direction.  Direction of rotation is not an issue with
single phase compressors since they will always start
and run in the proper direction.

However, three phase compressors will rotate in either
direction depending upon phasing of the power.  Since
there is a 50-50 chance of connecting power in such a
way as to cause rotation in the reverse direction,
verification of proper rotation must be made.
Verification of proper rotation direction is made by
observing that suction pressure drops and discharge
pressure rises when the compressor is energized.
Reverse rotation also results in an elevated sound level
over that with correct rotation, as well as, substantially
reduced current draw compared to tabulated values.

Verification of 

proper rotation

 must be made at the

time the equipment is put into service.  If improper
rotation is corrected at this time, there will be no
negative impact on the durability of the compressor.
However, reverse operation for over one hour may have
a negative impact on the bearing due to oil pump out.

NOTE: If compressor is allowed to run in reverse rotation

for several minutes, the compressor’s internal
protector will trip.

All three phase ZR compressors are wired identically
internally.  As a result, once the correct phasing is
determined for a specific system or installation,
connecting properly phased power leads to the same
Fusite terminal should maintain proper rotation
direction.

The direction of rotation of the compressor may be
changed by reversing any two line connections to the
unit.

PHASE MONITOR

All units with three phase scroll compressors are
equipped with a 3 phase line monitor to prevent
compressor damage due to phase reversal.

The phase monitor in this unit is equipped with two
LEDs.  If the Y signal is present at the phase monitor
and phases are correct the green LED will light.

If phases are reversed, the red fault LED will be lit and
compressor operation is inhibited.

If a fault condition occurs, reverse two of the supply
leads to the unit.  Do not reverse any of the unit factory
wires as damage may occur.

CONDENSER FAN OPERATION

The condenser fan motor on 230/208 volt, one and three
phase, 60 HZ units is a two-speed motor that comes
factory wired on high speed for peak performance.  If
ambient conditions permit, it can be reconnected to low
speed (red wire) for lower sound level.  See wiring
diagram.

50 HZ models must have fan wired on low speed.
These models are factory wired on low speed.

SERVICE HINTS

1. Caution homeowner to maintain clean air filters at

all times.  Also, not to needlessly close off supply

and return air registers.  This reduces air flow

through the system, which shortens equipment
service life as well as increasing operating costs.

2. Switching to heating cycle at 75° F or higher outside

temperature may cause a nuisance trip of the remote

reset high pressure switch.  Turn thermostat off then
on to reset the high pressure switch.

3. Check all power fuses or circuit breakers to be sure

they are the correct rating.

4. Periodic cleaning of the outdoor coil to permit full

and unrestricted airflow circulation is essential.

Summary of Contents for YA423

Page 1: ...INSTALLATION INSTRUCTIONS WALL MOUNTED PACKAGE AIR CONDITIONERS MODELS YA423 YA484 YA602 Manual 2100 459 Supersedes Date 06 20 05 Copyright 2005...

Page 2: ...17 Table 9 Maximum EXP Electric Heat Only 17 Table 10 Pressure Table 18 Table 11 Optional Accessories 19 Getting Other Information and Publications 1 Wall Mount General Information Heat Pump Wall Moun...

Page 3: ...ACCA Manual D Winter and Summer Air Conditioning and Equipment Selection FOR MORE INFORMATION CONTACT THESE PUBLISHERS ACCA Air Conditioning Contractors of America 1712 New Hampshire Ave N W Washingt...

Page 4: ...4 0 3 4 1 6 5 7 3 0 0 1 6 4 0 2 2 3 8 0 6 2 8 6 1 2 7 0 0 2 1 5 NOTE All vent options are without exhaust capability May require separate field supplied barometric relief in building MODEL NUMBER CON...

Page 5: ...e H H y l p p u S n r u t e R E F G I J K L M N O P Q R S T A B C B 2 4 A Y 8 4 A Y 0 6 A Y 5 7 0 2 4 2 3 4 2 2 5 7 8 4 8 8 8 9 8 8 9 2 8 8 5 1 8 8 9 2 8 8 3 4 0 1 9 1 6 6 1 3 0 0 0 3 8 6 2 3 4 9 6 2...

Page 6: ...8 0 2 0 3 2 1 1 1 2 r o 1 2 r o 1 5 3 5 3 9 5 5 8 0 1 1 0 5 0 5 0 6 0 9 0 1 1 8 8 6 4 2 0 1 0 1 0 1 8 6 A N A N A N 6 5 6 5 A N A N A N 6 2 2 5 A N A N A N 0 6 0 6 A N A N A N 0 3 0 6 A N A N A N 6 6...

Page 7: ...sdiction should be consulted before the installation is made See Page 1 for information on codes and standards Size of unit for a proposed installation should be based on heat loss calculation made ac...

Page 8: ...esign air flow requirement of the equipment Air Conditioning Contractors of America ACCA is an excellent guide to proper sizing All duct work or portions thereof not in the conditioned space should be...

Page 9: ...erial If a combustible wall use a minimum of 30 x 10 dimensions for sizing However it is generally recommended that a 1 inch clearance is used for ease of installation and maintaining the required cle...

Page 10: ...Manual 2100 459 Page 8 FIGURE 3 MOUNTING INSTRUCTIONS...

Page 11: ...required for the first 3 feet of ducting It is important to insure that the 1 4 inch minimum spacing is maintained at all points Failure to do this could result in overheating the combustible materia...

Page 12: ...LL STRUCTURE FACTORY SUPPLIED RAIN FLASHING MOUNT ON UNIT BEFORE INSTALLATION SEE UNIT DIMENSIONS FIGURE 1 FOR ACTUAL DIMENSIONS ATTACH TO TOP PLATE OF WALL 1 000 CLEARANCE ALL AROUND INTERIOR FINISHE...

Page 13: ...Manual 2100 459 Page 11 FIGURE 7 COMMON WALL MOUNTING INSTALLATIONS FREE AIR FLOW NO DUCT DUCTED SUPPLY RETURN AT UNIT FALSE WALL INSTALLATION CLOSET INSTALLATION MIS 550...

Page 14: ...on three phase scroll compressor start ups WIRING LOW VOLTAGE WIRING 230 208V 1 phase and 3 phase equipment dual primary voltage transformers All equipment leaves the factory wired on 240V tap For 208...

Page 15: ...Manual 2100 459 Page 13 FIGURE 8 UNIT 24V TERMINAL BOARD...

Page 16: ...cally internally As a result once the correct phasing is determined for a specific system or installation connecting properly phased power leads to the same Fusite terminal should maintain proper rota...

Page 17: ...cling the wall thermostat resets the manual lockout Low Pressure Switch Bypass and Lockout Sequence If the low pressure switch opens for more than 120 seconds the compressor contactor will de energize...

Page 18: ...D O 2 8 e r u t a r e p m e T 3 2 4 A Y 0 0 4 1 4 5 2 5 6 6 4 6 4 8 4 A Y 0 5 5 1 6 5 4 5 7 6 5 6 2 0 6 A Y 0 0 7 1 5 5 3 5 2 6 0 6 TABLE 7 INDOOR BLOWER PERFORMANCE CFM 230V P S E H n I 2 0 4 8 4 A Y...

Page 19: ...A 0 2 A 0 5 0 5 0 5 0 5 0 5 0 5 0 5 5 4 0 5 0 5 0 5 0 5 0 5 0 5 0 5 5 4 0 5 0 5 0 5 0 5 0 5 0 5 0 5 0 4 0 0 B 9 0 B 5 1 B 8 1 B 0 5 0 5 0 5 0 5 0 5 0 5 0 5 0 5 0 5 0 5 0 5 0 5 0 5 0 5 0 5 0 5 0 5 0 5...

Page 20: ...2 1 8 3 7 2 2 8 0 9 2 3 8 8 0 3 4 8 6 2 3 5 8 6 4 3 B D g e d 5 8 B W g e d 2 7 e d i S w o L e d i S h g i H 8 7 9 1 2 0 8 4 3 2 1 8 9 4 2 3 8 6 6 2 4 8 3 8 2 5 8 0 0 3 6 8 9 1 3 7 8 7 3 3 8 8 8 5 3...

Page 21: ...F c i r t e m o r a B r e p m a D r i A h s e r F d e z i r o t o M X X X X X X X X X X X X X X X X X X X X X X X X X X X 5 V R C 5 M F I E B 5 A V R E W B 5 C V R E W t s u a h x E h t i w r o t a l...

Reviews: