background image

Manual 2100-461
Page

13

IMPORTANT INSTALLER NOTE

For improved start-up performance, wash the indoor coil
with a dishwasher detergent.

HIGH PRESSURE SWITCH

The YA372 models are supplied with a remote reset
high pressure switch.  If tripped, this pressure switch
may be reset by turning the thermostat off then back on
again.

THREE PHASE SCROLL COMPRESSOR

START UP INFORMATION

Scroll compressors, like several other types of
compressors, will only compress in one rotational
direction.  Direction of rotation is not an issue with
single phase compressors since they will always start
and run in the proper direction.

However, three phase compressors will rotate in either
direction depending upon phasing of the power.  Since
there is a 50-50 chance of connecting power in such a
way as to cause rotation in the reverse direction,
verification of proper rotation must be made.  All three
phase units incorporate a phase monitor to ensure proper
field wiring.  See the 

Phase Monitor

 section later in this

manual.

Verification of 

proper rotation

 must be made any time a

compressor is change or rewired.  If improper rotation is
corrected at this time there will be no negative impact on
the durability of the compressor.  However, reverse
operation for over one hour may have a negative impact
on the bearing due to oil pump out.

NOTE: If compressor is allowed to run in reverse

rotation for several minutes, the compressor's
internal protector will trip.

All three phase ZR3 compressors are wired identical
internally.  As a result, once the correct phasing is
determined for a specific system or installation,
connecting properly phased power leads to the same
Fusite terminal should maintain proper rotation
direction.

Verification of proper rotation direction is made by
observing that suction pressure drops and discharge
pressure rises when the compressor is energized.
Reverse rotation also results in an elevated sound level
over that with correct rotations, as well as, substantially
reduced current draw compared to tabulated values.

START UP

PHASE MONITOR

All units with three phase compressors are equipped
with a 3 phase line monitor to prevent compressor
damage due to phase reversal.

The phase monitor in this unit is equipped with two
LEDs.  If the Y signal is present at the phase monitor
and phases are correct the green LED will light.

If phases are reversed, the red fault LED will be lit and
compressor operation is inhibited.

If a fault condition occurs, reverse two of the supply
leads to the unit.  Do not reverse any of the unit factory
wires as damage may occur.

SERVICE HINTS

1. Caution homeowner to maintain clean air filters at all

times.  Also, not to needlessly close off supply and
return air registers.  This reduces air flow through the
system, which shortens equipment service life as well
as increasing operating costs.

2. Check all power fuses or circuit breakers to be sure

they are the correct rating.

3. Periodic cleaning of the outdoor coil to permit full

and unrestricted airflow circulation is essential.

SEQUENCE OF OPERATION

Cooling—Circuit R-Y makes at thermostat pulling in
compressor contactor, starting the compressor and
outdoor motor.  The G (indoor motor) circuit is
automatically completed on any call for cooling
operation or can be energized by manual fan switch on
subbase for constant air circulation.  On all 230 volt
units there is a one minute off delay on the blower
motor.  460 volt models do not have an off delay.  On a
call for heating, circuit R-W1 make at the thermostat
pulling in heat contact for the strip heat and blower
operation.  On a call for second stage heat, R-W2 makes
bringing on second heat contactor, if so equipped.

The direction of rotation of the compressor may be
changed by reversing any two line connections to the
unit.

Summary of Contents for YA302

Page 1: ... Copyright 2005 Manual No 2100 461 Supersedes Date 06 20 05 INSTALLATION INSTRUCTIONS Models YA302 YA372 WALL MOUNTED PACKAGED AIR CONDITIONER MIS 383 ...

Page 2: ...Voltage Wiring 12 Figure 9 Fan Blade Setting 15 Tables Table 1 Electrical Specifications 2 Table 2 Dimensions of Basic Unit 3 Table 3 Electric Heat Table 4 Table 4 Operating Voltage Range 7 Table 5 Thermostat Wire Size 7 Table 6 Wall Thermostat and Subbase Combinations 7 Table 7 Fan Blade Dimensions 15 Table 8 Suction Line Temperatures 15 Table 9 Indoor Blower Performance 15 Table 10 CFM and ESP 1...

Page 3: ... Manual D Winter and Summer Air Conditioning and Equipment Selection FOR MORE INFORMATION CONTACT THESE PUBLISHERS ACCA Air Conditioning Contractors of America 1712 New Hampshire Avenue NW Washington DC 20009 Telephone 202 483 9370 Fax 202 234 4721 ANSI American National Standards Institute 11 West Street 13th Floor New York NY 10036 Telephone 212 642 4900 Fax 212 302 1286 ASHRAE American Society ...

Page 4: ... y t i c a p m A 1 m u m i x a M l a n r e t x E r o e s u F t k C r e k a e r B 2 d l e i F r e w o P e r i W e z i S 2 d n u o r G e r i W e z i S 3 m u m i n i M t i u c r i C y t i c a p m A 1 m u m i x a M l a n r e t x E e s u F t k C r o r e k a e r B 2 r e w o P d l e i F e z i S e r i W 2 d n u o r G e z i S e r i W T K C A T K C B T K C A T K C B T K C A T K C B T K C A T K C B Z 0 A 2 0...

Page 5: ...W h t p e D D t h g i e H H y l p p u S n r u t e R E F G I J K L M N O P Q R S T A B C B 2 0 3 A Y 2 7 3 A Y 0 2 8 3 5 2 1 7 1 3 6 5 0 7 8 8 7 8 8 7 2 8 8 3 1 8 8 7 2 0 0 0 4 0 5 8 1 5 7 5 2 3 9 7 1 5 7 6 2 5 7 8 2 5 2 9 2 0 0 7 2 5 7 2 9 1 9 3 5 7 2 2 4 1 9 9 1 4 0 0 2 1 0 0 5 FRONT VIEW BACK VIEW SIDE VIEW ...

Page 6: ...mmended guide they do not supersede any national and or local codes in any way Authorities having jurisdiction should be consulted before the installation is made See Page 1 for information on codes and standards Size of unit for a proposed installation should be based on heat loss calculation made according to methods of Air Conditioning Contractors of America ACCA The air duct should be installe...

Page 7: ...y and return must be properly sized for the design air flow requirement of the equipment Air Conditioning Contractors of America ACCA is an excellent guide to proper sizing All duct work or portions thereof not in the conditioned space should be properly insulated in order to both conserve energy and prevent condensation or moisture damage Refer to Table 11 for maximum static pressure available fo...

Page 8: ...igure 6 WIRING MAIN POWER Refer to the unit rating plate for wire sizing information and maximum fuse or HACR Type circuit breaker size Each outdoor unit is marked with a Minimum Circuit Ampacity This means that the field wiring used must be sized to carry that amount of current Depending on the installed KW of electric heat there may be two field power circuits required If this is the case the un...

Page 9: ...d 7 c i n o r t c e l E 3 4 0 3 0 4 8 0 0 2 M C l o o c e g a t s 1 t a e h e g a t s 1 n o o t u a n a F l o o c f f o t a e h m e t s y S WIRING LOW VOLTAGE WIRING 230 208V 1 phase and 3 phase equipment dual primary voltage transformers All equipment leaves the factory wired on 240V tap For 208V operation reconnect from 240V to 208V tap The acceptable operating voltage range for the 240 and 208V...

Page 10: ...nual 2100 461 Page 8 FIGURE 3 MOUNTINGINSTRUCTIONS NOTE It is recommended that a bead of silicone caulking be placed behind the side mounting flanges and under the top flashing at the time of installation ...

Page 11: ...61 Page 9 FIGURE 4 WALL MOUNTINGINSTRUCTIONS FIGURE 5 WALL MOUNTINGINSTRUCTIONS MIS 548 SEE FIGURE 3 MOUNTING INSTRUCTIONS SEE UNIT DIMENSIONS FIGURE 1 FOR ACTUAL DIMENSIONS SEE FIGURE 1 FOR DUCT DIMENSIONS MIS 549 ...

Page 12: ...Manual 2100 461 Page 10 MIS 550 FIGURE 6 COMMONWALL MOUNTINGINSTALLATIONS ...

Page 13: ...NCE MIS 277 WARNING WARNING A minimum of 1 4 inch clearance must be maintained between the supply air duct and combustible materials This is required for the first 3 feet of ducting It is important to insure that the 1 4 inch minimum spacing is maintained at all points Failure to do this could result in overheating the combustible material and may result in fire ...

Page 14: ...Manual 2100 461 Page 12 FIGURE 8 LOW VOLTAGE WIRING ...

Page 15: ...essure drops and discharge pressure rises when the compressor is energized Reverse rotation also results in an elevated sound level over that with correct rotations as well as substantially reduced current draw compared to tabulated values START UP PHASE MONITOR All units with three phase compressors are equipped with a 3 phase line monitor to prevent compressor damage due to phase reversal The ph...

Page 16: ...TROL MODULE The compressor control module is optional on the models covered by this manual The compressor control is an anti short cycle lockout timer with high and low pressure switch monitoring and alarm relay output Adjustable Delay On Make And Break Timer On initial power up or any time power is interrupted to the unit the delay on make period begins which will be 2 minutes plus 10 of the dela...

Page 17: ... o C y r D l i o C t e W l i o C y r D l i o C t e W 0 5 9 3 1 5 1 3 1 0 5 9 5 3 9 1 0 4 3 1 0 7 2 1 0 3 9 5 1 9 2 5 8 2 1 0 9 1 1 0 1 9 5 8 8 3 5 0 2 1 0 0 1 1 5 5 8 0 3 8 4 0 1 1 1 0 0 0 1 0 0 8 5 5 7 5 5 0 0 1 0 7 8 TABLE 11 MAXIMUM ESP OF OPERATION ELECTRIC HEAT ONLY l e d o M t e l t u O t n o r F t e l t u O p o T d e e p S w o L d e e p S h g i H d e e p S w o L d e e p S h g i H d e e p S ...

Page 18: ... 8 7 4 4 2 9 7 8 5 2 0 8 5 7 2 1 8 2 9 2 3 8 8 0 3 4 8 7 2 3 5 8 5 4 3 B D g e d 0 8 B W g e d 7 6 e d i S w o L e d i S h g i H 0 8 0 2 2 1 8 5 3 2 3 8 0 5 2 5 8 5 6 2 6 8 2 8 2 7 8 9 9 2 9 8 6 1 3 0 9 5 3 3 1 9 4 5 3 B D g e d 5 8 B W g e d 2 7 e d i S w o L e d i S h g i H 3 8 8 2 2 4 8 3 4 2 6 8 9 5 2 8 8 4 7 2 9 8 2 9 2 0 9 9 0 3 2 9 7 2 3 3 9 7 4 3 4 9 6 6 3 2 7 3 A Y B D g e d 5 7 B W g e d...

Page 19: ... n o C t n e i b m A w o L X X X A 6 1 A M C l o r t n o C e r u s s e r P w o L X X X X A 8 1 A M C C P L C A L X X X 5 1 C M C t i K t r a t S X 5 0 A 3 0 A W H E e g a k c a P r e t a e H 1 X 8 0 A 3 0 A W H E e g a k c a P r e t a e H 1 X 0 1 A 3 0 A W H E e g a k c a P r e t a e H 1 X 5 1 A 3 0 A W H E e g a k c a P r e t a e H 1 X 6 0 B 3 0 A W H E e g a k c a P r e t a e H 1 X X 9 0 B 3 0 A...

Reviews: