background image

Manual 2100-460
Page

9

WIRING — MAIN POWER

Refer to the unit rating plate for wire sizing information
and maximum fuse or “HACR" type circuit breaker
size.  Each outdoor unit is marked with a “Minimum
Circuit Ampacity”.  This means that the field wiring
used must be sized to carry that amount of current.
Depending on the installed KW of electric heat, there
may be two field power circuits required.  If this is the
case, the unit serial plate will so indicate.  All models
are suitable only for connection with copper wire.  Each
unit and/or wiring diagram will be marked “Use Copper
Conductors Only”.  These instructions 

must be

 adhered

to.  Refer to the National Electrical Code (NEC) for
complete current carrying capacity data on the various
insulation grades of wiring material.  All wiring must
conform to NEC and all local codes.

The electrical data lists fuse and wire sizes (75°C
copper) for all models, including the most commonly
used heater sizes.  Also shown are the number of field
power circuits required for the various models with
heaters.

The unit rating plate lists a “Maximum Time Delay
Relay Fuse” or “HACR” type circuit breaker that is to
be used with the equipment.  The correct size must be
used for proper circuit protection and also to assure that
there will be no nuisance tripping due to the momentary
high starting current of the compressor motor.

The disconnect access door on this unit may be locked
to prevent unauthorized access to the disconnect.  To
convert for the locking capability, bend the tab located
in the bottom left hand corner of the disconnect opening
under the disconnect access panel straight out.  This tab
will now line up with the slot in the door.  When shut, a
padlock may be placed through the hole in the tab
preventing entry.

Five (5) wires should be run from thermostat subbase to
the 24V terminal board in the unit.  A five conductor, 18
gauge copper, color-coded thermostat cable is
recommended.  The connection points are shown in
Figure 7.

WIRING — LOW VOLTAGE WIRING

230/208V – 1 phase and 3 phase equipment dual
primary voltage transformers.  All equipment leaves the
factory wired on 240V tap.  For 208V operation,
reconnect from 240V to 208V tap.  The acceptable
operating voltage range for the 240V and 208V taps are:

TAP

RANGE

240

253 – 216

208

220 – 187

TABLE  3

THERMOSTAT WIRE SIZE

r

e

m

r

o

f

s

n

a

r

T

A

V

A

L

F

e

g

u

a

G

e

r

i

W

m

u

m

i

x

a

M

n

i

e

c

n

a

t

s

i

D

t

e

e

F

5

5

3

.

2

e

g

u

a

G

0

2

e

g

u

a

G

8

1

e

g

u

a

G

6

1

e

g

u

a

G

4

1

e

g

u

a

G

2

1

5

4

0

6

0

0

1

0

6

1

0

5

2

NOTE: The voltage should be measured at the field

power connection point in the unit and while
the unit is operating at full load (maximum
amperage operating condition).

TABLE 4

WALL THERMOSTAT and SUBBASE COMBINATIONS

t

a

t

s

o

m

r

e

h

T

e

s

a

b

b

u

S

s

e

r

u

t

a

e

F

e

t

a

n

i

m

o

d

e

r

P

2

0

0

-

3

0

4

8

1

1

1

3

F

7

8

T

3

0

0

-

4

0

4

8

0

2

2

1

A

9

3

5

Q

l

o

o

c

e

g

a

t

s

1

,t

a

e

h

e

g

a

t

s

1

n

o

-

o

t

u

a

:

n

a

F

l

o

o

c

-

ff

o

-

t

a

e

h

:

m

e

t

s

y

S

1

4

0

-

3

0

4

8

C

4

3

0

8

T

-

-

-

l

o

o

c

e

g

a

t

s

1

,t

a

e

h

e

g

a

t

s

1

n

o

-

o

t

u

a

:

n

a

F

l

o

o

c

-

ff

o

-

t

a

e

h

:

m

e

t

s

y

S

9

1

0

-

3

0

4

8

0

6

7

1

C

4

7

8

T

2

1

0

-

4

0

4

8

1

0

0

1

A

4

7

6

Q

t

a

e

h

e

g

a

t

s

2

,l

o

o

c

e

g

a

t

s

1

n

o

-

o

t

u

a

:

n

a

F

l

o

o

c

-

o

t

u

a

-

t

a

e

h

:

m

e

t

s

y

S

1

2

0

-

3

0

4

8

4

3

9

1

D

4

7

8

T

2

1

0

-

4

0

4

8

1

0

0

1

A

4

7

6

Q

t

a

e

h

e

g

a

t

s

2

,l

o

o

c

e

g

a

t

s

2

n

o

-

o

t

u

a

:

n

a

F

l

o

o

c

-

o

t

u

a

-

t

a

e

h

:

m

e

t

s

y

S

9

4

0

-

3

0

4

8

0

8

3

-

3

9

F

1

-

-

-

t

a

e

h

e

g

a

t

s

2

,l

o

o

c

e

g

a

t

s

2

l

o

r

t

n

o

c

n

o

it

a

li

t

n

e

v

/

w

g

n

i

m

m

a

r

g

o

r

p

y

a

d

7

c

i

n

o

r

t

c

e

l

E

3

4

0

-

3

0

4

8

0

0

2

-

M

C

-

-

-

l

o

o

c

e

g

a

t

s

1

,t

a

e

h

e

g

a

t

s

1

n

o

-

o

t

u

a

:

n

a

F

l

o

o

c

-

ff

o

-

t

a

e

h

:

m

e

t

s

y

S

Summary of Contents for YA253

Page 1: ...Model YA253 WALL MOUNTED PACKAGED AIR CONDITIONER INSTALLATION INSTRUCTIONS Manual No 2100 460 Supersedes Date 06 20 05 Copyright 2005 MIS 383...

Page 2: ...frigerant Charge 13 Cooling Pressures 14 Optional Accessories 14 Figures Figure 1 Unit Dimensions 3 Figure 2 Fresh Air Damper Assembly 5 Figure 3 Mounting Instructions 6 Figure 4 Wall Mounting Instruc...

Page 3: ...ystems Load Calculation for ACCA Manual J Residential Winter and Summer Air Conditioning Duct Design for Residential ACCA Manual D Winter and Summer Air Conditioning and Equipment Selection For more i...

Page 4: ...iring must conform to NEC and all local codes 3 These Minimum Circuit Ampacity values are to be used for sizing the field power conductors Refer to the National Electric Code latest revision Article 3...

Page 5: ...e d o M h t d i W W h t p e D D t h g i e H H y l p p u S n r u t e R E F G I J K L M N O P Q R S T A B C B 2 5 2 A Y 0 0 3 3 3 5 2 1 7 1 3 6 5 0 7 8 8 7 8 8 9 1 8 8 1 1 8 8 9 1 0 0 5 3 0 5 8 1 5 7 5...

Page 6: ...1 0 0 8 2 1 8 3 3 3 0 0 3 7 2 8 8 2 5 7 4 0 2 0 1 6 1 4 0 3 1 4 3 2 6 3 0 0 6 5 2 6 4 4 1 0 0 5 0 2 5 2 1 0 6 3 5 1 Size of unit for a proposed installation should be based on heat loss calculation m...

Page 7: ...mmended that Bard Return Air Grille Kit RG 2 through RG 5 or RFG 2 through RFG 5 be installed when no return duct is used Contact distributor or factory for ordering information If using a return air...

Page 8: ...f used 4 Hook top rain flashing under back bend of top Top rain flashing is shipped attached to the back of the unit on the right side 5 Position unit in opening and secure with 5 16 lag bolts use 7 8...

Page 9: ...2100 460 Page 7 FIGURE 4 WALL MOUNTING INSTRUCTIONS MIS 548 MIS 549 SEE FIGURE 3 MOUNTING INSTRUCTIONS FOR OPENING SIZES FIGURE 5 WALL MOUNTING INSTRUCTIONS SEE UNIT DIMENSIONS FIGURE 1 FOR ACTUAL DIM...

Page 10: ...Manual 2100 460 Page 8 MIS 550 FIGURE 6 COMMON WALL MOUNTING INSTALLATIONS...

Page 11: ...he tab preventing entry Five 5 wires should be run from thermostat subbase to the 24V terminal board in the unit A five conductor 18 gauge copper color coded thermostat cable is recommended The connec...

Page 12: ...Manual 2100 460 Page 10 FIGURE 7 LOW VOLTAGE WIRING DIAGRAM...

Page 13: ...ion pressure drops and discharge pressure rises when the compressor is energized Reverse rotation also results in an elevated sound level over that with correct rotations as well as substantially redu...

Page 14: ...ROL MODULE The compressor control module is optional on the models covered by this manual The compressor control is an anti short cycle lockout timer with high and low pressure switch monitoring and a...

Page 15: ...from compressor as shown in Table 6 The suction line temperatures shown in Table 6 are based upon 80 F dry bulb 67 F wet bulb 50 percent R H temperature and rated airflow across the evaporator during...

Page 16: ...d i S h g i H 2 7 2 1 2 3 7 4 2 2 5 7 9 3 2 6 7 4 5 2 8 7 9 6 2 9 7 7 8 2 9 7 5 0 3 1 8 4 2 3 2 8 4 4 3 B D 0 8 B W 7 6 e d i S w o L e d i S h g i H 7 7 7 1 2 8 7 0 3 2 0 8 5 4 2 1 8 0 6 2 3 8 6 7 2...

Reviews: