background image

Manual   2100-361
Page  6

INSTALLATION INSTRUCTIONS

WALL MOUNTING INFORMATION

1. Two holes for the supply and return air openings must

be cut through the wall as shown in Figure 1.

2. On wood frame walls, the wall construction must be

strong and rigid enough to carry the weight of the unit
without transmitting any unit vibration.

       WARING

Fire hazard can result if 1/4 inch clearance to
combustible materials for supply air duct is not
maintained.  See Figure 2.

3. Concrete block walls must be thoroughly inspected to

insure that they are capable of carrying the weight of
the installed unit.

MOUNTING THE UNIT

1. These units are secured by wall mounting brackets

which secure the unit to the outside wall surface at
both sides.  A bottom mounting bracket is provided
for ease of installation, but is not required.

2. The unit itself is suitable for 0 inch clearance, but the

supply air duct flange and the first 3 feet of supply air
duct require a minimum of 1/4 inch clearance to
combustible material.  If a combustible wall use a
minimum of 30-1/2” x 10-1/2” dimensions for sizing.
However it is generally recommended that a 1 inch
clearance is used for ease of installation and
maintaining the required clearance to combustible
material.  The supply air opening would then be
32” x 12”.  See Figures 2 and 3 for details.

        WARNING

Failure to provide the 1/4 inch clearance
between the supply duct and a combustible
surface for the first 3 feet of duct can result in
fire causing damage, injury or death.

3. Locate and mark lag bolt locations and bottom

mounting bracket location.  See Figure 2.

4. Mount bottom mounting bracket.

5. Hook top rain flashing under back bend of top.  Top

rain flashing is shipped secured to the right side of the
back.

6. Position unit in opening and secure with 5/16 lag

bolts; use 7/8 inch diameter flat washers on the lag
bolts.

7. Secure rain flashing to wall and caulk across entire

length of top.  See Figure 2.

8. For additional mounting rigidity, the return air and

supply air frames or collars can be drilled and
screwed or welded to the structural wall itself
(depending upon wall construction).  Be sure to
observe required clearance if combustible wall.

9. On side by side installations, maintain a minimum of

20 inches clearance on right side to allow access to
control panel and heat strips, and to allow proper
airflow to the outdoor coil. Additional clearance may
be required to meet local or national codes.

Summary of Contents for WL7013

Page 1: ...IONS WALL MOUNTED PACKAGE AIR CONDITIONERS MODEL WL7013 Manual 2100 361 Supersedes File Volume III Tab 16 Date 01 26 2000 Bard Manufacturing Company Bryan Ohio 43506 Since 1914 Moving ahead just as pl...

Page 2: ...Rated ESP 15 Table 9 Maximum ESP of Operation Electric Heat Only 15 Table 10 Pressure Table 16 Getting Other Information and Publications 1 Wall Mount General Information 2 Air Conditioning Wall Mount...

Page 3: ...Manual D Winter and Summer Air Conditioning and Equipment Selection For more information contact these publishers ACCA Air Conditioning Contractors of America 1712 New Hampshire Ave N W Washington DC...

Page 4: ...U T B 0 9 7 1 2 0 0 6 0 3 7 8 1 0 3 0 3 2 0 0 1 6 1 4 0 3 1 4 3 2 6 3 0 0 6 5 2 MODEL NUMBER CONTROL MODULES CAPACITY 60 5 Ton VOLTS PHASE A 230 208 60 1 B 230 208 60 3 REVISIONS KW VENTILATIONOPTIONS...

Page 5: ...Manual 2100 361 Page 3 FIGURE 1 UNIT DIMENSIONS MIS 1456...

Page 6: ...ould be checked for external signs of shipping damage If damage is found the receiving party must contact the last carrier immediately preferably in writing requesting inspection by the carrier s agen...

Page 7: ...ient size to allow a maximum velocity of 400 fpm A 1 4 inch clearance to combustible material for the first three feet of duct attached to the outlet air frame is required See Wall Mounting Instructio...

Page 8: ...that a 1 inch clearance is used for ease of installation and maintaining the required clearance to combustible material The supply air opening would then be 32 x 12 See Figures 2 and 3 for details WAR...

Page 9: ...Manual 2100 361 Page 7 FIGURE 2 MOUNTING INSTRUCTIONS MIS 1445...

Page 10: ...RNING A minimum of 1 4 inch clearance must be maintained between the supply air duct and combustible materials This is required for the first 3 feet of ducting It is important to insure that the 1 4 i...

Page 11: ...L FRAMING MATERIAL 2 X 4 S 2 X 6 S AND OR STRUCTURAL STEEL THIS STRUCTURAL MEMBER LOCATED TO MATCH STUD SPACING FOR REST OF WALL A SECOND MEMBER MAY BE REQUIRED FOR SOME WALLS RETURN DUCT OPENING SUPP...

Page 12: ...Manual 2100 361 Page 10 FIGURE 6 COMMON WALL MOUNTING INSTALLATIONS MIS 550...

Page 13: ...ive 5 wires should be run from thermostat subbase to the 24V terminal board in the unit A five conductor 18 gauge copper color coded thermostat cable is recommended The connection points are shown in...

Page 14: ...Manual 2100 361 Page 12 FIGURE 7 UNIT 24V TERMINAL BOARD MIS 1373...

Page 15: ...nstallation connecting properly phased power leads to the same Fusite terminal should maintain proper rotation direction The direction of rotation of the compressor may be changed by reversing any two...

Page 16: ...e due to phase reversal The phase monitor in this unit is equipped with two LEDs If the Y signal is present at the phase monitor and phases are correct the green LED will light If phases are reversed...

Page 17: ...E 6 INDOOR BLOWER PERFORMANCE CFM 230V P S E H n I 2 O 3 1 0 7 L W d e e p S h g i H l i o C y r D l i o C t e W 0 1 2 5 7 7 1 5 7 6 1 5 7 5 1 0 0 6 1 5 2 5 1 5 2 4 1 TABLE 8 RATED CFM AND ESP 1 Rated...

Page 18: ...2 7 2 2 7 9 8 2 3 7 5 0 3 4 7 4 2 3 5 7 3 4 3 B D g e d 0 8 B W g e d 7 6 e d i S w o L e d i S h g i H 3 7 0 2 2 3 7 4 3 2 4 7 8 4 2 5 7 3 6 2 6 7 9 7 2 7 7 6 9 2 8 7 3 1 3 9 7 2 3 3 0 8 2 5 3 B D g...

Reviews: