background image

Manual 2100-405A
Page

6 of 18

SHIPPING DAMAGE

Upon receipt of equipment, the carton should be checked
for external signs of shipping damage.  If damage is
found, the receiving party must contact the last carrier
immediately, preferably in writing, requesting inspection
by the carrier’s agent.

GENERAL

The equipment covered in this manual is to be installed
by trained, experienced service and installation
technicians.

The refrigerant system is completely assembled and
charged.  All internal wiring is complete.

The unit is designed for use with or without duct work.
Flanges are provided for attaching the supply and return
ducts.

These instructions explain the recommended method to
install the air cooled self-contained unit and the
electrical wiring connections to the unit.

These instructions and any instructions packaged with
any separate equipment required to make up the entire
air conditioning system should be carefully read before
beginning the installation.  Note particularly “Starting
Procedure” and any tags and/or labels attached to the
equipment.

While these instructions are intended as a general
recommended guide, they do not supersede any national
and/or local codes in any way.  Authorities having
jurisdiction should be consulted before the installation is
made.  See Page 3 for information on codes and
standards.

Size of unit for a proposed installation should be based
on heat loss calculation made according to methods of
Air Conditioning Contractors of America (ACCA).  The
air duct should be installed in accordance with the
Standards of the National Fire Protection Association for
the Installation of Air Conditioning and Ventilating
Systems of Other Than Residence Type, NFPA No.
90A, and Residence Type Warm Air Heating and Air
Conditioning Systems, NFPA No. 90B.  Where local
regulations are at a variance with instructions, installer
should adhere to local codes.

DUCT WORK

Any heat pump is more critical of proper operating
charge and an adequate duct system than a straight air
conditioning unit.  All duct work, supply and return,
must be properly sized for the design airflow
requirement of the equipment.  Air Conditioning
Contractors of America (ACCA) is an excellent guide to
proper sizing.  All duct work or portions thereof not in
the conditioned space should be properly insulated in
order to both conserve energy and prevent condensation
or moisture damage.

Refer to Table 11 for maximum static pressure available
for duct design.

Design the duct work according to methods given by the
Air Conditioning Contractors of America (ACCA).
When duct runs through unheated spaces, it should be
insulated with a minimum of 1 inch of insulation.  Use
insulation with a vapor barrier on the outside of the
insulation.  Flexible joints should be used to connect the
duct work to the equipment in order to keep the noise
transmission to a minimum.

TABLE   3

 ELECTRIC HEAT TABLE

s

l

e

d

o

M

A

-

2

0

3

L

W

A

-

2

7

3

L

W

B

-

2

0

3

L

W

B

-

2

7

3

L

W

C

-

2

0

3

L

W

C

-

2

7

3

L

W

1

-

V

0

4

2

1

-

V

8

0

2

3

-

V

0

4

2

3

-

V

8

0

2

3

-

V

0

6

4

W

K

S

P

M

A

H

U

T

B

S

P

M

A

H

U

T

B

S

P

M

A

H

U

T

B

S

P

M

A

H

U

T

B

S

P

M

A

H

U

T

B

0

.

5

8

.

0

2

5

6

0

,

7

1

1

.

8

1

0

0

8

,

2

1

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

0

.

0

1

6

.

1

4

0

3

1

,

4

3

2

.

6

3

0

0

6

,

5

2

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

0

.

5

1

5

.

2

6

0

0

2

,

1

5

1

.

4

5

0

0

4

,

8

3

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

-

0

.

9

-

-

-

-

-

-

-

-

-

-

-

-

7

.

1

2

0

0

6

,

0

3

7

.

8

1

0

3

0

,

3

2

8

.

0

1

0

0

7

,

0

3

0

.

5

1

-

-

-

-

-

-

-

-

-

-

-

-

2

.

6

3

0

0

2

,

1

5

2

.

1

3

0

0

4

,

8

3

0

.

8

1

0

0

2

,

1

5

Summary of Contents for WL302

Page 1: ...o 2100 405A Supersedes 2100 405 File Volume III Tab 16 Date 07 25 06 Bard Manufacturing Company Inc Bryan Ohio 43506 Since 1914 Moving ahead just as planned Model WL302 WL372 WALL MOUNTED PACKAGED AIR...

Page 2: ...SP 17 Table 11 Maximum ESP of Operation Electric Heat Only 17 Table 12 Cooling Pressure 18 Table 13 Optional Accessories 18 Getting Other Information and Publications For more information contact thes...

Page 3: ...er and Summer Air Conditioning Duct Design for Residential ACCA Manual D Winter and Summer Air Conditioning and Equipment Selection FOR MORE INFORMATION CONTACT THESE PUBLISHERS ACCA Air Conditioning...

Page 4: ...uctors are in a raceway TABLE 1 ELECTRICAL SPECIFICATIONS s l e d o M d e t a R s t l o V s e s a h P o N d l e i F r e w o P s t i u c r i C 3 m u m i n i M t i u c r i C y t i c a p m A 1 m u m i x...

Page 5: ...i W W h t p e D D t h g i e H H y l p p u S n r u t e R E F G I J K L M N O P Q R S T A B C B 2 0 3 L W 1 7 3 L W 0 2 8 3 5 2 1 7 1 3 6 5 0 7 8 8 7 8 8 7 2 8 8 3 1 8 8 7 2 0 0 0 4 0 5 8 1 5 7 5 2 3 9...

Page 6: ...National Fire Protection Association for the Installation of Air Conditioning and Ventilating Systems of Other Than Residence Type NFPA No 90A and Residence Type Warm Air Heating and Air Conditioning...

Page 7: ...tructions and Figures 3 4 and 5 for further details Ducts through the walls must be insulated and all joints taped or sealed to prevent air or moisture entering the wall cavity Any grille that meets t...

Page 8: ...bustible wall 9 On side by side installations maintain a minimum of 20 inches clearance on left side to allow access to heat strips and control panel and to allow proper airflow to the outdoor coil Ad...

Page 9: ...OPERATING VOLTAGE RANGE P A T E G N A R V 0 4 2 6 1 2 3 5 2 V 8 0 2 7 8 1 0 2 2 r e m r o f s n a r T A V A L F e g u a G e r i W m u m i x a M e c n a t s i D t e e F n I 5 5 3 2 e g u a g 0 2 e g u...

Page 10: ...Manual 2100 405A Page 10 of 18 FIGURE 3 MOUNTING INSTRUCTIONS...

Page 11: ...ual 2100 405A Page 11 of 18 FIGURE 4 WALL MOUNTING INSTRUCTIONS FIGURE 5 WALL MOUNTING INSTRUCTIONS SEE FIGURE 3 MOUNTING INSTRUCTIONS FOR OPENING SIZES SEE UNIT DIMENSIONS FIGURE 1 FOR ACTUAL DIMENSI...

Page 12: ...Manual 2100 405A Page 12 of 18 FIGURE 6 COMMON WALL MOUNTING INSTALLATIONS...

Page 13: ...ustible materials This is required for the first 3 feet of ducting It is important to insure that the 1 4 inch minimum spacing is maintained at all points Failure to do this could result in overheatin...

Page 14: ...Manual 2100 405A Page 14 of 18 FIGURE 8 LOW VOLTAGE WIRING...

Page 15: ...urrent draw compared to tabulated values The direction of rotation of the compressor may be changed by reversing any two line connections to the unit START UP PHASE MONITOR All units with three phase...

Page 16: ...CONTROL MODULE The compressor control module is optional on the models covered by this manual The compressor control is an anti short cycle lockout timer with high and low pressure switch monitoring a...

Page 17: ...hes from compressor as shown in the following table A AIRFLOW TABLE 8 SUCTION LINE TEMPERATURES s l e d o M d e t a R w o l f r i A F 5 9 p m e T D O F 2 8 p m e T D O 2 0 3 L W 0 0 0 1 9 5 6 5 6 6 4...

Page 18: ...3 B D g e d 5 8 B W g e d 2 7 e d i S w o L e d i S h g i H 3 8 8 2 2 4 8 3 4 2 6 8 9 5 2 8 8 4 7 2 9 8 2 9 2 0 9 9 0 3 2 9 7 2 3 3 9 7 4 3 4 9 6 6 3 2 7 3 L W B D g e d 5 7 B W g e d 2 6 e d i S w o...

Reviews: