Manual 2100-193
Page 2
WALL MOUNT GENERAL INFORMATION
Heat Pump Wall Mount Model Nomenclature
WH
36 1 –
A
10
X
X
X
X
X
A
VOLTS & PHASE
A - 230/208/60/1
B - 230/208/60/3
C - 460/60/3
MODEL
NUMBER
REVISIONS
CAPACITY
30 - 2 1/2 Ton
36 - 3 Ton
KW
VENTILATION OPTIONS
X - Barometric Fresh Air Damper
(Standard)
B - Blank-off Plate
M - Motorized Fresh Air Damper
V - Commercial Room Ventilator -
Motorized with Exhaust
E - Economizer (Internal - Fully
Modulating with Exhaust
R - Energy Recovery Ventilator -
with Exhaust
FILTER OPTIONS
X - One Inch Throwaway
(Standard)
W - One Inch Washable
P - Two Inch Pleated
COLOR OPTIONS
X - Beige (Standard)
1 - White
2 - Mesa Brown
4 - Buckeye Gray
5 - Desert Brown
8 - Dark Bronze
CONTROL MODULES
COIL OPTIONS
X - Standard
1 - Phenolic Coated Evaporator
2 - Phenolic Coated Condenser
3 - Phenolic Coated Evaporator
and Condenser
OUTLET OPTIONS
X - Front (Standard)
T - Top on WH30 and WH36
Models
NOTE: For 0 KW and circuit breakers (230/208 Volt) or pull disconnects (460 Volt) applications, insert 0Z in the KW field of model
number.
SHIPPING DAMAGE
Upon receipt of equipment, the carton should be
checked for external signs of shipping damage. If
damage is found, the receiving party must contact the
last carrier immediately, preferably in writing,
requesting inspection by the carrier’s agent.
GENERAL
The equipment covered in this manual is to be installed
by trained, experienced service and installation
technicians.
The refrigerant system is completely assembled and
charged. All internal wiring is complete.
The unit is designed for use with or without duct work.
Flanges are provided for attaching the supply and return
ducts.
These instructions explain the recommended method to
install the air cooled self-contained unit and the
electrical wiring connections to the unit.
These instructions and any instructions packaged with
any separate equipment required to make up the entire
heat pump system should be carefully read before
beginning the installation. Note particularly “Starting
Procedure” and any tags and/or labels attached to the
equipment.
While these instructions are intended as a general
recommended guide, they do not supersede any national
and/or local codes in any way. Authorities having
jurisdiction should be consulted before the installation is
made. See Page 1 for information on codes and
standards.
Size of unit for a proposed installation should be based
on heat loss calculations made according to methods of
Air Conditioning Contractors of America (ACCA). The
air duct should be installed in accordance with the
Standards of the National Fire Protection Association
for the Installation of Air Conditioning and Ventilating
Systems of Other Than Residence Type, NFPA No.
90A, and Residence Type Warm Air Heating and Air
Conditioning Systems, NFPA No. 90B. Where local
regulations are at a variance with instructions, installer
should adhere to local codes.
DUCT WORK
Any heat pump is more critical of proper operating
charge and an adequate duct system than a straight air
conditioning unit. All duct work, supply and return,
must be properly sized for the design air flow
requirement of the equipment. Air Conditioning
Contractors of America (ACCA) is an excellent guide to
proper sizing. All duct work or portions thereof not in
the conditioned space should be properly insulated in
order to both conserve energy and prevent condensation
or moisture damage.