background image

Manual

2100-350D

Page

9 of 24

INSTALLATION  INSTRUCTIONS

WALL MOUNTING INFORMATION

1. Two holes, for the supply and return air openings,

must be cut through the wall as shown in Figure 3.

2. On wood-frame walls, the wall construction must

be strong and rigid enough to carry the weight of
the unit without transmitting any unit vibration.
See Figures 5 and 6.    

3. Concrete block walls must be thoroughly inspected

to insure that they are capable of carrying the
weight of the installing unit.  See Figure 5.

MOUNTING THE UNIT

1. These units are secured by wall mounting brackets

which secure the unit to the outside wall surface at
both sides.  A bottom mounting bracket is provided
for ease of installation, but it is not required.

2. The unit itself is suitable for “0” inch clearance, but

the supply air duct flange and the first 3 feet of
supply air duct require a minimum of 1/4 inch
clearance to combustible material.  If a combustible
wall, use a minimum of 28

½

" x 10

½

" dimensions

for sizing.  However, it is generally recommended
that a 1-inch clearance is used for ease of
installation and maintaining the required clearance
to combustible material.  The supply air opening
would then be 30" x 12".  See Figures 3 and 4 for
details.

3. Locate and mark lag bolt locations and bottom

mounting bracket location.  See Figure 4.

4. Mount bottom mounting bracket, if used.

5. Hook top rain flashing under back bend of top.

Top rain flashing is shipped attached to the back of
the unit on the right side.

6. Position unit in opening and secure with 5/16 lag

bolts; use 3/4 inch diameter flat washers on the lag
bolts.

7. Secure rain flashing to wall and caulk across entire

length of top.  See Figure 3.

8. For additional mounting rigidity, the return air and

supply air frames or collars can be drilled and
screwed or welded to the structural wall itself
(depending upon wall construction).  Be sure to
observe required clearance if combustible wall.

9. On side-by-side installations, maintain a minimum

of 20 inches clearance on right side to allow access
to heat strips and control panel, and to allow proper
airflow to the outdoor coil.  Additional clearance
may be required to meet local or national codes.

TYPICAL INSTALLATIONS

See Figure 7 for common ways to install the Wall
Mount unit.

          WARNING

Failure to provide the 1/4 inch clearance
between the supply duct and a combustible
surface for the first three feet of duct can
result in fire causing damage, bodily injury or
death.

Summary of Contents for WH262

Page 1: ...LLATION INSTRUCTIONS WALL MOUNTED PACKAGE HEAT PUMPS Models WH262 WH311 Manual 2100 350D Supersedes 2100 350C File Volume III Tab 17 Date 09 26 07 Bard Manufacturing Company Inc Bryan Ohio 43506 Since...

Page 2: ...an Blade Setting Dimensions 22 Removal of Fan Shroud 22 Refrigerant Charge 22 Pressure Tables 23 Optional Accessories 24 Figures Figure 1 Unit Dimensions 5 Figure 2 Fresh Air Damper Assembly 8 Figure...

Page 3: ...r Air Conditioning Manual N Low Pressure Low Velocity ACCA Manual D or Duct System Design for Winter Manual Q and Summer Air Conditioning FOR MORE INFORMATION CONTACT THESE PUBLISHERS ACCA Air Conditi...

Page 4: ...al Room Ventilator Motorized with Exhaust E Economizer Internal Fully Modulating with Exhaust R Energy Recovery Ventilator Motorized with Exhaust COIL OPTIONS X Standard 1 Phenolic Coated Evaporator 2...

Page 5: ...Manual 2100 350D Page 5 of 24 FIGURE 1 UNIT DIMENSIONS...

Page 6: ...A N A N Z 0 C 2 6 2 H W 3 0 6 4 1 0 1 5 1 4 1 4 1 A N A N A N A N A N A N A N A N Z 0 A 1 1 3 H W 1 8 0 2 0 3 2 1 6 2 0 4 0 1 0 1 A N A N A N A N A N A N A N A N Z 0 B 1 1 3 H W 3 8 0 2 0 3 2 1 0 2 5...

Page 7: ...irflow requirement of the equipment Air Conditioning Contractors of America ACCA is an excellent guide to proper sizing All duct work or portions thereof not in the conditioned space should be properl...

Page 8: ...s required for Department of Energy Energyguide Fact Sheets is based upon the fresh air blank off plate in place and is recommended for maximum energy efficiency FIGURE 2 BLOWER DAMPER ASSEMBLY The bl...

Page 9: ...ustible material The supply air opening would then be 30 x 12 See Figures 3 and 4 for details 3 Locate and mark lag bolt locations and bottom mounting bracket location See Figure 4 4 Mount bottom moun...

Page 10: ...Manual 2100 350D Page 10 of 24 FIGURE 3 MOUNTING INSTRUCTIONS...

Page 11: ...tween the supply air duct and combustible materials This is required for the first three 3 feet of ducting It is important to insure that the 1 4 minimum spacing is maintained at all points Failure to...

Page 12: ...Manual 2100 350D Page 12 of 24 FIGURE 5 WALL MOUNTING INSTRUCTIONS SEE FIGURE 3 MOUNTING INSTRUCTIONS FIGURE 6 WALL MOUNTING INSTRUCTIONS SEE UNIT DIMENSIONS FIGURE 1 FOR ACTUAL DIMENSIONS...

Page 13: ...Manual 2100 350D Page 13 of 24 FIGURE 7 COMMON WALL MOUNTING INSTALLATIONS...

Page 14: ...locked to prevent unauthorized access to the disconnect To convert for the locking capability bend the tab located in the bottom left hand corner of the disconnect opening under the disconnect access...

Page 15: ...eat loss calculation of the building are useful in determining the correct set points OPTIONAL COMPRESSOR CUTOFF THERMOSTAT See Figures 9 and 10 Heat pump compressor operation at outdoor temperatures...

Page 16: ...night set back condition or someone increasing the thermostat set point NOTE Some programmable thermostats do have a built in time delay for pulling in second stage heat when coming off set back condi...

Page 17: ...iminating pressure equalization noise except during defrost are to be used IMPORTANT INSTALLER NOTE For improved start up performance wash the indoor coil with a dishwashing detergent HIGH PRESSURE SW...

Page 18: ...st control board has an option of 30 60 or 90 minute setting All models are shipped from the factory on the 60 minute pin If special circumstances require a change to another time remove the wire from...

Page 19: ...Manual 2100 350D Page 19 of 24 FIGURE 13 DEFROST CONTROL BOARD...

Page 20: ...g i h e h t f I t i u c r i c d e s o l c a s i o t n o d n a f f o r e w o p e l c y C t n e n o p m o c e v i t c e f e d e c a l p e R r o s s e r p m o c e h t t u o k c o l l l i w l o r t n o c...

Page 21: ...507 66418 64399 62449 60565 58745 56985 55284 53640 52051 50514 49028 47590 46200 44855 43554 42295 41077 25 0 26 0 27 0 28 0 29 0 30 0 31 0 32 0 33 0 34 0 35 0 36 0 37 0 38 0 39 0 40 0 41 0 42 0 43 0...

Page 22: ...able 7 for proper subcooling levels for evaluation of proper charge G N I L O O C G N I T A E H l e d o M d e t a R w o l f r i A D O 5 9 e r u t a r e p m e T D O 2 8 e r u t a r e p m e T D O 7 4 e...

Page 23: ...9 8 8 3 2 0 9 4 5 2 1 9 1 7 2 2 9 0 9 2 4 9 9 0 3 5 9 1 3 3 1 1 3 H W B D g e d 5 7 B W g e d 2 6 e d i S w o L e d i S h g i H 3 7 0 9 1 4 7 5 0 2 5 7 0 2 2 6 7 7 3 2 7 7 4 5 2 8 7 2 7 2 8 7 1 9 2 9...

Page 24: ...X X 3 D A F M r e p m a D r i A h s e r F d e z i r o t o M X X X X X X A 3 A V R E W A 3 C V R E W r o t a l i t n e V y r e v o c e R y g r e n E r o t a l i t n e V y r e v o c e R y g r e n E X X...

Reviews: