background image

Manual 2100-516H 

Page 

3 of 19

TABLE  1

DIAGRAM TO USE WITH UNIT AND VENTS

System

Vent

None

CRV, ERV, MFAD

CRVMWH-3

CHCRV-5

EIFM 

Economizer

ECONWM*

CS2000A*

Vent Code

X

R, M, V, P

C

E

T, W, S

Thermostat Programmable Programmable Programmable Programmable Programmable

All

Model Series

No

Yes

No

Yes

No

Yes

No

Yes

No

Yes

Heat Pump

S**H

T**H

W**H

1

1

3 & 4

2

15

14

N/A

5

N/A

13

11

Heat Pump with

Dehumidification

S**H*D

T**H*D

W**H*D

7

6

9 & 10

8

N/A

14

N/A

12

N/A

13

N/A

NOTE:  The voltage should be measured at the field power 

connection point in the unit and while the unit 

is operating at full load (maximum amperage 

operating condition).

WIRING – LOW VOLTAGE WIRING

230/208V, 1 phase and 3 phase equipment dual primary 
voltage transformers.  All equipment leaves the factory 
wired on 240V tap.  For 208V operation, reconnect 
from 240V to 208V tap.  The acceptable operating 
voltage range for the 240V and 208V taps are:

TABLE  3

WALL THERMOSTAT

TABLE  2

OPERATING VOLTAGE RANGE

An 18 gauge copper, color-coded thermostat cable is 
recommended.  The connection points are shown in this 
Manual.  See Table above.

Low Voltage Connection

These units use a grounded 24-volt AC low voltage 
circuit.  

The “

R

” terminal is the 

hot

 terminal and the “

C

” 

terminal is 

grounded

.

G

” terminal is the 

fan input

.

Y

” terminal is the 

compressor input

B

” terminal is the 

reversing valve input

.  The reversing 

valve must be energized for heating mode.

R

” terminal is the 

24 VAC hot

.

C

” terminal is the 

24 VAC grounded

.

LOW VOLTAGE CONNECTIONS

FOR DDC CONTROL

  

Fan Only 

Energize G

  

Cooling Mode 

Energize Y, G

  

Heat Pump Heating 

Energize Y, G, B

  

2nd Stage Heating 

Energize G, W2, Y, B

  

w/Heat Pump (if employed)

  

Ventilation 

Energize G, O1

  

Emergency  Heat 

Energize B, W2, E, G

  

Dehumidification 

Energize W3

L

” terminal is 

compressor lockout output

.  This 

terminal is activated on a high or low pressure trip by the 
electronic heat pump control.  This is a 24 VAC output.

W2

” terminal is 

second stage heat

 (if equipped).

O1

” terminal is the 

ventilation input

.  This terminal 

energizes any factory installed ventilation option.

E

” terminal is the 

emergency heat input

.  This terminal 

energizes the emergency heat relay.

W3

” terminal is the 

dehumidification input

.  This 

terminal energizes compressor, blower and three-way 
valve.

TAP

RANGE

240V

253 – 216

208V

220 – 187

Part Number

Predominate Features

8403-058

(TH5220D1151)

2 stage Cool, 2 stage Heat - Conventional 

1 stage Cool, 2 stage Heat - Heat Pump 

Electronic Non-Programmable

 

Auto or Manual changeover

8403-060

(1120-445)

3 stage Cool; 3 stage Heat

Programmable/Non-Programmable Electronic

HP or Conventional

Auto or Manual changeover

Dehumidification Output

Summary of Contents for WH Series

Page 1: ...INGLE STAGE HEAT PUMPS LOW VOLTAGE CONTROL CIRCUIT WIRING MODELS W H W H D S H S H D T H T H D Manual 2100 516H Supersedes 2100 516G File Volume III Tab 16 Date 03 28 14 Bard Manufacturing Company Inc...

Page 2: ...D CRV ERV Vent Pkg Using Non Prog T Stat No Occupied Signal 13 Figure 10 HP w Dehumidification Sequence Opt MFAD CRV ERV Vent Pkg Using Non Prog T Stat with CO2 Controller 14 Figure 11 Heat Pump w CS2...

Page 3: ...d the C terminal is grounded G terminal is the fan input Y terminal is the compressor input B terminal is the reversing valve input The reversing valve must be energized for heating mode R terminal is...

Page 4: ...able stops Part Number Predominate Features 8403 067 Normally Open SPST relay closes on rise 24V dual wave length sensor Default setting 950ppm adjustable to 0 2000ppm Default off setting 1000ppm adju...

Page 5: ...1 Unit 1 24V Low Voltage Terminal Block W3 E L DH O1 W2 W1 Y1 B Y R G MIS 2645 C Aux Low Voltage Wiring Diagram C G R Rc Y O B 1 L E W1 E C Bard part 8403 058 TH5220D1151 Thermostat 2 Stage Heat 1 Sta...

Page 6: ...e Wiring Diagram C O B Y1 R G W2 Y O D W1 E Heat Pump with Optional MFAD CRV and ERV Bard part 8403 060 Thermostat Programmable L A Y2 Red Orange Black 2 Brown White Ventilation Packages Electronic Re...

Page 7: ...lack L B when DH Bard part 8403 058 W3 24V Low Voltage Thermostat TH5220D1151 R Red Factory Jumper Installed G ERV Orange Black Brown White CRV Packages Ventilation 1 whenever blower operates Add jump...

Page 8: ...w Voltage Wiring Diagram C O B Y R L AUX Terminal Block E 24V Low Voltage Bard part 8403 058 MFAD Bard part 8403 067 2 Stage Heat 1 Stage Cool Thermostat 1 Red 1 Orange Optional CO Controller Brown Wh...

Page 9: ...Voltage L Purple YO D Y1 1 Factory Jumper Installed 2 be active as first stage cooling Must be configured for economizer with YO D output to These wires are used in special control applications only...

Page 10: ...Y1 W2 Y2 DH L W1 Electronic B YO D Terminal Block Figure 6 Low Voltage Wiring Diagram C O B R G L 24V Low Voltage Bard part 8403 060 Thermostat using Thermostat part 8403 060 Combination Temperature...

Page 11: ...erminal Block TH5220D1151 W3 24V Low Voltage 1 Mechanical Humidistat L W1 Red Yellow 6 5 3 4 1 Factory Jumper Installed Jumper needs to be added Bard part 8403 047 Electronic Humidistat R Y W2 Thermos...

Page 12: ...nal CO controller is used L Y1 DH Y B W1 O1 R W2 2 and fan set to programmed fan for the A output to function 2 2 active for humidity control Must be configured to programmable Red Terminal Black cont...

Page 13: ...47 2 24V Low Voltage Bard part 8403 058 Rc Thermostat Ventilation 2 Stage Heat 1 Stage Cool O1 MFAD ERV Red 1 Black Brown White CRV Black Red Yellow 6 Packages 1 5 Orange 1 Factory Jumper Installed ac...

Page 14: ...8403 058 Jumper needs to be added TH5220D1151 1 Connect Orange wire to G Mechanical Humidistat Black MFAD Thermostat ERV 2 Red Ventilation CRV 1 Stage Optional CO Controller Bard part 8403 038 Factor...

Page 15: ...E WIRES WH SH HEAT PUMP CONNECTION DIAGRAM RC CONTACTS OPEN NORMALLY OPTIONAL DETECTOR MOTION LIGHTING CONTROL CONTROLLER PACKAGE OPTIONAL SETTINGS INSTALLED IN HEAT PUMP BARD P N 8403 058 HP WITH CS2...

Page 16: ...Econ Part 8201 062 W2 W1E R G C Thermostat Part 8403 060 W2 G R C E L O B YOD Y2 Y1 L W1 O B Y WH Unit Y1 Vent Option and 8403 060 Thermostat Dehum Relay Heat Relay Term Strip Economizer Part 8201 062...

Page 17: ...e configured for heat pump multistage no economizer 2 3 Low Voltage Wiring Diagram 2 Y1 W2 L 24V Low Voltage W2 Terminal Block W1 Wiring Harness to enable YO D output to be active as dehumidification...

Page 18: ...mper Installed Unit C G R Y E Y1 W2 W1 O1 DH L B W3 Terminal Block 24V Low Voltage 1 Low Voltage Wiring Diagram C O B Y1 R G W2 Y O D W1 E Bard part 8403 060 Thermostat Programmable L A Y2 Yellow Blac...

Page 19: ...Y L 1 Stage Cool 2 Stage Heat Thermostat TH5220D1151 Bard part 8403 058 AUX G R Rc O B C Low Voltage Wiring Diagram E 1 Unit C Factory Jumper Installed G 2 R E Y1 W2 W1 O1 DH L B Ventilation Y Black W...