background image

Form No.

S3378-1013

Supersedes

S3378-313

Page

9 of 12

Typical Sound Performance with Installation/Isolation Curbs & Acoustical Plenums

WA/L3S Sound Data Matrix (dBA @ 10 feet)

Unit Mounting

Direct

WMICF-5 

Isolation 

Curb

Direct

Direct

WMICF-5 

Isolation 

Curb

WMICF-5 

Isolation 

Curb

Supply Air Treatment

Grille

WAPFB51 

Free Blow 
Supply Air 

Plenum

Standard 

Supply Duct 

Standard 

Supply Duct 

Standard 

Supply Duct 

WAPS51-G 

Supply Air 

Silencer

Return Air Treatment

Grille

WAPR11-X 

Return Air 

Silencer

Grille

WAPR11-X 

Return Air 

Silencer

Blower Only Operation 

with CRV

37.8

30.7

33.6

33.6

27.4

27.6

Compressor Stage 1 

Operation with CRV

51.8

40.7

49.9

41.7

39.7

38.7

Compressor 

Stage 2 Operation

52.3

41.4

50.8

42.4

40.8

39.9

Compressor Stage 2 with 

ERV High Speed Operation

52.7

41.7

51.7

²

²

42.9

Indoor Integrated dBA

43.8

35.0

40.7

37.2

32.8

32.6

Compressor Stage 2 

Outdoor Sound Level

66.9

66.9

66.9

66.9

66.9

66.9

Note 1: dBA is sound pressure measured 10 feet in front of unit and 5 feet above floor.
Note 2: Unit or isolation curb is mounted to frame construction.
Note 3: Results may vary depending upon other factors such as room size, type of construction and acoustical variances.

WAPR11-X Return Air 

Silencer

Ducted  Supply Configuration

Free Blow Configuration

WA/L4S Sound Data Matrix (dBA @ 10 feet)

Unit Mounting

Direct

WMICF-5 

Isolation 

Curb

Direct

Direct

WMICF-5 

Isolation 

Curb

WMICF-5 

Isolation 

Curb

Supply Air Treatment

Grille

WAPFB51 

Free Blow 
Supply Air 

Plenum

Standard 

Supply Duct 

Standard 

Supply Duct 

Standard 

Supply Duct 

WAPS51-G 

Supply Air 

Silencer

Return Air Treatment

Grille

WAPR11-X 

Return Air 

Silencer

Grille

WAPR11-X 

Return Air 

Silencer

Blower Only Operation

40.1

38.9

38.4

34.5

32.8

28.2

Compressor 

Stage 1 Operation

52.0

41.4

50.9

41.2

40.5

39.0

Compressor 

Stage 2 Operation

53.7

44.0

52.9

44.3

42.0

40.5

Compressor Stage 2 with 

ERV High Speed Operation

55.0

46.2

54.0

²

²

44.8

Indoor Integrated dBA

45.4

40.4

44.0

37.8

35.8

33.0

Compressor Stage 2 

Outdoor Sound Level

65.0

65.0

65.0

65.0

65.0

65.0

Note 1: dBA is sound pressure measured 10 feet in front of unit and 5 feet above floor.
Note 2: Unit or isolation curb is mounted to frame construction.
Note 3: Results may vary depending upon other factors such as room size, type of construction and acoustical variances.

Free Blow Configuration

Ducted  Supply Configuration

WAPR11-X Return Air 

Silencer

WA/L5S Sound Data Matrix (dBA @ 10 feet)

Unit Mounting

Direct

WMICF-5 

Isolation 

Curb

Direct

Direct

WMICF-5 

Isolation 

Curb

WMICF-5 

Isolation 

Curb

Supply Air Treatment

Grille

WAPFB51 

Free Blow 
Supply Air 

Plenum

Standard 

Supply Duct 

Standard 

Supply Duct 

Standard 

Supply Duct 

WAPS51-G 

Supply Air 

Silencer

Return Air Treatment

Grille

WAPR11-X 

Return Air 

Silencer

Grille

WAPR11-X 

Return Air 

Silencer

Blower Only Operation

40.3

33.3

35.1

34.8

33.5

31.1

Compressor 

Stage 1 Operation

52.6

40.8

50.6

43.6

40.9

39.9

Compressor 

Stage 2 Operation

56.7

45.3

51.6

46.8

44.5

43.2

Compressor Stage 2 with 

ERV High Speed Operation

57.8

47.1

55.0

²

²

45.4

Indoor Integrated dBA

46.2

37.2

41.8

39.0

37.2

35.4

Compressor Stage 2 

Outdoor Sound Level

65.4

65.4

65.4

65.4

65.4

65.4

Note 1: dBA is sound pressure measured 10 feet in front of unit and 5 feet above floor.
Note 2: Unit or isolation curb is mounted to frame construction.
Note 3: Results may vary depending upon other factors such as room size, type of construction and acoustical variances.

Ducted  Supply Configuration

Free Blow Configuration

WAPR11-X Return Air 

Silencer

Summary of Contents for WA3S

Page 1: ...ressure controls Alarm output for alarm relay Liquid Line Filter Drier Standard on all units Protects system against moisture High Low Pressure Switches are Auto Reset Standard on all units Built in lock out circuit resets from the room thermostat Provides commercial quality protection to the compressor Engineered Features THE WALL MOUNT STEP CAPACITY AIR CONDITIONERS Integrated Part Load Value IP...

Page 2: ...0 4 5 3 0 0 4 5 3 0 0 4 5 3 0 0 0 6 4 0 0 0 6 4 0 0 0 6 4 0 0 5 6 5 0 0 5 6 5 0 0 5 6 5 y t i c a p a C g n i t a e H e l b a T t a e H c i r t c e l E e e S z H 0 6 g n i t a R l a c i r t c e l E 1 8 0 2 0 3 2 3 8 0 2 0 3 2 3 0 6 4 1 8 0 2 0 3 2 3 8 0 2 0 3 2 3 0 6 4 1 8 0 2 0 3 2 3 8 0 2 0 3 2 3 0 6 4 e g n a R e g a t l o V g n i t a r e p O 3 5 2 7 9 1 3 5 2 7 9 1 6 0 5 4 1 4 3 5 2 7 9 1 3 5 ...

Page 3: ...service door and allows outdoor air to be introduced through the air inlet openings The amount of outdoor air varies in response to the system controls and settings defined by the end user It includes a built in exhaust air damper The economizer is designed to provide free cooling when outside air conditions are cool and dry enough to satisfy cooling requirements without running the compressor Thi...

Page 4: ... 5 30 Vent Position Ventilation Airflow CFM Stage 2 Operation Blower Only Stage 1 Operation 0 100 200 300 400 500 600 700 800 900 1000 0 2 5 5 7 5 10 12 5 15 17 5 20 22 5 25 27 5 30 Vent Position Ventilation Airflow CFM Stage 2 Operation Stage 1 Operation Blower Only 0 100 200 300 400 500 600 700 800 900 1000 0 2 5 5 7 5 10 12 5 15 17 5 20 22 5 25 27 5 30 Vent Position Ventilation Airflow CFM Stag...

Page 5: ... 6 5 7 0 6 0 9 0 0 4 9 0 0 4 0 0 6 8 4 0 6 8 4 0 6 5 2 3 6 5 2 3 0 0 6 0 9 2 7 0 9 2 7 0 8 3 7 4 8 3 7 4 0 5 7 0 6 5 7 0 6 0 9 0 0 4 9 0 0 4 0 0 6 8 4 0 6 8 4 0 6 5 2 3 6 5 2 3 0 5 8 0 8 0 9 5 1 3 0 6 8 4 0 3 7 6 2 3 3 5 0 2 9 5 1 3 4 7 3 7 1 5 2 3 6 2 0 5 0 4 5 7 2 2 2 4 7 3 7 1 2 7 6 2 1 0 7 4 1 0 6 0 1 2 0 4 2 3 0 2 8 7 1 0 1 1 4 1 0 7 1 2 9 3 9 1 1 5 7 5 6 4 1 2 0 6 8 4 5 0 6 6 1 2 5 9 3 1 9 5...

Page 6: ...1 1 1 9 2 9 2 8 3 6 5 0 4 0 4 0 4 0 6 0 1 0 1 8 6 0 1 0 1 0 1 0 1 3 S 4 A W 2 S 4 L W Z 0 C 6 0 C 9 0 C 5 1 C 3 0 6 4 1 1 1 1 5 1 6 1 1 2 0 3 0 2 0 2 5 2 0 3 2 1 2 1 0 1 0 1 2 1 2 1 0 1 0 1 3 S 5 A W 2 S 5 L W Z 0 A 5 0 A 8 0 A 0 1 A 5 1 A 0 2 A 1 8 0 2 0 3 2 1 1 1 2 r o 1 2 r o 1 3 r o 1 4 4 4 4 3 5 3 6 9 8 5 1 1 0 5 0 5 0 6 0 7 0 9 0 2 1 8 8 6 6 3 2 0 1 0 1 0 1 8 8 6 4 4 4 4 4 4 6 2 2 5 2 5 6 2 ...

Page 7: ...9 7 2 1 0 6 0 6 4 4 1 8 7 4 0 2 0 5 4 5 2 1 9 5 3 5 1 0 6 2 7 8 7 4 0 2 2 5 5 9 6 0 4 8 8 1 0 8 0 8 3 3 3 4 0 3 7 2 0 0 6 8 8 2 8 7 4 0 2 0 9 0 9 7 1 2 7 1 7 0 3 5 7 6 7 8 1 8 3 0 3 2 0 9 8 0 1 7 1 7 0 3 8 2 8 4 0 1 0 6 2 8 2 0 0 1 0 0 1 7 1 4 0 3 1 4 3 0 5 7 1 6 3 8 9 5 5 2 0 5 1 0 5 1 5 2 6 1 6 3 5 9 1 1 5 5 2 1 1 1 4 5 2 1 3 6 9 3 8 3 0 5 1 0 8 1 5 9 1 1 5 0 8 3 1 3 7 1 9 9 0 7 4 0 0 2 0 0 2 3 ...

Page 8: ...OW SUPPLY AIR PLENUM WMICF5 ISOLATION CURB WAPR11 RETURN AIR ACCOUSTICAL PLENUM Patent Pending MIS 2284 A 9 7 8 1 1 2 13 3 4 42 1 4 3 3 4 1 1 2 3 3 4 1 1 2 3 8 29 7 8 18 1 2 Free Blow Acoustical Plenum WAPFB51 s e i r o s s e c c A n o i t a l l a t s n I l a n o i t p O n o i t p i r c s e D l e d o M r o l o C g n i p p i h S s b L t h g i e W r i A n r u t e R m u n e l P l a c i t s u o c A X ...

Page 9: ...turn Air Silencer Blower Only Operation 40 1 38 9 38 4 34 5 32 8 28 2 Compressor Stage 1 Operation 52 0 41 4 50 9 41 2 40 5 39 0 Compressor Stage 2 Operation 53 7 44 0 52 9 44 3 42 0 40 5 Compressor Stage 2 with ERV High Speed Operation 55 0 46 2 54 0 44 8 Indoor Integrated dBA 45 4 40 4 44 0 37 8 35 8 33 0 Compressor Stage 2 Outdoor Sound Level 65 0 65 0 65 0 65 0 65 0 65 0 Note 1 dBA is sound pr...

Page 10: ... 9 3 0 0 3 0 5 0 0 5 9 3 2 7 5 8 g n i l o o C l a t o T g n i l o o C e l b i s n e S 5 7 3 9 7 5 2 4 6 4 0 5 6 7 7 5 7 8 5 4 0 5 9 5 7 0 5 3 5 4 5 2 2 4 7 5 2 8 4 4 5 2 5 2 7 5 7 2 4 4 0 0 8 0 7 0 5 7 3 4 5 7 2 9 6 5 7 2 3 4 0 5 7 7 6 0 0 8 2 4 5 2 2 6 6 5 2 3 2 4 0 0 7 4 6 0 5 8 1 4 0 5 2 2 6 0 0 1 1 4 5 7 7 9 5 5 2 3 0 4 5 2 3 7 5 5 7 5 9 3 0 5 8 4 5 0 0 8 8 3 l e d o M B W B D 2 y t i c a p a...

Page 11: ...od Disconnect Access Panel C Breaker High Voltage Electrical Drain Side View I J D A C H 2 13 K 11 Economizer Air Intake Hood Brackets Shipping Location Supply Air Opening Return Air Opening Electrical Optional Built In Entrances Mounting Side Wall Top Rain Flashing Bottom Installation Bracket Back View M L O E R S S S S S T N Q B P 44 1 MIS 3210 Electric Heat Air Outlet Front View Filter Access P...

Page 12: ...tor Condenser SUPPLY AIR OUTLET X Front Standard CAPACITY 3S 3 Ton 4S 4 Ton 5S 5 Ton KW VOLTS PHASE A 230 208 60 1 B 230 208 60 3 C 460 60 3 REVISION WA 3 WL 2 FILTER OPTIONS P 2 inch Pleated MERV 8 VENTILATION OPTIONS See Chart Below STD Standard equipment for these specified models 1 HPC High pressure control is auto reset Always used with compressor control module CCM which is included See note...

Reviews: