background image

Manual  2100-404
Page   13

IMPORTANT INSTALLER NOTE

For improved start-up performance, wash the indoor
coil with a dishwasher detergent.

HIGH PRESSURE SWITCH

The WA372 models are supplied with a remote reset
high pressure switch.  If tripped, this pressure switch
may be reset by turning the thermostat off then back on
again.

THREE PHASE SCROLL COMPRESSOR
START UP INFORMATION

Scroll compressors, like several other types of
compressors, will only compress in one rotational
direction.  Direction of rotation is not an issue with
single phase compressors since they will always start
and run in the proper direction.

However, three phase compressors will rotate in either
direction depending upon phasing of the power.  Since
there is a 50-50 chance of connecting power in such a
way as to cause rotation in the reverse direction,
verification of proper rotation must be made. All three
phase units incorporate a phase monitor to ensure proper
field wiring.  See the Phase Monitor section later in this
manual.

Verification of proper rotation must be made any time
a compressor is change or rewired.  If improper rotation
is corrected at this time there will be no negative impact
on the durability of the compressor. However, reverse
operation for over one hour may have a negative impact
on the bearing due to oil pump out.

NOTE: If compressor is allowed to run in reverse

rotation for several minutes, the compressor's
internal protector will trip.

All three phase ZR3 compressors are wired identical
internally.  As a result, once the correct phasing is
determined for a specific system or installation,
connecting properly phased power leads to the  same
Fusite terminal should maintain proper rotation
direction.

Verification of proper rotation direction is made by
observing that suction pressure drops and discharge
pressure rises when the compressor is energized.
Reverse rotation also results in an elevated sound level
over that with correct rotations, as well as, substantially
reduced current draw compared to tabulated values.

START UP

PHASE MONITOR

All units with three phase compressors are equipped
with a 3 phase line monitor to prevent compressor
damage due to phase reversal.

The phase monitor in this unit is equipped with two
LEDs.  If the Y signal is present at the phase monitor
and phases are correct the green LED will light.

If phases are reversed, the red fault LED will be lit and
compressor operation is inhibited.

If a fault condition occurs, reverse two of the supply
leads to the unit.  Do not reverse any of the unit factory
wires as damage may occur.

SERVICE HINTS

1. Caution homeowner to maintain clean air filters at all

times. Also, not to needlessly close off supply and
return air registers. This reduces air flow through the
system, which shortens equipment service life as well
as increasing operating costs.

2. Check all power fuses or circuit breakers to be sure

they are the correct rating.

3. Periodic cleaning of the outdoor coil to permit full

and unrestricted airflow circulation is essential.

SEQUENCE OF OPERATION

Cooling—Circuit R-Y makes at thermostat pulling in
compressor contactor, starting the compressor and
outdoor motor. The G (indoor motor) circuit is
automatically completed on any call for cooling
operation or can be energized by manual fan switch on
subbase for constant air circulation. On all 230 volt
units there is a one minute off delay on the blower
motor.  460 volt models do not have an off delay. On a
call for heating, circuit R-W1 make at the thermostat
pulling in heat contact for the strip heat and blower
operation. On a call for second stage heat, R-W2 makes
bringing on second heat contactor, if so equipped.

The direction of rotation of the compressor may be
changed by reversing any two line connections to the
unit.

Summary of Contents for WA302

Page 1: ...l No 2100 404 Supersedes File Volume III Tab 16 Date 04 01 02 Bard Manufacturing Company Bryan Ohio 43506 Since 1914 moving ahead just as planned Models WA302 WA372 WALL MOUNTED PACKAGED AIR CONDITION...

Page 2: ...9 Fan Blade Setting 15 Tables Table 1 Electrical Specifications 2 Table 2 Dimensions of Basic Unit 3 Table 3 Electric Heat Table 4 Table 4 Operating Voltage Range 7 Table 5 Thermostat Wire Size 7 Tab...

Page 3: ...Manual D Winter and Summer Air Conditioning and Equipment Selection FOR MORE INFORMATION CONTACT THESE PUBLISHERS ACCA Air Conditioning Contractors of America 1712 New Hampshire Avenue NW Washington D...

Page 4: ...e s a h P o N d l e i F r e w o P s t i u c r i C 3 m u m i n i M t i u c r i C y t i c a p m A 1 m u m i x a M l a n r e t x E r o e s u F t k C r e k a e r B 2 d l e i F r e w o P e r i W e z i S 2...

Page 5: ...W h t p e D D t h g i e H H y l p p u S n r u t e R E F G I J K L M N O P Q R S T A B C B 2 0 3 A W 1 7 3 A W 0 2 8 3 5 2 1 7 1 3 6 5 0 7 8 8 7 8 8 7 2 8 8 3 1 8 8 7 2 0 0 0 4 0 5 8 1 5 7 5 2 3 9 7 1...

Page 6: ...mmended guide they do not supersede any national and or local codes in any way Authorities having jurisdiction should be consulted before the installation is made See Page 1 for information on codes a...

Page 7: ...be properly sized for the design air flow requirement of the equipment Air Conditioning Contractors of America ACCA is an excellent guide to proper sizing All duct work or portions thereof not in the...

Page 8: ...e Figure 6 WIRING MAIN POWER Refer to the unit rating plate for wire sizing information and maximum fuse or HACR Type circuit breaker size Each outdoor unit is marked with a Minimum Circuit Ampacity T...

Page 9: ...i n o r t c e l E 3 4 0 3 0 4 8 0 0 2 M C l o o c e g a t s 1 t a e h e g a t s 1 n o o t u a n a F l o o c f f o t a e h m e t s y S WIRING LOW VOLTAGE WIRING 230 208V 1 phase and 3 phase equipment...

Page 10: ...404 Page 8 FIGURE 3 MOUNTINGINSTRUCTIONS NOTE It is recommended that a bead of silicone caulking be placed behind the side mounting flanges and under the top flashing at the time of installation MIS...

Page 11: ...URE 4 WALL MOUNTINGINSTRUCTIONS MIS 549 FIGURE 5 WALL MOUNTINGINSTRUCTIONS MIS 548 MIS 311 MIS 311 MIS 311 SEE FIGURE 3 MOUNTING INSTRUCTIONS SEE UNIT DIMENSIONS FIGURE 1 FOR ACTUAL DIMENSIONS SEE FIG...

Page 12: ...Manual 2100 404 Page 10 MIS 550 FIGURE 6 COMMONWALL MOUNTINGINSTALLATIONS...

Page 13: ...E MIS 277 WARNING WARNING A minimum of 1 4 inch clearance must be maintained between the supply air duct and combustible materials This is required for the first 3 feet of ducting It is important to i...

Page 14: ...Manual 2100 404 Page 12 MIS 1373C FIGURE 8 LOWVOLTAGEWIRING...

Page 15: ...ssure drops and discharge pressure rises when the compressor is energized Reverse rotation also results in an elevated sound level over that with correct rotations as well as substantially reduced cur...

Page 16: ...ROL MODULE The compressor control module is optional on the models covered by this manual The compressor control is an anti short cycle lockout timer with high and low pressure switch monitoring and a...

Page 17: ...l i o C y r D l i o C t e W l i o C y r D l i o C t e W 0 5 9 3 1 5 1 3 1 0 5 9 5 3 9 1 0 4 3 1 0 7 2 1 0 3 9 5 1 9 2 5 8 2 1 0 9 1 1 0 1 9 5 8 8 3 5 0 2 1 0 0 1 1 5 5 8 0 3 8 4 0 1 1 1 0 0 0 1 0 0 8...

Page 18: ...8 7 4 4 2 9 7 8 5 2 0 8 5 7 2 1 8 2 9 2 3 8 8 0 3 4 8 7 2 3 5 8 5 4 3 B D g e d 0 8 B W g e d 7 6 e d i S w o L e d i S h g i H 0 8 0 2 2 1 8 5 3 2 3 8 0 5 2 5 8 5 6 2 6 8 2 8 2 7 8 9 9 2 9 8 6 1 3 0...

Page 19: ...o C t n e i b m A w o L X X X A 6 1 A M C l o r t n o C e r u s s e r P w o L X X X X A 8 1 A M C C P L C A L X X X 5 1 C M C t i K t r a t S X 5 0 A 3 0 A W H E e g a k c a P r e t a e H 1 X 8 0 A 3...

Reviews: