background image

Manual 2100-406A
Page

15 of 16

FAN BLADE SETTING DIMENSIONS

Shown in the drawing below are the correct fan blade
setting dimensions for proper air delivery across the
outdoor coil.

Any service work requiring removal or adjustment in
the fan and/or motor area will require that the
dimensions below be checked and blade adjusted in or
out on the motor shaft accordingly.

TROUBLESHOOTING

Removal of Fan Shroud

1. Disconnect all power to unit.

2. Remove the screws holding both grills – one on each

side of unit – and remove grills.

3. Remove screws holding fan shroud to condenser and

bottom – 9 screws.

4. Unwire condenser fan motor.

5. Slide complete motor, fan blade, and shroud

assembly out the right side of the unit.

6. Service motor/fan as needed.

7. Reverse steps to reinstall.

Refrigerant Charge

The correct system R-22 charge is shown on the unit
rating plate.  Optimum unit performance will occur with
a refrigerant charge resulting in a suction line
temperature 6 inches from compressor) as shown in
Table 6.

The suction line temperatures shown in Table 6 are
based upon 80°F dry bulb/67°F wet bulb (50 percent
R.H.) temperature and rated airflow across the
evaporator during cooling cycle.

"A"

AIRFLOW

TABLE  6

SUCTION LINE TEMPERATURES

l

e

d

o

M

d

e

t

a

R

w

o

l

f

r

i

A

F

°

5

9

D

O

e

r

u

t

a

r

e

p

m

e

T

F

°

2

8

D

O

e

r

u

t

a

r

e

p

m

e

T

3

5

2

A

W

0

0

8

6

5

-

4

5

3

6

-

1

6

TABLE  7

INDOOR BLOWER PERFORMANCE

CFM at 230V

.

P

.

S

.

E

H

n

i

2

O

3

5

2

A

W

V

0

3

2

y

r

D

t

e

W

0

.

1

.

2

.

3

.

0

2

0

1

0

6

9

5

6

8

0

2

8

5

7

9

5

0

9

0

0

8

5

3

7

4

.

5

.

5

3

7

5

1

6

0

5

6

5

3

5

TABLE  8

CFM and ESP

*  Rated CFM and ESP on high speed tap.

l

e

d

o

M

d

e

t

a

R

*

M

F

C

d

e

t

a

R

*

P

S

E

d

e

d

n

e

m

m

o

c

e

R

e

g

n

a

R

w

o

l

f

r

i

A

3

5

2

A

W

0

0

8

0

2

.

0

5

9

-

0

0

7

TABLE  9

MAXIMUM ESP of OPERATION

ELECTRIC HEAT ONLY

Values shown are for units equipped with
standard  1" throwaway filter or 1" washable
filter.  Derate ESP by .15 for 2" pleated filters.

FIGURE 8

FAN BLADE SETTING

TABLE  5

FAN BLADE DIMENSIONS

l

e

d

o

M

A

n

o

i

s

n

e

m

i

D

3

5

2

A

W

0

0

.

1

l

e

d

o

M

P

S

E

3

5

2

A

W

Z

0

A

-

,

0

0

A

-

0

5

.

4

0

A

-

0

5

.

5

0

A

-

0

5

.

8

0

A

-

0

5

.

0

1

A

-

0

5

.

3

5

2

A

W

0

0

B

-

0

5

.

6

0

B

-

0

5

.

Summary of Contents for WA253 Series

Page 1: ...WA253 WALL MOUNTED PACKAGED AIR CONDITIONER INSTALLATION INSTRUCTIONS Manual No 2100 406A Supersedes 2100 406 File Volume III Tab 16 Date 07 25 06 Bard Manufacturing Company Inc Bryan Ohio 43506 Sinc...

Page 2: ...Removal of Fan Shroud 15 Refrigerant Charge 15 Cooling Pressures 16 Optional Accessories 16 Figures Figure 1 Unit Dimensions 5 Figure 2 Fresh Air Damper Assembly 7 Figure 3 Mounting Instructions 8 Fi...

Page 3: ...er and Summer Air Conditioning Duct Design for Residential ACCA Manual D Winter and Summer Air Conditioning and Equipment Selection For more information contact these publishers ACCA Air Conditioning...

Page 4: ...protection of field wiring conductors 2 Based on 75 C copper wire All wiring must conform to NEC and all local codes 3 These Minimum Circuit Ampacity values are to be used for sizing the field power...

Page 5: ...t e R E F G I J K L M N O P Q R S T A B C B 2 5 2 A W 0 0 3 3 3 5 2 1 7 1 3 6 5 0 7 8 8 7 8 8 9 1 8 8 1 1 8 8 9 1 0 0 5 3 0 5 8 1 5 7 5 2 6 5 0 2 5 7 6 2 6 0 8 2 5 2 9 2 0 0 7 2 3 6 2 3 1 4 3 6 0 2 2...

Page 6: ...8 1 0 0 8 2 1 8 3 3 3 0 0 3 7 2 8 8 2 5 7 4 0 2 0 1 6 1 4 0 3 1 4 3 2 6 3 0 0 6 5 2 6 4 4 1 0 0 5 0 2 5 2 1 0 6 3 5 1 Size of unit for a proposed installation should be based on heat loss calculation...

Page 7: ...r Grille Kit RG 2 through RG 5 or RFG 2 through RFG 5 be installed when no return duct is used Contact distributor or factory for ordering information If using a return air filter grille filters must...

Page 8: ...red See Figure 3 INSTALLATION INSTRUCTIONS 3 Mount bottom mounting bracket if used 4 Hook top rain flashing under back bend of top Top rain flashing is shipped attached to the back of the unit on the...

Page 9: ...ual 2100 406A Page 9 of 16 FIGURE 4 WALL MOUNTING INSTRUCTIONS SEE FIGURE 3 MOUNTING INSTRUCTIONS FOR OPENING SIZES FIGURE 5 WALL MOUNTING INSTRUCTIONS SEE UNIT DIMENSIONS FIGURE 1 FOR ACTUAL DIMENSIO...

Page 10: ...Manual 2100 406A Page 10 of 16 FIGURE 6 COMMON WALL MOUNTING INSTALLATIONS...

Page 11: ...bottom left hand corner of the disconnect opening under the disconnect access panel straight out This tab will now line up with the slot in the door When shut a padlock may be placed through the hole...

Page 12: ...Manual 2100 406A Page 12 of 16 FIGURE 7 LOW VOLTAGE WIRING DIAGRAM...

Page 13: ...tion pressure drops and discharge pressure rises when the compressor is energized Reverse rotation also results in an elevated sound level over that with correct rotations as well as substantially red...

Page 14: ...NTROL MODULE The compressor control module is optional on the models covered by this manual The compressor control is an anti short cycle lockout timer with high and low pressure switch monitoring and...

Page 15: ...6 inches from compressor as shown in Table 6 The suction line temperatures shown in Table 6 are based upon 80 F dry bulb 67 F wet bulb 50 percent R H temperature and rated airflow across the evaporato...

Page 16: ...e d i S h g i H 2 7 2 1 2 3 7 4 2 2 5 7 9 3 2 6 7 4 5 2 8 7 9 6 2 9 7 7 8 2 9 7 5 0 3 1 8 4 2 3 2 8 4 4 3 B D 0 8 B W 7 6 e d i S w o L e d i S h g i H 7 7 7 1 2 8 7 0 3 2 0 8 5 4 2 1 8 0 6 2 3 8 6 7...

Reviews: