TABLE  3A — COOLING PRESSURE TABLE

Low side pressure  ± 4 PSIG                                                        

 

High side pressure ± 10 PSIG
Tables are based upon rated CFM (airflow) across the evaporator coil.  If there is any doubt as to correct operating charge being in the system, the charge 

should be removed, system evacuated and recharged to serial plate charge weight.

NOTE:  Pressure table based on high speed condenser fan operation.  If condensing pressures appear elevated check condenser fan wiring.  See 

“Condenser Fan Operation”.

TABLE  3B — HEATING PRESSURES – (ALL TEMPERATURES °F)

MODEL

RETURN

AIR 

TEMP.

PRESSURE

AIR TEMPERATURE ENTERING OUTDOOR COIL

75°

80°

85°

90°

95°

100°

105°

110°

115°

120°

W18H2

75 DB

62 WB

Low Side

High Side

132

292

134

311

137

332

138

353

140

376

142

400

144

424

146

450

148

477

150

505

80 DB

67 WB

Low Side

High Side

141

299

143

319

146

340

148

362

150

386

152

410

154

435

156

462

158

489

160

518

85 DB

72 WB

Low Side

High Side

146

309

148

330

151

352

153

375

155

400

157

424

159

450

161

478

164

506

166

536

W24H2

75 DB

62 WB

Low Side

High Side

124

329

126

351

128

373

131

398

133

423

135

449

137

475

138

503

140

531

142

561

80 DB

67 WB

Low Side

High Side

133

337

135

360

137

383

140

408

142

434

144

460

146

487

148

516

150

545

152

575

85 DB

72 WB

Low Side

High Side

138

349

140

373

142

396

145

422

147

449

149

476

151

504

153

534

155

564

157

595

W30H2

75 DB

62 WB

Low Side

High Side

125

326

128

350

131

373

133

398

136

423

137

448

139

472

141

496

143

522

145

547

80 DB

67 WB

Low Side

High Side

134

334

137

359

140

383

142

408

144

438

147

459

149

484

151

509

153

535

155

561

85 DB

72 WB

Low Side

High Side

139

346

142

372

145

396

147

422

150

449

152

475

154

501

156

527

158

554

160

581

W36H2

75 DB

62 WB

Low Side

High Side

122

329

124

351

126

375

128

399

130

424

132

449

135

476

137

503

138

530

141

559

80 DB

67 WB

Low Side

High Side

131

337

133

360

135

385

137

409

137

444

141

461

144

488

146

516

148

544

151

573

85 DB

72 WB

Low Side

High Side

136

349

138

373

140

398

142

423

144

450

146

477

149

505

151

534

153

563

156

593

W42H2

75 DB

62 WB

Low Side

High Side

127

354

130

372

132

392

134

413

135

437

136

461

137

488

137

516

137

546

136

578

80 DB

67 WB

Low Side

High Side

136

363

139

382

141

402

143

424

143

452

145

473

146

500

146

529

146

560

145

593

85 DB

72 WB

Low Side

High Side

141

376

144

395

146

416

148

439

149

464

150

490

151

518

151

548

151

580

150

614

W48H2

75 DB

62 WB

Low Side

High Side

129

352

132

374

134

398

136

422

137

449

139

476

141

505

143

535

145

566

146

600

80 DB

67 WB

Low Side

High Side

138

361

141

384

143

408

145

433

147

460

149

488

151

518

153

549

155

581

156

615

85 DB

72 WB

Low Side

High Side

143

374

146

397

148

422

150

448

152

476

154

505

156

536

158

568

160

601

161

637

W60H2

75 DB

62 WB

Low Side

High Side

126

332

128

352

131

373

133

397

135

421

137

448

139

476

141

505

143

536

145

568

80 DB

67 WB

Low Side

High Side

135

341

137

361

140

383

142

407

143

434

147

459

149

488

151

518

153

550

155

583

85 DB

72 WB

Low Side

High Side

140

353

142

374

145

396

147

421

149

447

152

475

154

505

156

536

158

569

160

603

MODEL

RETURN

AIR 

TEMP.

PRESSURE

AIR TEMPERATURE ENTERING OUTDOOR COIL

0

5

10

15

20

25

30

35

40

45

50

55

60

W18H2

70

Low Side

High Side

48

290

52

285

56

282

61

282

66

285

72

290

79

297

87

307

95

319

104

334

114

352

124

372

135

394

W24H2

70

Low Side

High Side

57

292

55

296

55

301

57

307

59

314

64

323

70

332

77

342

86

354

96

367

108

380

121

395

135

411

W30H2

70

Low Side

High Side

53

254

53

266

55

278

58

290

61

301

66

312

72

322

80

332

88

342

97

351

108

360

119

369

132

377

W36H2

70

Low Side

High Side

47

281

49

282

51

283

55

287

59

292

64

300

70

308

77

319

85

331

93

345

103

361

113

379

124

398

W42H2

70

Low Side

High Side

50

299

50

300

52

303

54

308

58

314

62

322

68

331

75

342

84

355

93

370

104

386

115

404

128

423

W48H2

70

Low Side

High Side

42

268

45

270

49

274

54

278

59

284

64

291

70

298

77

307

84

317

92

327

100

339

109

352

118

366

W60H2

70

Low Side

High Side

39

294

43

296

47

300

52

305

58

311

63

319

70

328

76

338

84

349

92

362

100

376

109

391

118

408

Summary of Contents for W18H2

Page 1: ...PACKAGE HEAT PUMPS MODELS W18H2 W24H2 W24H2D W30H2 W30H2D W36H2 W36H2D W42H2 W42H2D W48H2 W48H2D W60H2 W60H2D Manual 2100 604 Supersedes NEW File Volume III Tab 17 Date 10 01 13 Bard Manufacturing Co...

Page 2: ...rmance 25 Tables 7 Maximum ESP Electric Heat Only 26 Table 8 Electric Heat 26 Table 9 Optional Accessories 27 Table 10 Vent Control Options 28 Getting Other Information and Publications 3 Wall Mount G...

Page 3: ...ter and Summer Air Conditioning Duct Design for Residential ACCA Manual D Winter and Summer Air Conditioning and Equipment Selection FOR MORE INFORMATION CONTACT THESE PUBLISHERS ACCA Air Conditioning...

Page 4: ...ation on codes and standards Size of unit for a proposed installation should be based on heat loss gain calculation made according to methods of Air Conditioning Contractors of America ACCA The air du...

Page 5: ...G 2W through RG 5W or RFG 2W through RFG 5W be installed when no return duct is used Contact distributor or factory for ordering information If using a return air filter grille filters must be of suff...

Page 6: ...elf is suitable for 0 inch clearance but the supply air duct flange and the first 3 feet of supply air duct require a minimum of 1 4 inch clearance to combustible material for model series W30 W36 W42...

Page 7: ...t factory installed only for W30H and W36H models only FIGURE 2 All dimensions are in inches Dimensional drawings are not to scale W H RIGHT UNIT SIDE VIEW BACK VIEW FRONT VIEW Dimensions of Basic Uni...

Page 8: ...ING ENTIRE LENGTH OF TOP TOP WALL OF CAULKING ALONG PANEL FOAM AIR SEAL WALL STRUCTURE NOTES RAIN FLASHING HEATER ACCESS TOP FLASHING AT TIME OF INSTALLATION THE SIDE MOUNTING FLANGES AND UNDER SILICO...

Page 9: ...CLEARANCE ON ALL RAIN FLASHING COMBUSTIBLE MATERIALS DUCT TOP FLASHING AT TIME OF INSTALLATION 1 4 MIN CLEARANCE FROM REQUIRED DIMENSIONS TO MAINTAIN OPENING ENTIRE LENGTH OF TOP MATERIALS NOTES OF CA...

Page 10: ...4 32 12 5 1 2 2 NOTES WALL STRUCTURE 1 SUPPLY AIR IT IS RECOMMENDED THAT A BEAD OF OPENING Right Side View RAIN FLASHING SILICONE CAULKING BE PLACED BEHIND RECOMMENDED 1 CLEARANCE FROM THE SIDE MOUNTI...

Page 11: ...tible materials This is required for the first 3 feet of ducting It is important to insure that the 1 4 inch minimum spacing is maintained at all points Failure to do this could result in overheating...

Page 12: ...PPLIED RAIN FLASHING SUPPLY AIR MIS 548 A SIDE VIEW I A C K E 1 000 B 1 000 SUPPLY DUCT OVER FRAME INTERIOR FINISHED WALL ALL AROUND DUCT FRAMING MATERIAL EXTERIOR FINISH WALL OPENING FOR ACTUAL DIMEN...

Page 13: ...WALL OPENING W GRILLE SUPPLY DUCT MAYBE LOCATED IN AN ATTIC OR BELOW CEILING RAFTERS AS SHOWN CEILING RAIN RETURN AIR SLEEVE WALL SUPPLY AIR DUCT RAFTERS RAFTERS RETURN AIR OPENING W GRILLE RAIN FALSE...

Page 14: ...circuit breaker that is to be used with the equipment The correct size must be used for proper circuit protection and also to assure that there will be no nuisance tripping due to the momentary high...

Page 15: ...e leaks and recharges R 410A refrigerant is close to being an azeotropic blend it behaves like a pure compound or single component refrigerant The remaining refrigerant charge in the system may be use...

Page 16: ...eral minutes the compressor s internal protector will trip All three phase ZP compressors are wired identically internally As a result once the correct phasing is determined for a specific system or i...

Page 17: ...cumstances require a change to another time remove the wire from the 60 minute terminal and reconnect to the desired terminal Refer to Figure 8 There is a cycle speed up jumper on the control This can...

Page 18: ...28 120 SW 1 SW 2 TIME SEC OFF OFF ON ON OFF ON OFF ON 30 60 180 MIS 2668 A OFF LOW PRESSURE BYPASS TIMER SWITCH FACTORY SETTING 120 SECONDS ACCUMULATED DEFROST TIME TIMER FACTORY SETTING 60 MIN ON FIG...

Page 19: ...e transformer is bad or the unit wiring is incorrect 10 Check for Compressor output signal Is there 24 volts AC between CC C Yes go to Step 12 No go to Step 13 11 No Y compressor input signal Check th...

Page 20: ...16 0 144374 22 0 43554 60 0 15310 98 0 6098 15 0 139576 23 0 42295 61 0 14921 99 0 5961 14 0 134956 24 0 41077 62 0 14544 100 0 5827 13 0 130506 25 0 39898 63 0 14177 101 0 5697 12 0 126219 26 0 38757...

Page 21: ...testing with this refrigerant charge quantity The following pressure tables show nominal pressures for the units Since many installation specific situations can affect the pressure readings this infor...

Page 22: ...573 85 DB 72 WB Low Side High Side 136 349 138 373 140 398 142 423 144 450 146 477 149 505 151 534 153 563 156 593 W42H2 75 DB 62 WB Low Side High Side 127 354 130 372 132 392 134 413 135 437 136 461...

Page 23: ...W24H2 B00 B0Z B06 230 208 3 1 1 17 35 20 40 12 8 12 10 W24H2 C00 C0Z C06 460 3 1 1 11 21 15 25 14 10 14 10 W30H2 A00 A0Z A05 A10 230 208 1 1 1 1 or 2 24 50 76 35 50 80 8 8 4 10 10 8 50 26 50 30 8 10...

Page 24: ...Ckt A Ckt B Ckt A Ckt B W24H2DA00 A0Z A04 A08 230 208 1 1 1 1 or 2 24 44 65 25 50 70 10 8 6 10 10 8 44 21 45 25 8 10 10 10 W24H2DB00 B0Z B06 230 208 3 1 1 17 35 20 40 12 8 12 10 W24H2DC00 C0Z C06 460...

Page 25: ...igh Speed Low Speed High Speed Low Speed Dry Coil Wet Coil Dry Coil Wet Coil Dry Coil Wet Coil Dry Coil Wet Coil Dry Coil Wet Coil Dry Coil Wet Coil Dry Coil Wet Coil Dry Coil Wet Coil 0 1 2 3 4 5 102...

Page 26: ...W24H B00 B06 50 50 W24H C00 C06 50 50 Model Front Outlet Top Outlet Low Speed High Speed Low Speed High Speed W30H W36H A00 A05 A10 A15 50 40 35 35 50 50 40 40 50 40 25 NA 50 50 40 NA W30H W36H B00 B0...

Page 27: ...EHWH36 A05 X EHWH36 A10 X EHWH36 A15 X EHWH03 B06 X EHW36H B06 X EHWH03 B09 X X EHW30H B15 X EHWC03A C06 X X EHWH42 A05 X X EHWH42 A10 X X EHWH42 A15 X X EHWH 04 A20 X X EHWH05 B06 X X EHWH05 B09 X X...

Page 28: ...Commercial Ventilator Power Return X EIFM 3C Economizer X ERVF A3 Energy Recovery Ventilator 230 Volt X ERVF C3 Energy Recovery Ventilator 460 Volt X BFAD 5 Barometric Fresh Air Damper Standard X BOP...

Reviews: