TABLE 3A – Cooling Pressure Table

Low side pressure  ± 4 PSIG                                                         
High side pressure ± 10 PSIG
Tables are based upon rated CFM (airflow) across the evaporator coil.  If there is any doubt as to correct operating charge being in the system, the charge should 
be removed, system evacuated and recharged to serial plate charge weight.

NOTE:  Pressure table based on high speed condenser fan operation.  If condensing pressures appear elevated check condenser fan wiring.  See 

“Condenser Fan Operation”.

TABLE 3B – Heating Pressures (All Temperatures °F)

MODEL

RETURN

AIR 

TEMP.

PRESSURE

AIR TEMPERATURE ENTERING OUTDOOR COIL

75°

80°

85°

90°

95°

100°

105°

110°

115°

120°

W18H2

75 DB

62 WB

Low Side

High Side

132
292

134
311

137
332

138
353

140
376

142
400

144
424

146
450

148
477

150
505

80 DB

67 WB

Low Side

High Side

141
299

143
319

146
340

148
362

150
386

152
410

154
435

156
462

158
489

160
518

85 DB

72 WB

Low Side

High Side

146
309

148
330

151
352

153
375

155
400

157
424

159
450

161
478

164
506

166
536

W24H2

75 DB

62 WB

Low Side

High Side

124
329

126
351

128
373

131
398

133
423

135
449

137
475

138
503

140
531

142
561

80 DB

67 WB

Low Side

High Side

133
337

135
360

137
383

140
408

142
434

144
460

146
487

148
516

150
545

152
575

85 DB

72 WB

Low Side

High Side

138
349

140
373

142
396

145
422

147
449

149
476

151
504

153
534

155
564

157
595

W30H2

75 DB

62 WB

Low Side

High Side

125
326

128
350

131
373

133
398

136
423

137
448

139
472

141
496

143
522

145
547

80 DB

67 WB

Low Side

High Side

134
334

137
359

140
383

142
408

144
438

147
459

149
484

151
509

153
535

155
561

85 DB

72 WB

Low Side

High Side

139
346

142
372

145
396

147
422

150
449

152
475

154
501

156
527

158
554

160
581

W36H2

75 DB

62 WB

Low Side

High Side

122
329

124
351

126
375

128
399

130
424

132
449

135
476

137
503

138
530

141
559

80 DB

67 WB

Low Side

High Side

131
337

133
360

135
385

137
409

137
444

141
461

144
488

146
516

148
544

151
573

85 DB

72 WB

Low Side

High Side

136
349

138
373

140
398

142
423

144
450

146
477

149
505

151
534

153
563

156
593

W42H2

75 DB

62 WB

Low Side

High Side

127
354

130
372

132
392

134
413

135
437

136
461

137
488

137
516

137
546

136
578

80 DB

67 WB

Low Side

High Side

136
363

139
382

141
402

143
424

143
452

145
473

146
500

146
529

146
560

145
593

85 DB

72 WB

Low Side

High Side

141
376

144
395

146
416

148
439

149
464

150
490

151
518

151
548

151
580

150
614

W48H2

75 DB

62 WB

Low Side

High Side

129
352

132
374

134
398

136
422

137
449

139
476

141
505

143
535

145
566

146
600

80 DB

67 WB

Low Side

High Side

138
361

141
384

143
408

145
433

147
460

149
488

151
518

153
549

155
581

156
615

85 DB

72 WB

Low Side

High Side

143
374

146
397

148
422

150
448

152
476

154
505

156
536

158
568

160
601

161
637

W60H2

75 DB

62 WB

Low Side

High Side

126
332

128
352

131
373

133
397

135
421

137
448

139
476

141
505

143
536

145
568

80 DB

67 WB

Low Side

High Side

135
341

137
361

140
383

142
407

143
434

147
459

149
488

151
518

153
550

155
583

85 DB

72 WB

Low Side

High Side

140
353

142
374

145
396

147
421

149
447

152
475

154
505

156
536

158
569

160
603

MODEL

RETURN

AIR 

TEMP.

PRESSURE

AIR TEMPERATURE ENTERING OUTDOOR COIL

0

5

10

15

20

25

30

35

40

45

50

55

60

W18H2

70

Low Side

High Side

48

290

52

285

56

282

61

282

66

285

72

290

79

297

87

307

95

319

104
334

114
352

124
372

135
394

W24H2

70

Low Side

High Side

57

292

55

296

55

301

57

307

59

314

64

323

70

332

77

342

86

354

96

367

108
380

121
395

135
411

W30H2

70

Low Side

High Side

53

254

53

266

55

278

58

290

61

301

66

312

72

322

80

332

88

342

97

351

108
360

119
369

132
377

W36H2

70

Low Side

High Side

47

281

49

282

51

283

55

287

59

292

64

300

70

308

77

319

85

331

93

345

103
361

113
379

124
398

W42H2

70

Low Side

High Side

50

299

50

300

52

303

54

308

58

314

62

322

68

331

75

342

84

355

93

370

104
386

115
404

128
423

W48H2

70

Low Side

High Side

42

268

45

270

49

274

54

278

59

284

64

291

70

298

77

307

84

317

92

327

100
339

109
352

118
366

W60H2

70

Low Side

High Side

39

294

43

296

47

300

52

305

58

311

63

319

70

328

76

338

84

349

92

362

100
376

109
391

118
408

Summary of Contents for W18H2-A

Page 1: ...6H2 B W36H2 C Bard Manufacturing Company Inc Bryan Ohio 43506 www bardhvac com Manual 2100 604A Supersedes 2100 604 Date 2 1 16 W42H2 A W42H2 B W42H2 C W48H2 A W48H2 B W48H2 C W60H2 A W60H2 B W60H2 C...

Page 2: ...25 Tables 7 Maximum ESP Electric Heat Only 26 Table 8 Electric Heat 26 Table 9 Optional Accessories 27 Table 10 Vent and Control Options 28 Getting Other Information and Publications 3 Wall Mount Gene...

Page 3: ...ummer Air Conditioning Duct Design for Residential ACCA Manual D Winter and Summer Air Conditioning and Equipment Selection For more information contact these publishers ACCA Air Conditioning Contract...

Page 4: ...for information on codes and standards Size of unit for a proposed installation should be based on heat loss gain calculation made according to methods of Air Conditioning Contractors of America ACCA...

Page 5: ...ugh RG 5W or RFG 2W through RFG 5W be installed when no return duct is used Contact distributor or factory for ordering information If using a return air filter grille filters must be of sufficient si...

Page 6: ...self is suitable for 0 clearance but the supply air duct flange and the first 3 of supply air duct require a minimum of 1 4 clearance to combustible material for model series W30 W36 W42 W48 and W60 H...

Page 7: ...Optional top outlet factory installed only for W30H and W36H models only FIGURE 2 All dimensions are in inches Dimensional drawings are not to scale W H RIGHT UNIT Dimensions of Basic Unit for Archite...

Page 8: ...ING ENTIRE LENGTH OF TOP TOP WALL OF CAULKING ALONG PANEL FOAM AIR SEAL WALL STRUCTURE NOTES RAIN FLASHING HEATER ACCESS TOP FLASHING AT TIME OF INSTALLATION THE SIDE MOUNTING FLANGES AND UNDER SILICO...

Page 9: ...CLEARANCE ON ALL RAIN FLASHING COMBUSTIBLE MATERIALS DUCT TOP FLASHING AT TIME OF INSTALLATION 1 4 MIN CLEARANCE FROM REQUIRED DIMENSIONS TO MAINTAIN OPENING ENTIRE LENGTH OF TOP MATERIALS NOTES OF CA...

Page 10: ...4 32 12 5 1 2 2 NOTES WALL STRUCTURE 1 SUPPLY AIR IT IS RECOMMENDED THAT A BEAD OF OPENING Right Side View RAIN FLASHING SILICONE CAULKING BE PLACED BEHIND RECOMMENDED 1 CLEARANCE FROM THE SIDE MOUNT...

Page 11: ...ombustible materials This is required for the first 3 of ducting It is important to insure that the 1 4 minimum spacing is maintained at all points Failure to do this could result in overheating the c...

Page 12: ...UPPLIED RAIN FLASHING SUPPLY AIR MIS 548 A SIDE VIEW I A C K E 1 000 B 1 000 SUPPLY DUCT OVER FRAME INTERIOR FINISHED WALL ALL AROUND DUCT FRAMING MATERIAL EXTERIOR FINISH WALL OPENING FOR ACTUAL DIME...

Page 13: ...WALL OPENING W GRILLE SUPPLY DUCT MAYBE LOCATED IN AN ATTIC OR BELOW CEILING RAFTERS AS SHOWN CEILING RAIN RETURN AIR SLEEVE WALL SUPPLY AIR DUCT RAFTERS RAFTERS RETURN AIR OPENING W GRILLE RAIN FALSE...

Page 14: ...er that is to be used with the equipment The correct size must be used for proper circuit protection and also to assure that there will be no nuisance tripping due to the momentary high starting curre...

Page 15: ...iple leaks and recharges R 410A refrigerant is close to being an azeotropic blend it behaves like a pure compound or single component refrigerant The remaining refrigerant charge in the system may be...

Page 16: ...es the compressor s internal protector will trip All three phase ZP compressors are wired identically internally As a result once the correct phasing is determined for a specific system or installatio...

Page 17: ...cycle the outdoor motor stops electric heaters are energized and hot gas passing through the outdoor coil melts any accumulated frost When the temperature rises to approximately 57 F the coil temperat...

Page 18: ...ls for a few seconds can do this Low Pressure Switch Bypass Operation The control has a selectable SW1 low pressure switch bypass set up to ignore the low pressure switch input during the first 30 60...

Page 19: ...ansformer is bad or the unit wiring is incorrect 10 Check for Compressor output signal Is there 24 volts AC between CC C Yes go to Step 12 No go to Step 13 11 No Y compressor input signal Check thermo...

Page 20: ...16 0 144374 22 0 43554 60 0 15310 98 0 6098 15 0 139576 23 0 42295 61 0 14921 99 0 5961 14 0 134956 24 0 41077 62 0 14544 100 0 5827 13 0 130506 25 0 39898 63 0 14177 101 0 5697 12 0 126219 26 0 3875...

Page 21: ...h this refrigerant charge quantity The following pressure tables show nominal pressures for the units Since many installation specific situations can affect the pressure readings this information shou...

Page 22: ...573 85 DB 72 WB Low Side High Side 136 349 138 373 140 398 142 423 144 450 146 477 149 505 151 534 153 563 156 593 W42H2 75 DB 62 WB Low Side High Side 127 354 130 372 132 392 134 413 135 437 136 461...

Page 23: ...H2 B00 B0Z B06 230 208 3 1 1 17 35 20 40 12 8 12 10 W24H2 C00 C0Z C06 460 3 1 1 11 21 15 25 14 10 14 10 W30H2 A00 A0Z A05 A10 230 208 1 1 1 1 or 2 24 50 76 35 50 80 8 8 4 10 10 8 50 26 50 30 8 10 10 1...

Page 24: ...A Ckt B Ckt A Ckt B W24H2DA00 A0Z A04 A08 230 208 1 1 1 1 or 2 24 44 65 25 50 70 10 8 6 10 10 8 44 21 45 25 8 10 10 10 W24H2DB00 B0Z B06 230 208 3 1 1 17 35 20 40 12 8 12 10 W24H2DC00 C0Z C06 460 3 1...

Page 25: ...High Speed Low Speed High Speed Low Speed Dry Coil Wet Coil Dry Coil Wet Coil Dry Coil Wet Coil Dry Coil Wet Coil Dry Coil Wet Coil Dry Coil Wet Coil Dry Coil Wet Coil Dry Coil Wet Coil 0 1 2 3 4 5 10...

Page 26: ...W24H B00 B06 50 50 W24H C00 C06 50 50 Model Front Outlet Top Outlet Low Speed High Speed Low Speed High Speed W30H W36H A00 A05 A10 A15 50 40 35 35 50 50 40 40 50 40 25 NA 50 50 40 NA W30H W36H B00 B...

Page 27: ...EHWH36 A05 X EHWH36 A10 X EHWH36 A15 X EHWH03 B06 X EHW36H B06 X EHWH03 B09 X X EHW30H B15 X EHWC03A C06 X X EHWH42 A05 X X EHWH42 A10 X X EHWH42 A15 X X EHWH 04 A20 X X EHWH05 B06 X X EHWH05 B09 X X...

Page 28: ...3 Commercial Ventilator Power Return X ECONWMS E3B Economizer X ERVF A3 Energy Recovery Ventilator 230 Volt X ERVF C3 Energy Recovery Ventilator 460 Volt X BFAD 5 Barometric Fresh Air Damper Standard...

Reviews: