Bard T36S1-A Installation Instructions Manual Download Page 13

Manual 2100-547J 

Page 

13 of 26

START UP

These units require R-410A refrigerant and Polyol Ester 
oil.

General

1.  Use separate service equipment to avoid cross 

contamination of oil and refrigerants.

2.  Use recovery equipment rated for R-410A 

refrigerant.

3.  Use manifold gauges rated for R-410A (800 

psi/250 psi low).

4.  R-410A is a binary blend of HFC-32 and HFC-

125.

5.  R-410A is nearly azeotropic—similar to R-22 and 

R-12.  Although nearly azeotropic, charge with 
liquid refrigerant.

6.  R-410A operates at 40-70% higher pressure 

than  R-22 and systems designed for R-22 cannot 
withstand this higher pressure.

7.  R-410A has an ozone depletion potential of zero, 

but must be reclaimed due to its global warming 
potential.

8.  R-410A compressors use Polyol Ester oil.
9.  Polyol Ester oil is hygroscopic; it will rapidly absorb 

moisture and strongly hold this moisture in the oil.

10. A liquid line dryer must be used—even a deep 

vacuum will not separate moisture from the oil.

11. Limit atmospheric exposure to 15 minutes.
12. If compressor removal is necessary, always plug 

compressor immediately after removal. Purge with 
small amount of nitrogen when inserting plugs.

Topping Off System Charge

If a leak has occurred in the system, Bard 
Manufacturing recommends reclaiming, evacuating 
(see criteria above) and charging to the nameplate 
charge. If done correctly, topping off the system charge 
can be done without problems.
With R-410A, there are no significant changes in the 
refrigerant composition during multiple leaks and 
recharges. R-410A refrigerant is close to being an 
azeotropic blend (it behaves like a pure compound 
or single component refrigerant). The remaining 
refrigerant charge, in the system, may be used after 
leaks have occurred and then “top-off” the charge by 
utilizing the pressure charts on the inner control panel 
cover as a guideline.

REMEMBER: 

When adding R-410A refrigerant, it must 

come out of the charging cylinder/tank as a liquid to 

avoid any fractionation, and to ensure optimal system 

performance. Refer to instructions for the cylinder that 

is being utilized for proper method of liquid extraction.

Safety Practices

1.  Never mix R-410A with other refrigerants.

2.  Use gloves and safety glasses. Polyol Ester oils can 

be irritating to the skin and liquid refrigerant will 
freeze the skin.

3.  Never use air and R-410A to leak check; the 

mixture may become flammable.

4.  Do not inhale R-410A—the vapor attacks 

the nervous system, creating dizziness, loss 
of coordination and slurred speech. Cardiac 
irregularities, unconsciousness and ultimately 
death can result from breathing this concentration.

5.  Do not burn R-410A. This decomposition produces 

hazardous vapors. Evacuate the area if exposed.

6.  Use only cylinders rated DOT4BA/4BW 400.

7.  Never fill cylinders over 80% of total capacity.

8.  Store cylinders in a cool area, out of direct 

sunlight.

9.  Never heat cylinders above 125°F.

10. Never trap liquid R-410A in manifold sets, gauge 

lines or cylinders. R-410A expands significantly at 
warmer temperatures. Once a cylinder or line is full 
of liquid, any further rise in temperature will cause 
it to burst.

        WARNING

Failure to conform to these practices could 
lead to damage, injury or death.

Summary of Contents for T36S1-A

Page 1: ...B T36S1 C T42S1 A T42S1 B T42S1 C T48S1 A T48S1 B T48S1 C T60S1 A T60S1 B T60S1 C Bard Manufacturing Company Inc Bryan Ohio 43506 www bardhvac com Manual 2100 547J Supersedes 2100 547I Date 5 14 21 T...

Page 2: ...le 7 Indoor Blower Performance 23 Table 8 Dehumidification Relay Logic Board 26 Getting Other Information and Publications 3 Wall Mount General Information 4 Wall Mount Model Nomenclature 4 Shipping D...

Page 3: ...itioning ACCA Manual J Duct Design for Residential Winter and Summer Air Conditioning and Equipment Selection ACCA Manual D For more information contact these publishers ACCA Air Conditioning Contract...

Page 4: ...ion made according to methods of Air Conditioning Contractors of America ACCA The air duct should be installed in accordance with the Standards of the National Fire Protection Association for the Inst...

Page 5: ...hrough RFG5 be installed when no return duct is used Contact distributor or factory for ordering information If using a return air filter grille filters must be of sufficient size to allow a maximum v...

Page 6: ...ction Be sure to observe required clearance if combustible wall Placement 1 On side by side installations maintain a minimum of 20 clearance on right side to allow access to control panel and heat str...

Page 7: ...g brackets after the unit is in its final operating location Remove the side grille to gain access to the compressor shipping brackets The brackets are located on the compressor double isolation base...

Page 8: ...Y AIR IT IS RECOMMENDED THAT A BEAD OF OPENING Right Side View RAIN FLASHING SILICONE CAULKING BE PLACED BEHIND RECOMMENDED 1 CLEARANCE FROM THE SIDE MOUNTING FLANGES AND UNDER TOP FLASHING AT TIME OF...

Page 9: ...rials This is required for the first 3 of ducting It is important to insure that the 1 4 minimum spacing is maintained at all points Failure to do this could result in overheating the combustible mate...

Page 10: ...IR FACTORY SUPPLIED RAIN FLASHING SUPPLY AIR MIS 548 A SIDE VIEW I A C K E 1 000 B 1 000 SUPPLY DUCT OVER FRAME INTERIOR FINISHED WALL ALL AROUND DUCT FRAMING MATERIAL EXTERIOR FINISH WALL OPENING FOR...

Page 11: ...best unit performance and efficiency Review duct grille or return duct work Avoid using restrictive duct work to Unit Mount Return Grille Fixed Blade Wall wall Outside Wall Ducted Installations Adjus...

Page 12: ...under the disconnect access panel straight out This tab will now line up with the slot in the door When shut a padlock may be placed through the hole in the tab preventing entry See Three Phase Scroll...

Page 13: ...ple leaks and recharges R 410A refrigerant is close to being an azeotropic blend it behaves like a pure compound or single component refrigerant The remaining refrigerant charge in the system may be u...

Page 14: ...reverse operation for over 1 hour may have a negative impact on the bearing due to oil pump out NOTE If compressor is allowed to run in reverse rotation for several minutes the compressor s internal...

Page 15: ...com en SCCA07H See the replacement parts manual for replacement core part numbers Defrost Cycle The defrost cycle is controlled by temperature and time on the solid state heat pump control When the o...

Page 16: ...there is likely no actual frost on the outdoor coil in this artificial test condition There is also a 5 minute compressor time delay function built into the HPC This is to protect the compressor from...

Page 17: ...Heat pump control defective Check for 24 V between RV C and B C 1 Check circuit control wiring 2 Replace heat pump control Reversing valve solenoid coil defective Check for open or shorted coil Replac...

Page 18: ...16 0 144374 22 0 43554 60 0 15310 98 0 6098 15 0 139576 23 0 42295 61 0 14921 99 0 5961 14 0 134956 24 0 41077 62 0 14544 100 0 5827 13 0 130506 25 0 39898 63 0 14177 101 0 5697 12 0 126219 26 0 3875...

Page 19: ...ng with this refrigerant charge quantity The following pressure tables show nominal pressures for the units Since many installation specific situations can affect the pressure readings this informatio...

Page 20: ...548 85 deg DB 72 deg WB Low SIde High Side 144 337 146 360 147 384 148 408 149 434 151 459 153 485 154 511 156 539 159 567 T48S 75 deg DB 62 deg WB Low SIde High Side 137 326 138 339 139 356 140 375 1...

Page 21: ...r 2 45 71 97 97 113 60 80 100 100 125 8 4 3 3 2 10 8 8 8 6 45 45 45 45 26 52 52 52 26 50 50 50 50 30 60 60 60 30 8 8 8 8 10 6 6 6 10 10 10 10 10 10 10 10 10 10 T60S1 B00 B0Z B09 B15 B18 230 208 60 3 1...

Page 22: ...or 2 1 or 2 1 or 2 45 71 97 97 113 60 80 100 100 125 8 4 3 3 2 10 8 8 8 6 45 45 45 45 26 52 52 52 26 50 50 50 50 30 60 60 60 30 8 8 8 8 10 6 6 6 10 10 10 10 10 10 10 10 10 10 T60S1DB00 B0Z DB09 DB15 D...

Page 23: ...inches WC shown is with 2 thick disposable filter Blower only CFM is the total air being circulated during continuous fan mode Airflow remains constant Blower only CFM reduces during continuous fan m...

Page 24: ...it s air noise cabinet duct or motor noise interview customer if necessary Air noise High static creating high blower speed Is airflow set properly Does removing filter cause blower to slow down Chec...

Page 25: ...site side of the connector plug and gently pulling the plug out of the connector socket in the control DO NOT PULL ON THE WIRES GRIP THE PLUG ONLY 6 The control module is now completely detached from...

Page 26: ...ied X X X X X X X X Y Y1 B G 2nd Heating Unoccupied X X X X X X X Y Y1 B G O1 2nd Heating Occupied X X X X X X X X X Y Y1 B G O1 W3 2nd Heat Dehum Occupied X X X X X X X X X X X Y Y1 B G W3 2nd Heat D...

Reviews: