Bard SH612 Installation Instructions Manual Download Page 22

Manual 2100-481
Page

22 of 23

REMOVAL OF FAN SHROUD

1. Disconnect all power to the unit.

2. Remove the screws holding both grilles, one on each

side of unit, and remove grilles.

3. Remove screws holding fan shroud to condenser and

bottom.  Nine (9) screws.

4. Unwire condenser fan motor.

5. Slide complete motor, fan blade, and shroud

assembly out the left side of the unit.

6. Service motor/fan as needed.

7. Reverse steps to reinstall.

REFRIGERANT CHARGE

The correct system R-22 charge is shown on the unit
rating plate.  Optimum unit performance will occur with
a refrigerant charge shown on the unit serial plate.

If correct charge is in doubt, recover the refrigerant and
recharge per the charge on the unit rating plate.  See
Table 7 for proper subcooling levels for evaluation of
proper charge.

TABLE 6

FAN BLADE DIMENSION

l

e

d

o

M

A

n

o

i

s

n

e

m

i

D

2

1

6

H

S

"

5

7

.

1

G

N

I

L

O

O

C

G

N

I

T

A

E

H

l

e

d

o

M

d

e

t

a

R

w

o

l

f

r

i

A

D

O

5

9

e

r

u

t

a

r

e

p

m

e

T

D

O

2

8

e

r

u

t

a

r

e

p

m

e

T

D

O

7

4

e

r

u

t

a

r

e

p

m

e

T

D

O

7

1

e

r

u

t

a

r

e

p

m

e

T

2

1

6

H

S

0

5

3

1

9

1

-

6

1

8

1

-

5

1

6

1

-

2

1

8

1

-

4

1

* Rated CFM and ESP on high speed tap.

TABLE  8

RATED CFM & RATED ESP

l

e

d

o

M

d

e

t

a

R

*

M

F

C

d

e

t

a

R

*

P

S

E

d

e

d

n

e

m

m

o

c

e

R

e

g

n

a

R

w

o

l

f

r

i

A

2

1

6

H

S

0

5

3

1

0

2

.

0

0

1

1

5

7

4

1

Subtract .08 static for 2" filter

TABLE  9

INDOOR BLOWER PERFORMANCE

CFM 

@

 230V / 460V

.

P

.

S

.

E

H

n

I

2

O

H

S

2

1

6

d

e

e

p

S

h

g

i

H

d

e

e

p

S

w

o

L

l

i

o

C

y

r

D

l

i

o

C

t

e

W

l

i

o

C

y

r

D

l

i

o

C

t

e

W

0

.

1

.

2

.

3

.

4

.

0

0

8

1

0

0

7

1

0

0

6

1

0

0

5

1

-

-

-

0

5

5

1

0

5

4

1

0

5

3

1

0

5

2

1

-

-

-

0

0

6

1

0

0

5

1

0

0

4

1

5

2

3

1

-

-

-

0

5

3

1

0

5

2

1

0

5

1

1

5

7

0

1

-

-

-

"A"

AIRFLOW

MIS-1724

TABLE  10

MAXIMUM ESP OF OPERATION

d

e

e

p

S

h

g

i

H

d

e

e

p

S

w

o

L

5

0

A

8

0

A

0

1

A

0

2

A

3

.

3

.

3

.

3

.

3

.

3

.

3

.

3

.

9

0

B

3

.

3

.

9

0

C

3

.

3

.

NOTE: SH612 is shipped with the indoor

blower on low speed.  Move to high
speed for high static applications.

FIGURE  15

FAN BLADE SETTING

FAN BLADE SETTING DIMENSIONS

Shown in Figure 15 are the correct fan blade setting
dimensions for proper air delivery across the outdoor
coil.

Any service work requiring removal or adjustment in
the fan and/or motor area will require that the
dimensions below be checked and blade adjusted in or
out on the motor shaft accordingly.

1

Expected subcooling levels during cooling operation.
Above subcooling levels are provided to troubleshoot low
charge or overcharged conditions.  If charge is in doubt,
evacuate and recharge the unit to the refrigerant charge
listed on the serial plate.

TABLE  7  

1

REFRIGERANT CHARGE

SUBCOOLING LEVEL

Summary of Contents for SH612

Page 1: ...3 INSTALLATION INSTRUCTIONS WALL MOUNTED PACKAGE HEAT PUMPS Model SH612 Manual 2100 481 Supersedes NEW File Volume III Tab 17 Date 12 19 07 Bard Manufacturing Company Inc Bryan Ohio 43506 Since 1914 M...

Page 2: ...oor Blower Performance 22 Table 10 Maximum ESP of Operation 22 Table 11 Pressure Table Cooling 23 Table 12 Pressure Table Heating 23 Getting Other Information and Publications For More Information 3 W...

Page 3: ...ter and Summer Air Conditioning Duct Design for Residential ACCA Manual D Winter and Summer Air Conditioning and Equipment Selection FOR MORE INFORMATION CONTACT THESE PUBLISHERS ACCA Air Conditioning...

Page 4: ...2 0 2 2 3 8 0 6 2 8 6 4 2 7 0 0 2 1 5 MODEL NUMBER CONTROL MODULES CAPACITY 61 5 ton VOLTS PHASE A 230 208 60 1 B 230 208 60 3 C 460 60 3 REVISIONS KW VENTILATION OPTIONS X Barometric Fresh Air Dampe...

Page 5: ...NSIONS t i n U h t d i W W h t p e D D t h g i e H H y l p p u S n r u t e R E F G I J K L M N O P Q A B C B 2 1 6 H S 2 4 4 1 2 2 8 7 4 9 8 7 9 8 7 9 2 8 7 5 1 8 7 9 2 8 7 3 4 9 1 8 5 1 4 0 3 6 1 1 1...

Page 6: ...an adequate duct system than a straight air conditioning unit All duct work supply and return must be properly sized for the design airflow requirement of the equipment Air Conditioning Contractors o...

Page 7: ...ordering information If using a return air filter grille filters must be of sufficient size to allow a maximum velocity of 400 fpm FILTERS A 1 inch throwaway filter is supplied with each unit The fil...

Page 8: ...2 x 12 See Figures 3 and 4 for details 3 Locate and mark lag bolt locations and bottom mounting bracket location See Figure 3 4 Mount bottom mounting bracket 5 Hook top rain flashing under back bend o...

Page 9: ...96 A Top flashing detail view Attach supplied rain flashing Apply caulk between flashing and wall Foam air seal Seal with bead of caulking along entire length of top Supply flange Side view of wall wi...

Page 10: ...is required for the first 3 feet of ducting It is important to insure that the 1 4 inch minimum spacing is maintained at all points Failure to do this could result in overheating the combustible mate...

Page 11: ...Manual 2100 481 Page 11 of 23 FIGURE 5 WALL MOUNTING INSTRUCTIONS FIGURE 6 WALL MOUNTING INSTRUCTIONS SEE FIGURE 4 MOUNTING INSTRUCTIONS SEE UNIT DIMENSIONS FIGURE 1 FOR ACTUAL DIMENSIONS...

Page 12: ...Manual 2100 481 Page 12 of 23 FIGURE 7 COMMON WALL MOUNTING INSTALLATIONS...

Page 13: ...e sizing information and maximum fuse or HACR type circuit breaker size Each outdoor unit is marked with a Minimum Circuit Ampacity This means that the field wiring used must be sized to carry that am...

Page 14: ...of the heating equipment to the individual structure Utilization of the heating Application Data and the heat loss calculation of the building are useful in determining the correct set points Temperat...

Page 15: ...r pulling in second stage heat when coming off set back conditions OPTIONAL COMPRESSOR CUTOFF THERMOSTAT See Figures 9 and 10 Heat pump compressor operation at outdoor temperatures below 0 F are neith...

Page 16: ...uired 5 if no ventilation system is installed For proper system operation under Emergency Heat conditions where the compressor needs to be deactivated the B W2 E outputs need to be energized Removing...

Page 17: ...r rewired If improper rotation is corrected at this time there will be no negative impact on the durability of the compressor However reverse operation for over one hour may have a negative impact on...

Page 18: ...the system operating pressures can be observed Pressure tables can be found later in the manual covering all models on both cooling and heating cycles It is imperative to match the correct pressure ta...

Page 19: ...time to elapse Use a small screwdriver or other metallic object or another 1 4 inch QC to short between the SPEEDUP terminals to accelerate the HPC timer and initiate defrost Be careful not to touch...

Page 20: ...c p m u p t a e h n o y a l e r n a f s s o r c a k c e h C l o r t n o c p m u p t a e h e c a l p e R e v i t c e f e d r o t o M r o t o m e c a l p e R g n i d n i w r o t o m d e t r o h s r o n...

Page 21: ...507 66418 64399 62449 60565 58745 56985 55284 53640 52051 50514 49028 47590 46200 44855 43554 42295 41077 25 0 26 0 27 0 28 0 29 0 30 0 31 0 32 0 33 0 34 0 35 0 36 0 37 0 38 0 39 0 40 0 41 0 42 0 43 0...

Page 22: ...e t a R M F C d e t a R P S E d e d n e m m o c e R e g n a R w o l f r i A 2 1 6 H S 0 5 3 1 0 2 0 0 1 1 5 7 4 1 Subtract 08 static for 2 filter TABLE 9 INDOOR BLOWER PERFORMANCE CFM 230V 460V P S E...

Page 23: ...i S h g i H 2 7 1 9 1 4 7 8 0 2 5 7 5 2 2 7 7 2 4 2 8 7 1 6 2 0 8 9 7 2 1 8 8 9 2 1 8 8 1 3 2 8 8 3 3 B D g e d 5 8 B W g e d 2 7 e d i S w o L e d i S h g i H 5 7 8 9 1 7 7 5 1 2 8 7 3 3 2 0 8 0 5 2...

Reviews: