background image

Manual

2100-532B

Page

43 of 46

TROUBLESHOOTING  GE  ECM

 MOTORS CONT’D.

Motor

Motor OK when

R > 100k ohm

ECM 2.0

Only remove

Hex Head Bolts

Connector Orientation

Between 4 and 8 o'clock

Drip Loop

Back of

Control

Figure 5

Winding Test

Figure 4

Note:              
Use the shorter 
bolts and 
alignment pin 
supplied when 
replacing an 
ECM 2.0 
control.

Figure 3

ECM 
2.3/2.5

Power Connector
(5-pin)

Control Connector
(16-pin)

Hex-head Screws

Motor Connector
(3-pin)

Motor Connector
(3-pin)

Control Disassembly

Drip Loop

Push until

Latch Seats
Over Ramp

From Motor

Circuit

Board

Replacing ECM Control Module

To replace the control module for the GE variable-speed indoor blower
motor you need to take the following steps:

1. You MUST have the correct replacement module.  The controls are

factory programmed for specific operating modes.  Even though they look
alike, different modules may have completely different functionality.

USING THE WRONG CONTROL MODULE VOIDS ALL PRODUCT
WARRANTIES AND MAY PRODUCE UNEXPECTED RESULTS.

2. Begin by removing AC power from the furnace or air handler being

serviced.  

DO NOT WORK ON THE MOTOR WITH AC POWER

APPLIED.  

To avoid electric shock from the motor’s capacitors, disconnect

power and wait at least 5 minutes before opening motor.

3. It is usually not necessary to remove the motor from the blower

assembly.  However, it is recommended that the whole blower assembly,
with the motor, be removed from the furnace/air handler.  (Follow the
manufacturer’s procedures).  Unplug the two cable connectors to the motor.
There are latches on each connector.  

DO NOT PULL ON THE WIRES.

The plugs remove easily when properly released.

4. Locate the two standard ¼" hex head bolts at the rear of the control

housing (at the back end of the control opposite the shaft end).  

Refer

to Figure 28.  

Remove these two bolts from the motor and control

assembly while holding the motor in a way that will prevent the motor
or control from falling when the bolts are removed.  If an ECM2.0
control is being replaced (recognized by an aluminum casting rather
that a deep-drawn black steel can housing the electronics), remove
only the hex-head bolts.  

DO NOT REMOVE THE TORX-HEAD

SCREWS.

5. The control module is now free of mechanical attachment to the

motor endshield but is still connected by a plug and three wires inside
the control.  Carefully rotate the control to gain access to the plug at
the control end of the wires.  With thumb and forefinger, reach the
latch holding the plug to the control and release it by squeezing the
latch tab and the opposite side of the connector plug and gently pulling
the plug out of the connector socket in the control.  

DO NOT PULL

ON THE WIRES.  GRIP THE PLUG ONLY.

6. The control module is now completely detached from the motor.

Verify with a standard ohmmeter that the resistance from each motor
lead (in the motor plug just removed) to the motor shell is >100K ohms.

Refer to Figure 29.  

(Measure to unpainted motor end plate.)  If any

motor lead fails this test, do not proceed to install the control module.

THE MOTOR IS DEFECTIVE AND MUST BE REPLACED.

Installing the new control module will cause it to fail also.

7. Verify that the replacement control is correct for your

application.  Refer to the manufacturer's authorized replacement list.

USING THE WRONG CONTROL WILL RESULT IN
IMPROPER OR NO BLOWER OPERATION.

  Orient the control

module so that the 3-wire motor plug can be inserted into the socket in
the control.  Carefully insert the plug and press it into the socket until
it latches.  

A SLIGHT CLICK WILL BE HEARD WHEN

PROPERLY INSERTED.

  Finish installing the replacement control per

one of the three following paragraphs, 8a, 8b or 8c.

8a. 

IF REPLACING AN ECM 2.0 CONTROL

 (control in cast

aluminum can with air vents on the back of the can) 

WITH AN ECM

2.3 CONTROL

 (control containing black potting for water protection in

black deep-drawn steel case with no vents in the bottom of the can),
locate the two through-bolts and plastic tab that are packed with the
replacement control.  Insert the plastic tab into the slot at the perimeter
of the open end of the can so that the pin is located on the inside of the
perimeter of the can.  Rotate the can so that the tab inserts into the tab
locater hole in the endshield of the motor.  Using the two through-bolts
provided with the replacement control, reattach the can to the motor.

THE TWO THROUGH-BOLTS PROVIDED WITH THE
REPLACEMENT ECM 2.3 CONTROL ARE SHORTER THAN
THE BOLTS ORIGINALLY REMOVED FROM THE ECM 2.0
CONTROL AND MUST BE USED IF SECURE ATTACHMENT
OF THE CONTROL TO THE MOTOR IS TO BE ACHIEVED.

DO NOT OVERTIGHTEN THE BOLTS.

8b. 

IF REPLACING AN ECM 2.3 CONTROL

 

WITH AN ECM

2.3 CONTROL

, the plastic tab and shorter through-bolts are not

needed.  The control can be oriented in two positions 180° apart.

MAKE SURE THE ORIENTATION YOU SELECT FOR
REPLACING THE CONTROL ASSURES THE CONTROL'S
CABLE CONNECTORS WILL BE LOCATED DOWNWARD IN
THE APPLICATION SO THAT WATER CANNOT RUN DOWN
THE CABLES AND INTO THE CONTROL.

  Simply orient the

new control to the motor's endshield, insert bolts, and tighten.  

DO

NOT OVERTIGHTEN THE BOLTS.

8c. 

IF REPLACING AN ECM 2.0 CONTROL WITH AN ECM

2.0 CONTROL 

(It is recommended that ECM 2.3 controls be used for

all replacements), 

the new control must be attached to the motor using

through bolts identical to those removed with the original control.  

DO

NOT OVERTIGHTEN THE BOLTS.

9. Reinstall the blower/motor assembly into the HVAC equipment.

Follow the manufacturer's suggested procedures.

10. Plug the 16-pin control plug into the motor.  The plug is keyed.

Make sure the connector is properly seated and latched.

11. Plug the 5-pin power connector into the motor.  Even though the

plug is keyed, 

OBSERVE THE PROPER ORIENTATION.  DO

NOT FORCE THE CONNECTOR.

  It plugs in very easily when

properly oriented.  

REVERSING THIS PLUG WILL CAUSE

IMMEDIATE FAILURE OF THE CONTROL MODULE.

12. Final installation check.  Make sure the motor is installed as

follows:

a. Unit is as far INTO the blower housing as possible.
b.Belly bands are not on the control module or covering vent

holes.

c. Motor connectors should be oriented between the 4 o’clock

and 8 o’clock positions when the blower is positioned in its
final location and orientation.

d.Add a drip loop to the cables so that water cannot enter the

motor by draining down the cables.  

Refer to Figure 30.

The installation is now complete.  Reapply the AC power to the
HVAC equipment and verify that the new motor control module is
working properly.  Follow the manufacturer's procedures for
disposition of the old control module.

Figure 29

Figure 28

Figure 30

Summary of Contents for QW2S1

Page 1: ...NSTALLATION INSTRUCTIONS Models QW2S1 QW3S1 QW4S1 QW5S1 Manual No 2100 532B Supersedes 2100 532A File Vol II Tab 14 Date 07 19 10 Bard Manufacturing Company Inc Bryan Ohio 43506 Since 1914 Moving ahea...

Page 2: ...pressor Control Module 23 Adjustments 23 Optional CFM 24 Important Installer Note 24 Phase Monitor 24 Service Hints 24 Sequence of Operation 24 25 Pressure Service Ports 25 Pressure Tables 28 Optional...

Page 3: ...t Wiring D Option 21 Figure 16 Remote Thermostat Wiring H Option 22 Figure 17 Fluid Connections w Ventilation Wall Sleeve 26 Figure 18 Fluid Connections w o Ventilation Wall Sleeve 27 Figure 19 Circul...

Page 4: ...rocedures for Ground Source IGSHPA Heat Pump Systems Soil and Rock Classification for the Design IGSHPA of Ground Coupled Heat Pump Systems Ground Source Installation Standards IGSHPA Closed Loop Geot...

Page 5: ...than one field power conductor circuit is run through one conduit the conductors must be derated Pay special attention to Note 8 of Table 310 regarding Ampacity Adjustment Factors when more than three...

Page 6: ...CE BACK VIEW FREEBLOW OPTIONAL LOW VOLTAGE ELECTRICAL ENTRANCE 1 11 16 3 3 4 3 1 16 3 3 8 VENT OPTIONAL HIGH INTAKE VOLTAGE VENT EXHAUST ENTRANCE ELECTRICAL ACCESS FOR FLUID CONNECTION FOR DORFC PUMP...

Page 7: ...it can not be slid through the door then the unit will have to be put on a cart and tipped down to roll through the door It is recommended that an appliance cart be used with a strap to hold the unit...

Page 8: ...any tags and or labels attached to the equipment While these instructions are intended as a general recommended guide they do not supersede any national and or local codes in any way Authorities havin...

Page 9: ...TARY OR TOGGLE DISCONNECT ELECTRICAL ACCESS BLOW PLENUM BOX TOP SIDE AND LOCKING COVER LOW VOLTAGE OPTIONAL FREE ELECTRICAL ENTRANCE TOP REAR SIDE VENTILATION PERMANENT HIGH VOLTAGE QW2S QW3S 42 000 Q...

Page 10: ...40 FLOOR 8 FT 8 IN INSTALLATION HEIGHT 9 FT MINIMUM REQUIRED UNIT HEIGHT 7 FT 6 IN MINIMUM 25 IN TO DUCT BOTTOM 2 IN MINIMUM FROM DUCT FLANGE INSTALLATION HEIGHT 8 FT 9 IN MINIMUM REQUIRED MINIMUM 12...

Page 11: ...o the ceiling This extends 20 above the unit for a total height above the floor of 10 7 8 The unit is equipped with a variable speed indoor blower motor which increases in speed with an increase in du...

Page 12: ...ewall Ifthedrainistoberoutedthroughanunconditioned space it must be protected from freezing The drain line must be able to be removed from the unit if it is necessary to remove the unit from the wall...

Page 13: ...that the mist eliminator be inspected annually and serviced as required The mist eliminator can be inspected from the outside of the building by looking through the outdoor grille The mist eliminator...

Page 14: ...OVERY VENTILATOR 3 Underneath the heat recovery cassette there is a power connector for the lower blower assembly To disconnect this plug the tabs on both sides of the plug must be squeezed to release...

Page 15: ...ping connections are to be within the confines of this bracket See Figure 1 for cabinet openings and location of fluid coil connection points 2 Position the unit in front of the wall mounting bracket...

Page 16: ...of 46 FIGURE 11 UNIT MOUNTING WITHOUT VENTILATION WALL SLEEVE BRACKET WALL MOUNTING BASE TRIM SIDE TRIM CUT TO LENGTH 41 ADJUSTABLE SIDE TRIM EXTENSION KIT ORDERED SEPARATELY SIDE TRIM EXTENSION MIS 2...

Page 17: ...Manual 2100 532B Page 17 of 46 FIGURE 12 COMPONENTLOCATION WIRE ENTRANCE SIDE FIELD TERMINAL BLOCK REMOTE THERMOSTAT INDOOR DUAL BLOWERS CONTROL BOX CIRCUIT BREAKER PANEL MIS 2745...

Page 18: ...LTAGE WIRING 230 208V 1 PHASE AND 3 PHASE EQUIPMENT DUAL PRIMARY VOLTAGE TRANSFORMERS All equipment leaves the factory wired on 240V tap For 208V operation reconnect from 240V to 208V tap The acceptab...

Page 19: ...for ventilation during occupied programming conditions and feeds through Pin 5 of Plug P2 The W2 terminal is the electric heat signal and feeds through Pin 9 of Plug P2 The W1 E terminal is the emerge...

Page 20: ...CO2 Controller 24VAC O B Out Part 8403 060 C Y2 A Y1 R G Analog Controller Terminal Strip E W2 O C Y2 A W2 Y1 R Temp and Humidity Low Voltage D YO Orange Orange Orange Yellow Green Green Brown White B...

Page 21: ...TAT WIRING DIAGRAM D THERMOSTAT OPTION Blue Pink Purple L O B W1 E Y1 Part 8403 060 C Y2 A W2 G R Temp and Humidity Controller D YO Orange Yellow Brown White Brown 9 8 11 10 PLUG 2 Red Yellow Red Whit...

Page 22: ...E L CO2 Controller Out C Y2 A W2 Analog Temp and Humidity Controller Part 8403 060 Orange Orange Orange Yellow Green Green Brown Brown Brown White Brown Red White PLUG 1 Red Yellow PLUG 2 Red Red Bla...

Page 23: ...ESSURE SWITCH AND LOCKOUT SEQUENCE If the high pressure switch opens the compressor contactor will de energize immediately The lockout timer will go into a soft lockout and stay in soft lockout until...

Page 24: ...eakers to be sure that they are the correct rating 3 The heat pump wall thermostats perform multiple functions Be sure that all function switches are correctly set for the desired operating mode befor...

Page 25: ...2 1 S 2 W Q 0 0 5 0 0 0 8 0 0 8 0 0 9 0 0 0 1 1 S 3 W Q 0 0 5 0 0 0 8 0 0 9 0 5 0 1 0 5 1 1 1 S 4 W Q 0 0 5 0 0 0 9 0 5 1 1 5 2 2 1 0 5 3 1 1 S 6 W Q 0 0 5 0 0 0 9 0 5 2 1 0 0 3 1 0 5 4 1 PRESSURE SER...

Page 26: ...HIPPED WITH UNIT CEILING SIDE TRIM PIECES SHIPPED WITH UNIT IF THE WALL THICKNESS IS LESS THAN 14 BUT GREATER THAN 8 A SIDE TRIM EXTENSION KIT QSTX42 IS REQUIRED REFER FLUID ACCESS FROM SLEEVE TOP OF...

Page 27: ...WITHOUT VENTILATION WALL SLEEVE 23 1 2 8 1 2 66 1 2 4 LEFT BRACKET REMOVED FOR FLOOR FLUID ACCESS FROM FLOOR FLUID ACCESS FROM TOP CLARITY WALL BRACKET OPENING IN REAR OF UNIT 3 x 8 BACK OF UNIT MIS...

Page 28: ...9 8 3 1 3 1 1 0 4 0 4 1 2 1 4 9 4 1 4 2 4 9 5 1 5 3 4 8 6 1 7 4 4 S 5 W Q B D 0 7 e d i S w o L e d i S h g i H 7 3 8 8 2 4 4 0 0 3 1 5 2 1 3 8 5 4 2 3 5 6 5 3 3 2 7 7 4 3 9 7 9 5 3 6 8 1 7 3 3 9 2 8...

Page 29: ...i t a l P 4 8 4 S B P Q t n i a P y a r G X 8 4 S B P Q t n i a P e g i e B e d i s h c a e n o e l l i r g n o i t c e f e d y a w 2 s u l p 8 4 B P Q s a e m a S s g n i l i e C o t s e x o B m u n...

Page 30: ...st be closely matched with the pressure of FIGURE 19 CIRCULATIONSYSTEM head loss of the entire system in order to provide the required flow through the heat pump Insufficient flow through the heat exc...

Page 31: ...capacity If the module selection is correct there is probably trapped air or a restriction in the piping circuit 8 Start the unit in cooling mode by moving the thermostat switch to cool Fan should be...

Page 32: ...10 20 30 40 50 60 70 0 5 10 15 20 25 30 35 Flow GPM Head Feet FIGURE 22 PERFORMANCE MODEL DORFC 2 LOOP PUMP MODULE 0 5 10 15 20 25 30 35 0 5 10 15 20 25 30 35 Flow GPM Head Feet FIGURE 21 PERFORMANCE...

Page 33: ...icated by the arrow on the side of the valve body Table 7 is a table showing the flow rate of each valve Two constant flow rate valves may be installed in parallel to increase the flow For example whe...

Page 34: ...wer disconnect to ON Except as required for safety while servicing do not open the unit disconnect switch 4 Check system airflow for obstructions A Move thermostat fan switch to ON Blower runs B Be su...

Page 35: ...er 3 Corrosion of Metal Corrosion of metal parts results from either highly corrosive water acid water generally not the case with ground water of galvanic reaction between dissimilar metals in the pr...

Page 36: ...suspended in the dry well casing Jet pumps and other types of suction pumps normally consume more electrical energy than similarly sized submersible pumps Pipe the unit the same as a water well system...

Page 37: ...of 46 FIGURE 25 WATER WELL SYSTEM 12 to 15 LAKE or POND WATER LEVEL GRAVEL FILL WELL CAP ELECTRICAL LINE PITLESS ADAPTER TO PRESSURE TANK SUBMERSIBLE PUMP PERFORATED PLASTIC CASING DROP PIPE WATER SU...

Page 38: ...4 8 0 1 2 1 2 8 2 9 8 1 5 5 9 6 2 1 3 1 4 9 9 6 1 2 4 6 6 7 4 1 4 1 6 0 1 5 4 4 2 3 7 4 8 6 1 5 1 1 8 9 6 8 1 6 1 9 6 7 0 2 7 1 9 9 4 8 2 2 8 1 WARNING Thin ice may result in the vicinity of the disc...

Page 39: ...Manual 2100 532B Page 39 of 46 FIGURE 26 WATER SOURCE HEAT PUMP...

Page 40: ...Manual 2100 532B Page 40 of 46 FIGURE 27 WATER SOURCE HEAT PUMP...

Page 41: ...de while the low side shell and suction line contains pressure the pressurized refrigerant and oil mixture could ignite when it escapes and contacts the brazing flame To prevent this occurrence it is...

Page 42: ...it s air noise cabinet duct or motor noise interview customer if necessary Air noise High static creating high blower speed Is airflow set properly Does removing filter cause blower to slow down Check...

Page 43: ...Refer to the manufacturer s authorized replacement list USING THE WRONG CONTROL WILL RESULT IN IMPROPER OR NO BLOWER OPERATION Orient the control module so that the 3 wire motor plug can be inserted...

Page 44: ...Defective Air Volume Low Air Filters Dirty Undersized or Restricted Ductwork Auxillary Heat Upstream of Coil Compressor Will Not Run No Power at Contactor Compressor Will Not Run Power at Contactor Co...

Page 45: ...alled 5 User s Owner s Name Address 6 Unit Location WATER SYSTEM INFORMATION 7 Open Loop System Water Well Closed Loop System A If Open Loop where is water discharged 8 The following questions are for...

Page 46: ...ontactor A 19 Amperage at compressor common terminal A 20 Suction line temperature 6 from compressor F 21 Superheat at compressor F 22 Liquid line temperature at metering device F 23 Coil subcooling F...

Reviews: