Manual
2100-418F
Page
19 of 49
WIRING – MAIN POWER
Refer to the unit rating plate and/or Table 1 for wire
sizing information and maximum fuse or “HACR Type”
circuit breaker size. Each unit is marked with a
“Minimum Circuit Ampacity”. This means that the
field wiring used must be sized to carry that amount of
current. Depending on the installed KW of electric heat,
there may be two field power circuits required. If this is
the case, the unit serial plate will so indicate. All
models are suitable only for connection with copper
wire. Each unit and/or wiring diagram will be marked
“Use Copper Conductors Only”. These instructions
must be
adhered to. Refer to the National Electrical
Code (NEC) for complete current carrying capacity data
on the various insulation grades of wiring material. All
wiring must conform to NEC and all local codes.
The electrical data lists fuse and wire sizes (75°C copper)
for all models, including the most commonly used heater
sizes. Also shown are the number of field power circuits
required for the various models with heaters.
The unit rating plate lists a “Maximum Time Delay
Relay Fuse” or “HACR Type” circuit breaker that is to
be used with the equipment. The correct size must be
used for proper circuit protection, and also to assure that
there will be no nuisance tripping due to the momentary
high starting current of the compressor motor.
The disconnect access door on this unit may be locked
to prevent unauthorized access to the disconnect.
The field wiring connections are located behind the top
panel in the circuit breaker panel. The return air panel
must be removed first. This panel is equipped with a
door switch which shuts the unit down when it is
removed. The filter rack must be removed next.
WIRING – LOW VOLTAGE WIRING
230/208V, 1 PHASE AND 3 PHASE EQUIPMENT
DUAL PRIMARY VOLTAGE TRANSFORMERS
All equipment leaves the factory wired on 240V tap.
For 208V operation, reconnect from 240V to 208V tap.
The acceptable operating voltage range for the 240 and
208V taps are as noted in Table 2.
The standard Climate Control
Option X
is a remote
thermostat connection terminal block. See Figure 15 for
wiring diagram. Compatible thermostats are listed in
Table 3.
The Climate Control
Option E
is an electronic
programmable thermostat and a humidistat. The subbase
of the thermostat and the humidistat are factory wired to
the front panel of the unit. See Figure 16 for wiring
diagram. Compatible for use with Energy Recovery
Ventilator or Ventilator.
GENERAL
This unit is equipped with a variable speed ECM motor.
The motor is designed to maintain rated airflow up to the
maximum static allowed.
It is important that the
blower motor plugs are not plugged in or unplugged
while the power is on. Failure to remove power prior to
unplugging or plugging in the motor could result in
motor failure.
NOTE: The voltage should be measured at the field
power connection point in the unit and while
the unit is operating at full load (maximum
amperage operating condition).
TABLE 2
OPERATING VOLTAGE RANGE
P
A
T
E
G
N
A
R
V
0
4
2
6
1
2
-
3
5
2
V
8
0
2
7
8
1
-
0
2
2
TABLE 3
WALL THERMOSTATS
t
a
t
s
o
m
r
e
h
T
s
e
r
u
t
a
e
F
t
n
a
n
i
m
o
d
e
r
P
8
3
0
-
3
0
4
8
)
A
0
0
6
H
(
t
a
t
s
i
d
i
m
u
H
0
6
0
-
3
0
4
8
)
5
4
4
-
0
2
1
1
(
t
a
e
H
e
g
a
t
s
3
;
l
o
o
C
e
g
a
t
s
3
c
i
n
o
r
t
c
e
l
E
e
l
b
a
m
m
a
r
g
o
r
P
-
n
o
N
/
e
l
b
a
m
m
a
r
g
o
r
P
l
a
n
o
i
t
n
e
v
n
o
C
r
o
P
H
r
e
v
o
e
g
n
a
h
c
l
a
u
n
a
M
r
o
o
t
u
A
8
5
0
-
3
0
4
8
)
1
5
1
1
D
0
2
2
5
H
T
(
t
a
e
H
e
g
a
t
s
2
;
l
o
o
C
e
g
a
t
s
2
e
l
b
a
m
m
a
r
g
o
r
P
-
n
o
N
c
i
n
o
r
t
c
e
l
E
r
e
v
o
e
g
n
a
h
c
l
a
u
n
a
M
r
o
o
t
u
A
CAUTION
Do not plug in or unplug blower motor
connectors while the power is on.
Failure to do so may result in motor failure.