When the humidity is above the setpoint of the
humidistat, the compressor circuit and the 3 way valve
are energized and the evaporator air flow is reduced.
The 3 way valve directs hot discharge gas into a
separate desuperheating condenser circuit that reheats
the conditioned air before it is delivered to the room.  If
the return air thermostat sensed a temperature below 65°
during dehumidification, the fist stage electric heaters
are brought on to raise the return air temperature above
65°.  When the humidistat is satisfied, the system
switches back to normal air conditioning mode.

If the thermostat calls for cooling during
dehumidification mode, the call for cooling takes
precedence over the dehumidification and the unit will
cool until the thermostat is satisfied.  Once the call for
cooling is satisfied, the unit may continue to
dehumidify.

If the thermostat calls for heat when the unit is in the
dehumidification mode, the electric heaters will
energize and the evaporator air flow will return to the
heating air flow.  When the thermostat is satisfied, the
electric heaters will turn off and the air flow will be
reduced and the system will continue to dehumidify
until humidistat is satisfied.

If the unit is running in heat pump mode and the
humidistat calls for dehumidification, the
dehumidification mode takes precedence over the heat
pump heating mode.  The unit will not return to the
heating mode until 2nd stage heating is called for.

The Climate Control Option G has a non-programmable
electronic thermostat, humidistat and is compatible for
use with a CS2000 Energy Control Monitor.  This unit
has a refrigerant reheat circuit that is controlled by a
three-way valve.

Unit operation is controlled by the thermostat and
humidistat, and optional CS2000 Energy Monitor
Controller can be easily integrated by simple connection
to the low voltage terminal block provided.  See Figure
16C.

NOTE: The CS2000 (or other means for ventilation

control) must be used if any mechanical
(motorized) ventilation options are installed.

Dehumidification can be set to be available only when
CS2000 is active or to be available continuously by
switching a toggle switch at the control panel.

REFRIGERANT TUBE SCHEMATIC FOR
REHEAT COIL

Figure 19 shows the refrigerant gas flow through the
reheat coil during the dehumidification mode.

When the unit is in standard cooling (Figure 20) or
heating mode the reheat coil is inactive.

PRESSURE SERVICE PORTS

High and low pressure service ports are installed on all
units so that the system operating pressures can be
observed.  Pressure curves can be found later in the
manual covering all models on both cooling and heating
cycles.  It is imperative to match the correct pressure
curve to the unit by model number.  Upper and lower
service doors must be attached to obtain proper reading.

When the humidity is above the setpoint of the
humidistat, the compressor circuit and the 3 way valve
are energized and the evaporator air flow is reduced.
The 3 way valve directs hot discharge gas into a
separate desuperheating condenser circuit that reheats
the conditioned air before it is delivered to the room.  If
the return air thermostat sensed a temperature below
65°  during dehumidification, the fist stage electric
heaters are brought on to raise the return air temperature
above 65°.  When the humidistat is satisfied, the system
switches back to normal air conditioning mode.

If the thermostat calls for cooling during
dehumidification mode, the call for cooling takes
precedence over the dehumidification and the unit will
cool until the thermostat is satisfied.  Once the call for
cooling is satisfied, the unit may continue to
dehumidify.

If the thermostat calls for heat when the unit is in the
dehumidification mode, the electric heaters will
energize and the evaporator air flow will return to the
heating air flow.  When the thermostat is satisfied, the
electric heaters will turn off and the air flow will be
reduced and the system will continue to dehumidify
until humidistat is satisfied.

If the unit is running in heat pump mode and the
humidistat calls for dehumidification, the
dehumidification mode takes precedence over the heat
pump heating mode.  The unit will not return to the
heating mode until 2nd stage heating is called for.

Summary of Contents for QTEC QH602D Series

Page 1: ...QH602D QTEC SERIES PACKAGED HEAT PUMP INSTALLATION INSTRUCTIONS Bard Manufacturing Company Bryan Ohio 43506 Since 1914 Moving ahead just as planned Manual 2100 380C Supersedes 2100 380B File Vol II Ta...

Page 2: ...igure 16B Thermostat Wiring Diagram F Option19 Figure 16C Thermostat Wiring Diagram G Option 20 Figure 17 Fresh Air Damper Removal 24 Figure 18 QERV Removal 25 Figure 19 Dehumidification Mode Circuit...

Page 3: ...Manual N Air Conditioning Low Pressure Low Velocity ACCA Manual D or Duct System Design Manual Q Winter and Summer Air Conditioning FOR MORE INFORMATION CONTACT THESE PUBLISHERS ACCA Air Conditioning...

Page 4: ...Motorized w Exhaust Spring Return FILTER OPTIONS X 1 Inch Fiberglass Standard F 2 Inch Fiberglass P 2 Inch Pleated COLOR OPTIONS V Platinum w Slate Front Vinyl 4 Gray paint TABLE 1 FACTORY BUILT IN EL...

Page 5: ...E W O P E R I W E Z I S k D N U O R G E R I W E Z I S l M U M I N I M T I U C R I C Y T I C A P M A M U M I X A M L A N R E T X E R O E S U F T I U C R I C R E K A E R B k D L E I F R E W O P E Z I S...

Page 6: ...a n r e t x E r o e s u F t i u c r i C r e k a e r B 2 d l e i F r e w o P e z i S e r i W 2 d n u o r G e z i S e r i W o N l e d o M T K C A T K C B T K C A T K C B T K C A T K C B T K C A T K C B...

Page 7: ...Manual 2100 380 Page 5 FIGURE 1 UNITDIMENSIONS MIS 1636...

Page 8: ...emoved and discarded See Figure 3 A The return air grille panel can be removed to provide a place to hold the unit The unit can be slid forward on the skit until the front wheels hang over the edge of...

Page 9: ...ral recommended guide they do not supersede any national and or local codes in any way Authorities having jurisdiction should be consulted before the installation is made See Page 1 for information on...

Page 10: ...FT 6 IN MINIMUM RECOMMENDED CEILING HEIGHT 8 FT 5 IN FLOOR MIS 1573 SUSPENDED CEILING FIXED CEILING DUCT DUCT FLANGE 8 FT 7 IN MINIMUM RECOMMENDED CEILING HEIGHT 7 FT 4 IN UNIT HEIGHT 12 IN MINIMUM 2...

Page 11: ...g by opening the hinged door This door is attached by 1 4 turn fasteners and one locking latch The internal filter brackets are adjustable to accommodate 2 inch filters The tabs for the 1 inch filters...

Page 12: ...tions on the unit The rear drain is the primary drain and is located on the right lower rear panel of the unit The optional side drain is located on the bottom right side of the unit The side drain is...

Page 13: ...re device This indicates that the unit needs to be serviced FIGURE 12 UNITMOUNTING BOTTOM TRIM PIECE BOTTOM TRIM EXTENSION MOUNTING BRACKET SIDE TRIM 2 PCS SIDE TRIM 2 PCS MIS 1576 CABINET SIDE PANEL...

Page 14: ...it centered in the sleeve Also check the alignment to the mounting brackets This unit must be level from side to side If adjustments are necessary shim up under the rollers with sheets of steel or an...

Page 15: ...re Each unit and or wiring diagram will be marked Use Copper Conductors Only These instructions MUST BE adhered to Refer to the National Electrical Code NEC for complete current carrying capacity data...

Page 16: ...e emergency heat input This terminal energizes the emergency heat relay NOTE For total and proper control using DDC a total of 7 controlled outputs are required 6 if no ventilation system is installed...

Page 17: ...C 4 3 0 3 0 4 8 0 8 4 9 F 1 A N l o o C t a e H e l b a m a r g o r P c i n o r t c e l E 8 3 0 3 0 4 8 A 0 0 6 H A N t a t s i d i m u H 2 4 0 3 0 4 8 0 7 0 1 G 1 1 5 8 T A N l o o C t a e H o t u A...

Page 18: ...Manual 2100 380 Page 16 4102 023 FIGURE 16 THERMOSTATWIRINGDIAGRAM X THERMOSTATOPTION DEHUMIDIFICATIONMODULE NOTE See next page for additional details on LVTB connection identification...

Page 19: ...24VAC HOT DEHUM CIRCUIT 24VAC COM DEHUM CIRCUIT NOTE FIELD SUPPLIED DEHUMIDISTAT MUST BE DRY CONTACT CONNECTED TO TERMINALS 5 AND 4 ON LVTB COMPRESSOR SYSTEM CHECK LIGHT REVERSING VALVE 2ND STAGE HEAT...

Page 20: ...Manual 2100 380 Page 18 4102 025 FIGURE 16A REMOTE THERMOSTAT WIRING DIAGRAM E THERMOSTAT OPTION DEHUMIDIFICATION MODULE...

Page 21: ...Manual 2100 380 Page 19 FIGURE 16B REMOTETHERMOSTATWIRINGDIAGRAM F THERMOSTATOPTION DEHUMIDIFICATIONMODULE 4102 024...

Page 22: ...age 20 FIGURE 16C UNIT MOUNTED THERMOSTAT AND HUMIDISTAT WIRING DIAGRAM G THERMOSTATOPTION DEHUMIDIFICATIONMODULE 4102 027 REMOVE Y TO Y1 JUMPER WHEN CS2000 ENERGY MONITOR IS USED SEE CS2000 MANUAL 21...

Page 23: ...or to prevent compressor damage due to phase reversal The phase monitor in this unit is equipped with two LEDs If the Y signal is present at the phase monitor and phases are correct the green LED will...

Page 24: ...inet side panel g Remove screws that attach the duct work to the unit flanges This unit is equipped with four rollers mounted to the base For ease of pulling unit out from the wall you may want to rem...

Page 25: ...he opening in the back of the unit The mist eliminator must be raised up and the bottom can be pulled toward the front of the unit and removed QTEC R ENERGY RECOVERY VENTILATOR Option Before starting...

Page 26: ...Manual 2100 380 Page 24 MIS 1627 FIGURE 17 FRESH AIR DAMPER REMOVAL MOUNTING SCREW...

Page 27: ...Manual 2100 380 Page 25 MIS 1039 FIGURE 18 QERVREMOVAL MOUNTING SCREWS FRONT FILL LOWER BLOWER ASSEMBLY POWER CONNECTOR POWER CONNECTORS...

Page 28: ...rmostat closes and brings on stage one electric heat to maintain 65 High Low Pressure control provides protection for the compressor In the event system pressures go above 350 PSI or below 3 5 PSI in...

Page 29: ...talled Dehumidification can be set to be available only when CS2000 is active or to be available continuously by switching a toggle switch at the control panel REFRIGERANT TUBE SCHEMATIC FOR REHEAT CO...

Page 30: ...Manual 2100 380 Page 28 FIGURE 19 QTEC DEHUMIDIFICATIONMODECIRCUITDIAGRAM MIS 1088...

Page 31: ...Manual 2100 380 Page 29 FIGURE 20 QTEC COOLING MODE CIRCUIT DIAGRAM MIS 1089...

Page 32: ...coil temperature This can be used to check defrost operation of the unit without waiting for the outdoor ambient to fall into the defrost region Use a small screwdriver or other metallic object or an...

Page 33: ...c d e t r o h s r o n e p o r o t i c a p a c e c a l p e R l o r t n o c p m u p t a e H e v i t c e f e d t a e h n o y a l e r n a f s s o r c a k c e h C l o r t n o c p m u p C N m o C l o r t n...

Page 34: ...7 0 3 2 5 7 0 1 9 2 7 0 7 6 0 7 7 0 5 8 6 8 1 4 6 6 9 9 3 4 6 9 4 4 2 6 5 6 5 0 6 5 4 7 8 5 0 3 1 0 4 1 0 5 1 0 6 1 0 7 1 0 8 1 0 9 1 0 0 2 0 1 2 0 2 2 0 3 2 0 4 2 0 5 2 0 6 2 0 7 2 0 8 2 0 9 2 0 0 3...

Page 35: ...formance will occur with a refrigerant charge resulting in a Super Heat as shown in Table 8 If correct charge is in doubt recover the refrigerant and recharge per the charge on the unit rating plate T...

Page 36: ...d i S h g i H 4 7 2 1 2 4 7 5 1 2 5 7 3 3 2 6 7 1 5 2 7 7 9 6 2 8 7 7 8 2 9 7 5 0 3 0 8 3 2 3 1 8 1 4 3 B D g e d 0 8 B W g e d 7 6 e d i S w o L e d i S h g i H 9 7 9 1 2 9 7 0 2 2 0 8 9 3 2 1 8 7 5...

Page 37: ...2 6 3 H Q g e d 0 7 e d i S w o L e d i S h g i H 3 1 7 4 1 7 1 3 5 1 1 2 9 5 1 5 2 4 6 1 7 2 7 6 1 0 3 1 7 1 4 3 6 7 1 8 3 2 8 1 2 4 8 8 1 6 4 4 9 1 2 5 2 0 2 5 5 6 0 2 9 5 1 1 2 3 6 7 1 2 2 2 4 H Q...

Reviews: