Manual 2100-601E
Page
42 of 42
MODEL
RETURN
AIR
TEMP.
PRESSURE
AIR TEMPERATURE ENTERING OUTDOOR COIL
0
5
10
15
20
25
30
35
40
45
50
55
60
Q24H2
70
Low Side
High Side
35
284
42
290
49
297
57
304
64
313
72
322
79
331
86
342
94
353
101
365
109
378
117
392
124
406
Q30H2
70
Low Side
High Side
44
295
47
299
52
305
56
312
62
320
68
330
75
341
82
353
90
367
99
382
108
398
118
415
129
434
Q36H2
70
Low Side
High Side
28
271
38
278
48
286
57
294
65
302
72
310
79
319
85
327
91
336
96
346
100
355
104
365
107
374
Q42H2
70
Low Side
High Side
30
272
38
283
46
294
54
305
61
317
68
328
76
339
83
350
90
362
96
373
103
385
109
396
115
408
Q48H2
70
Low Side
High Side
27
272
36
281
46
291
54
300
63
310
71
320
78
330
85
339
91
349
97
359
103
369
108
380
113
390
Q60H2
70
Low Side
High Side
7
252
19
266
31
280
42
293
52
306
61
318
69
330
76
341
83
352
89
362
94
371
98
380
101
389
TABLE 10
Heating Pressure
(All Temperatures in Degrees F)
Low side pressure ± 4 psig
High side pressure ± 10 psig
Tables are based upon rated CFM (airflow) across the evaporator coil. If there is any doubt as to correct operating charge being in the
system, the charge should be removed, system evacuated and recharged to serial plate instructions.
75°F outdoor temperature condenser fan motor is running on low speed.