background image

Manual 2100-603

Page 

41 of 44

Manual

2100-522B

Page

36 of 38

TROUBLESHOOTING  GE  ECM

 MOTORS CONT’D.

Motor

Motor OK when

R > 100k ohm

ECM 2.0

Only remove

Hex Head Bolts

Connector Orientation

Between 4 and 8 o'clock

Drip Loop

Back of

Control

Figure 5

Winding Test

Figure 4

Note:              

Use the shorter 

bolts and 

alignment pin 

supplied when 

replacing an 

ECM 2.0 

control.

Figure 3

ECM 

2.3/2.5

Power Connector

(5-pin)

Control Connector

(16-pin)

Hex-head Screws

Motor Connector

(3-pin)

Motor Connector

(3-pin)

Control Disassembly

Drip Loop

Push until

Latch Seats

Over Ramp

From Motor

Circuit

Board

Replacing ECM Control Module

To replace the control module for the GE variable-speed indoor blower

motor you need to take the following steps:

1. You MUST have the correct replacement module.  The controls are

factory programmed for specific operating modes.  Even though they look

alike, different modules may have completely different functionality.

USING THE WRONG CONTROL MODULE VOIDS ALL PRODUCT

WARRANTIES AND MAY PRODUCE UNEXPECTED RESULTS.

2. Begin by removing AC power from the furnace or air handler being

serviced.  

DO NOT WORK ON THE MOTOR WITH AC POWER

APPLIED.  

To avoid electric shock from the motor’s capacitors, disconnect

power and wait at least 5 minutes before opening motor.

3. It is usually not necessary to remove the motor from the blower

assembly.  However, it is recommended that the whole blower assembly,

with the motor, be removed from the furnace/air handler.  (Follow the

manufacturer’s procedures).  Unplug the two cable connectors to the motor.

There are latches on each connector.  

DO NOT PULL ON THE WIRES.

The plugs remove easily when properly released.

4. Locate  the  two  standard  ¼"  hex  head  bolts  at  the  rear  of  the  control

housing  (at  the  back  end  of  the  control  opposite  the  shaft  end).   

Refer  to

Figure  24.   

Remove  these  two  bolts  from  the  motor  and  control  assembly

while  holding  the  motor  in  a  way  that  will  prevent  the  motor  or  control

from  falling  when  the  bolts  are  removed.    If  an  ECM2.0  control  is  being

replaced  (recognized  by  an  aluminum  casting  rather  that  a  deep-drawn

black  steel  can  housing  the  electronics),  remove  only  the  hex-head  bolts.

DO  NOT  REMOVE  THE  TORX-HEAD  SCREWS.

5. The  control  module  is  now  free  of  mechanical  attachment  to  the

motor  endshield  but  is  still  connected  by  a  plug  and  three  wires  inside

the  control.    Carefully  rotate  the  control  to  gain  access  to  the  plug  at

the  control  end  of  the  wires.    With  thumb  and  forefinger,  reach  the

latch  holding  the  plug  to  the  control  and  release  it  by  squeezing  the

latch  tab  and  the  opposite  side  of  the  connector  plug  and  gently  pulling

the  plug  out  of  the  connector  socket  in  the  control.   

DO  NOT  PULL

ON  THE  WIRES.    GRIP  THE  PLUG  ONLY.

6. The  control  module  is  now  completely  detached  from  the  motor.

Verify  with  a  standard  ohmmeter  that  the  resistance  from  each  motor

lead  (in  the  motor  plug  just  removed)  to  the  motor  shell  is  >100K  ohms.

Refer to Figure 25.  

(Measure to unpainted motor end plate.)  If any

motor  lead  fails  this  test,  do  not  proceed  to  install  the  control  module.

THE  MOTOR  IS  DEFECTIVE  AND  MUST  BE  REPLACED.

Installing  the  new  control  module  will  cause  it  to  fail  also.

7. Verify  that  the  replacement  control  is  correct  for  your

application.    Refer  to  the  manufacturer's  authorized  replacement  list.

USING  THE  WRONG  CONTROL  WILL  RESULT  IN

IMPROPER  OR  NO  BLOWER  OPERATION.

    Orient  the  control

module  so  that  the  3-wire  motor  plug  can  be  inserted  into  the  socket  in

the  control.    Carefully  insert  the  plug  and  press  it  into  the  socket  until

it  latches.   

A  SLIGHT  CLICK  WILL  BE  HEARD  WHEN

PROPERLY  INSERTED.

    Finish  installing  the  replacement  control  per

one  of  the  three  following  paragraphs,  8a,  8b  or  8c.

8a. 

IF  REPLACING  AN  ECM  2.0  CONTROL

  (control  in  cast

aluminum  can  with  air  vents  on  the  back  of  the  can) 

WITH  AN  ECM

2.3  CONTROL

  (control  containing  black  potting  for  water  protection  in

black  deep-drawn  steel  case  with  no  vents  in  the  bottom  of  the  can),

locate  the  two  through-bolts  and  plastic  tab  that  are  packed  with  the

replacement  control.    Insert  the  plastic  tab  into  the  slot  at  the  perimeter

of the open end of the can so that the pin is located on the inside of the

perimeter of the can.  Rotate the can so that the tab inserts into the tab

locater  hole  in  the  endshield  of  the  motor.    Using  the  two  through-bolts

provided  with  the  replacement  control,  reattach  the  can  to  the  motor.

THE  TWO  THROUGH-BOLTS  PROVIDED  WITH  THE

REPLACEMENT  ECM  2.3  CONTROL  ARE  SHORTER  THAN

THE  BOLTS  ORIGINALLY  REMOVED  FROM  THE  ECM  2.0

CONTROL  AND  MUST  BE  USED  IF  SECURE  ATTACHMENT

OF  THE  CONTROL  TO  THE  MOTOR  IS  TO  BE  ACHIEVED.

DO  NOT  OVERTIGHTEN  THE  BOLTS.

8b. 

IF  REPLACING  AN  ECM  2.3  CONTROL

 

WITH  AN  ECM  2.3

CONTROL

,  the  plastic  tab  and  shorter  through-bolts  are  not  needed.    The

control  can  be  oriented  in  two  positions  180°  apart.   

MAKE  SURE  THE

ORIENTATION  YOU  SELECT  FOR  REPLACING  THE

CONTROL  ASSURES  THE  CONTROL'S  CABLE  CONNECTORS

WILL  BE  LOCATED  DOWNWARD  IN  THE  APPLICATION  SO

THAT  WATER  CANNOT  RUN  DOWN  THE  CABLES  AND  INTO

THE  CONTROL.

    Simply  orient  the  new  control  to  the  motor's  endshield,

insert bolts, and tighten.  

DO  NOT  OVERTIGHTEN  THE  BOLTS.

8c. 

IF  REPLACING  AN  ECM  2.0  CONTROL  WITH  AN  ECM  2.0

CONTROL 

(It  is  recommended  that  ECM  2.3  controls  be  used  for  all

replacements), 

the  new  control  must  be  attached  to  the  motor  using

through  bolts  identical  to  those  removed  with  the  original  control.   

DO

NOT  OVERTIGHTEN  THE  BOLTS.

9. Reinstall  the  blower/motor  assembly  into  the  HVAC  equipment.

Follow  the  manufacturer's  suggested  procedures.

10.  Plug  the  16-pin  control  plug  into  the  motor.    The  plug  is  keyed.

Make  sure  the  connector  is  properly  seated  and  latched.

11.  Plug  the  5-pin  power  connector  into  the  motor.    Even  though  the

plug  is  keyed, 

OBSERVE  THE  PROPER  ORIENTATION.    DO  NOT

FORCE  THE  CONNECTOR.

    It  plugs  in  very  easily  when  properly

oriented.   

REVERSING  THIS  PLUG  WILL  CAUSE  IMMEDIATE

FAILURE  OF  THE  CONTROL  MODULE.

12.  Final  installation  check.    Make  sure  the  motor  is  installed  as  follows:

a. Unit  is  as  far  INTO  the  blower  housing  as  possible.

b. Belly  bands  are  not  on  the  control  module  or  covering  vent  holes.

c. Motor  connectors  should  be  oriented  between  the  4  o’clock  and  8

o’clock  positions  when  the  blower  is  positioned  in  its  final

location  and  orientation.

d. Add  a  drip  loop  to  the  cables  so  that  water  cannot  enter  the  motor

by  draining  down  the  cables.   

Refer  to  Figure  26.

The  installation  is  now  complete.    Reapply  the  AC  power  to  the  HVAC

equipment  and  verify  that  the  new  motor  control  module  is  working

properly.    Follow  the  manufacturer's  procedures  for  disposition  of  the  old

control  module.

Figure 25

Figure 24

Figure 26

Figure 28

Figure 29

Figure 30

TROUBLESHOOTING ECM

 MOTORS CONT’D.

Replacing ECM Control Module

To replace the control module for the GE variable-speed indoor blower 

motor you need to take the following steps:

  1.  You MUST have the correct replacement module.  The controls are 

factory programmed for specific operating modes.  Even though they look 

alike, different modules may have completely different functionality.

USING THE WRONG CONTROL MODULE VOIDS ALL PRODUCT 
WARRANTIES AND MAY PRODUCE UNEXPECTED RESULTS.

 

2.  Begin by removing AC power from the furnace or air handler being 

serviced.  

DO NOT WORK ON THE MOTOR WITH AC POWER 

APPLIED.  

To avoid electric shock from the motor’s capacitors, disconnect 

power and wait at least 5 minutes before opening motor.
  3.  It is usually not necessary to remove the motor from the blower 

assembly.  However, it is recommended that the whole blower assembly, 

with the motor, be removed from the furnace/air handler.  (Follow the 

manufacturer’s procedures).  Unplug the two cable connectors to the motor.  

There are latches on each connector.  

DO NOT PULL ON THE WIRES.  

The plugs remove easily when properly released.

  4.  Locate the two standard ¼" hex head bolts at the rear of the control 

housing (at the back end of the control opposite the shaft end).  

Refer to 

Figure 28.  

Remove these two bolts from the motor and control assembly 

while holding the motor in a way that will prevent the motor or control 

from falling when the bolts are removed.  If an ECM2.0 control is being 

replaced (recognized by an aluminum casting rather that a deep-drawn 

black steel can housing the electronics), remove only the hex-head bolts.  

DO NOT REMOVE THE TORX-HEAD SCREWS.

  5.  The control module is now free of mechanical attachment to the 

motor endshield but is still connected by a plug and three wires inside 

the control.  Carefully rotate the control to gain access to the plug at 

the control end of the wires.  With thumb and forefinger, reach the latch 

holding the plug to the control and release it by squeezing the latch tab 

and the opposite side of the connector plug and gently pulling the plug 

out of the connector socket in the control.  

DO NOT PULL ON THE 

WIRES.  GRIP THE PLUG ONLY.

  6.  The control module is now completely detached from the motor.  

Verify with a standard ohmmeter that the resistance from each motor 

lead (in the motor plug just removed) to the motor shell is >100K ohms.  

Refer to Figure 29.  

(Measure to unpainted motor end plate.)  If any motor 

lead fails this test, do not proceed to install the control module.  

THE 

MOTOR IS DEFECTIVE AND MUST BE REPLACED.

  Installing 

the new control module will cause it to fail also.
  7.  Verify that the replacement control is correct for your application.  

Refer to the manufacturer's authorized replacement list.  

USING THE 

WRONG CONTROL WILL RESULT IN IMPROPER OR NO 
BLOWER OPERATION.

  Orient the control module so that the 3-wire 

motor plug can be inserted into the socket in the control.  Carefully insert 

the plug and press it into the socket until it latches.  

A SLIGHT CLICK 

WILL BE HEARD WHEN PROPERLY INSERTED.

  Finish installing 

the replacement control per one of the three following paragraphs, 8a, 8b or 8c.
 8a. 

IF REPLACING AN ECM 2.0 CONTROL

 (control in cast 

aluminum can with air vents on the back of the can) 

WITH AN ECM 

2.3 CONTROL

 (control containing black potting for water protection 

in black deep-drawn steel case with no vents in the bottom of the can), 

locate the two through-bolts and plastic tab that are packed with the 

replacement control.  Insert the plastic tab into the slot at the perimeter 

of the open end of the can so that the pin is located on the inside of the 

perimeter of the can.  Rotate the can so that the tab inserts into the tab 

locater hole in the endshield of the motor.  Using the two through-bolts 

provided with the replacement control, reattach the can to the motor.

THE TWO THROUGH-BOLTS PROVIDED WITH THE 
REPLACEMENT ECM 2.3 CONTROL ARE SHORTER THAN 
THE BOLTS ORIGINALLY REMOVED FROM THE ECM 2.0 
CONTROL AND MUST BE USED IF SECURE ATTACHMENT OF 
THE CONTROL TO THE MOTOR IS TO BE ACHIEVED.
DO NOT OVERTIGHTEN THE BOLTS.

 

 8b. 

IF REPLACING AN ECM 2.3 CONTROL

 

WITH AN ECM 2.3 

CONTROL

, the plastic tab and shorter through-bolts are not needed.  The 

control can be oriented in two positions 180° apart.  

MAKE SURE THE 

ORIENTATION YOU SELECT FOR REPLACING THE CONTROL 
ASSURES THE CONTROL'S CABLE CONNECTORS WILL BE 
LOCATED DOWNWARD IN THE APPLICATION SO THAT WATER 
CANNOT RUN DOWN THE CABLES AND INTO THE CONTROL.

  

Simply orient the new control to the motor's endshield, insert bolts, and 

tighten.  

DO NOT OVERTIGHTEN THE BOLTS.

 

8c. 

IF REPLACING AN ECM 2.0 CONTROL WITH AN ECM 2.0 

CONTROL (It is recommended that ECM 2.3 controls be used for all 
replacements), 

the new control must be attached to the motor using through 

bolts identical to those removed with the original control.  

DO NOT 

OVERTIGHTEN THE BOLTS.

  9.  Reinstall the blower/motor assembly into the HVAC equipment.  

Follow the manufacturer's suggested procedures.

  10. Plug the 16-pin control plug into the motor.  The plug is keyed.  

Make sure the connector is properly seated and latched.
  11. Plug the 5-pin power connector into the motor.  Even though the 

plug is keyed, 

OBSERVE THE PROPER ORIENTATION.  DO NOT 

FORCE THE CONNECTOR.

  It plugs in very easily when properly 

oriented.  

REVERSING THIS PLUG WILL CAUSE IMMEDIATE 

FAILURE OF THE CONTROL MODULE.

 12. 

Final installation check.  Make sure the motor is installed as follows:

    a. Unit is as far INTO the blower housing as possible.

    b. Belly bands are not on the control module or covering vent holes.

    c. Motor connectors should be oriented between the 4 o’clock and 8  

      o’clock positions when the blower is positioned in its final    

      location and orientation.

    d. Add a drip loop to the cables so that water cannot enter the motor  

      by draining down the cables.  

Refer to Figure 30.

The installation is now complete.  Reapply the AC power to the HVAC 

equipment and verify that the new motor control module is working 

properly.  Follow the manufacturer's procedures for disposition of the old 

control module.

Summary of Contents for Q-TEC Q24H2D Series

Page 1: ...Company Inc Bryan Ohio 43506 Since 1914 Moving ahead just as planned Manual 2100 603 Supersedes NEW File Vol II Tab 14 Date 11 05 13 Models Q24H2D Q30H2D Q36H2D Q42H2D Q48H2D Q60H2D Q TEC SERIES PACK...

Page 2: ...le 2 Electrical Specifications 5 Table 3 Operating Voltage Range 19 Table 4 Wall Thermostats 21 Table 5 Troubleshooting 38 Table 6 Temp vs Resistance of Temp Sensor 39 Table 7 Fan Blade Dimensions 42...

Page 3: ...mmer Manual N Air Conditioning Low Pressure Low Velocity ACCA Manual D or Duct System Design Manual Q Winter and Summer Air Conditioning FOR MORE INFORMATION CONTACT THESE PUBLISHERS ACCA Air Conditio...

Page 4: ...Ambient Control Outdoor Thermostat FILTER OPTIONS X 1 inch Fiberglass Standard F 2 inch Fiberglass P 2 inch Pleated Q 36 H 2 D A 10 X X X X X X CAPACITY 24 2 Ton 30 2 Ton 36 3 Ton 42 3 Ton 48 4 Ton 60...

Page 5: ...0 30 14 10 10 10 14 10 10 10 Q48H2DA0Z A05 A10 A15 230 208 1 1 1 or 2 1 or 2 1 or 2 38 63 88 88 50 70 90 90 8 6 3 3 10 8 8 8 38 38 38 25 50 50 50 50 50 25 50 50 8 8 8 10 8 8 10 10 10 10 10 10 Q48H2DB0...

Page 6: ...Manual 2100 603 Page 6 of 44 FIGURE 1 UNIT DIMENSIONS Q24H2D Q60H2D Q30H2D Q36H2D Q42H2D Q48H2D...

Page 7: ...moved to provide a place to hold the unit The unit can be slid forward on the skid until the front wheels hang over the edge of the skid See Figure 3 B The unit can be tipped forward and slid down the...

Page 8: ...parate equipment required to make up the entire air conditioning system should be carefully read before beginning the installation Note particularly Start Procedure and any tags and or labels attached...

Page 9: ...Manual 2100 603 Page 9 of 44 FIGURE 6 DUCTED APPLICATION FIGURE 5 INSTALLATION WITH DUCT FREE PLENUM...

Page 10: ...ounts on top of the unit and has both vertically and horizontally adjustable louvers on the front discharge grille For hot water coil option a QPBHWxx F for free blow or QPBHWxx D for ducted airflow i...

Page 11: ...he drain is to be routed through an unconditioned space it must be protected from freezing The drain line must be able to be removed from the unit if it is necessary to remove the unit from the wall W...

Page 12: ...RE 11 REAR DRAIN TOP VIEW WALL MAXIMUM 10 FOR REAR DRAIN COUPLINGS NOT SHOWN BUT RECOMMENDED FOR EASE OF REMOVABILITY FOR SERVICE SLEEVE DRAIN LINE WALL BRACKET UNIT FIGURE 10 STANDARD REAR DRAIN FIGU...

Page 13: ...Manual 2100 603 Page 13 of 44 MIS 2469 DRAIN BOX WALL SLEEVE OVERFLOW TUBE CAULK AROUND TUBE FIGURE 12A...

Page 14: ...PLASTIC PIPE NIPPLE HORIZONTAL TO FLOOR TIGHTEN THREADS SO TEE IS THREADS APPLY TEFLON TAPE TO REAR DRAIN CONNECTION IN Q Tec PRODUCT 1 2 SLIP X 1 2 SLIP X 3 4 NPT TEE SUPPLIED WITH DRAIN BOX KIT PLU...

Page 15: ...Manual 2100 603 Page 15 of 44 REMOVE KNOCK OUT FOR INDOOR DRAIN HOSE CONNECTOR MIS 2471 FIGURE 12C If Used...

Page 16: ...RAIN PAN MOVE HOSE FROM ATTACHMENT IN LOWER DRAIN PAN AND SLIDE ONTO DRAIN BOX BARB FITTING SECURING WITH SUPPLIED CLAMP IF OUTDOOR PAN IS BYPASSED WILL REDUCE RISK OF ALGAE GROWTH IN THE OUTDOOR PAN...

Page 17: ...le FIGURE 13A UNIT MOUNTING BOTTOM TRIM PIECE BOTTOM TRIM EXTENSION MOUNTING BRACKET SIDE TRIM 2 PCS SIDE TRIM 2 PCS CABINET SIDE PANEL ENLARGED VIEW OF MOUNTING BRACKET SHOWING SLEEVE TO CABINET ATTA...

Page 18: ...ck both sides of the unit as it is being rolled to keep it centered in the sleeve Also check the alignment to the mounting brackets This unit must be level from side to side If adjustments are necessa...

Page 19: ...the installed KW of electric heat there may be two field power circuits required If this is the case the unit serial plate will so indicate All models are suitable only for connection with copper wire...

Page 20: ...during dehumidification mode the call for cooling takes precedence over the dehumidification and the unit will cool until the thermostat is satisfied Once the call for cooling is satisfied the unit m...

Page 21: ...may result in motor failure FIGURE 16 TABLE 4 WALL THERMOSTATS CONTROLS MIS 1285 Thermostat Predominant Features 8403 067 Carbon Dioxide Sensor with LCD for Sensor Readings 8403 060 1120 445 3 stage C...

Page 22: ...te Black White Black White Black Red Yellow Plug 4 2 3 1 2 3 4 5 6 7 8 9 10 11 12 1 2 3 4 5 6 7 8 9 10 12 W1 E 4102 063 B 8403 060 SC With X Thermostat Option FACTORY INSTALLED JUMPER 1 Dehumidificati...

Page 23: ...ellow Plug 4 2 3 1 2 3 4 5 6 7 8 9 10 11 12 1 2 3 4 5 6 7 8 9 10 12 Red White MIS 2690 C 6 5 And Demand Ventilation FACTORY INSTALLED JUMPER 1 With X Thermostat Option Dehumidification Wiring Diagram...

Page 24: ...Diagram Thermostat Plug 2 Pink Red White Brown Blue Yellow Orange Brown White Purple White Black White Brown Blue Yellow Orange Brown White Purple White Red Red White Red White Red White 1 2 3 4 5 Plu...

Page 25: ...og Out CO Controller Bard Part 8403 067 2 2 1 2 3 4 5 6 Red White 1 COM Yellow Orange Thermostat Blue Brown Red White Black White Red White 4102 066 B Plug 4 1 2 3 4 5 6 7 8 9 10 11 12 L C R W2 B W1 E...

Page 26: ...ermostat Plug 2 Pink Red White Brown Blue Yellow Orange Brown White Purple White Black White Brown Blue Yellow Orange Brown White Purple White Red Red White Red White Red White Black White Black White...

Page 27: ...e leaks and recharges R 410A refrigerant is close to being an azeotropic blend it behaves like a pure compound or single component refrigerant The remaining refrigerant charge in the system may be use...

Page 28: ...age due to phase reversal The phase monitor in this unit is equipped with two LEDs If the Y signal is present at the phase monitor and phases are correct the green LED will light and the compressor co...

Page 29: ...cabinet side panel g Remove screws that attach the duct work to the unit flanges This unit is equipped with four rollers mounted to the base For ease of pulling unit out from the wall you may want to...

Page 30: ...gh the opening in the back of the unit The mist eliminator must be raised up and the bottom can be pulled toward the front of the unit and removed Q Tec ENERGY RECOVERY VENTILATOR Option Before starti...

Page 31: ...Manual 2100 603 Page 31 of 44 FIGURE 22 FRESH AIR DAMPER REMOVAL MOUNTING SCREW...

Page 32: ...Manual 2100 603 Page 32 of 44 FIGURE 23 QERV REMOVAL MOUNTING SCREWS FRONT FILL LOWER BLOWER ASSEMBLY POWER CONNECTOR POWER CONNECTORS...

Page 33: ...g to hold the ball on the seat This will make the method of checking the ball freedom with a magnet difficult Refer to Figures 25 and 26 for the location of the check valve and drain back capillary Wh...

Page 34: ...OR REHEAT COIL Figure 25 shows the refrigerant gas flow through the reheat coil during the dehumidification mode When the unit is in standard cooling Figure 26 or heating mode the reheat coil is inact...

Page 35: ...perating pressures can be observed Pressure curves can be found later in the manual covering all models on both cooling and heating cycles It is imperative to match the correct pressure curve to the u...

Page 36: ...erwise the timing will remain accelerated and run through the 1 minute minimum defrost length sequence in a matter of seconds and will automatically terminate the defrost sequence There is an initiate...

Page 37: ...44 120 SW 1 SW 2 TIME SEC OFF OFF ON ON OFF ON OFF ON 30 60 180 LOW PRESSURE BYPASS TIMER SWITCH FACTORY SETTING 120 SECONDS ACCUMULATED RUN TIME SELECTOR FACTORY SETTING 30 MIN MIS 2684 A ON OFF FIGU...

Page 38: ...eck for 24V between RV C and B C 1 Check control circuit wiring 2 Replace heat pump control Reversing valve solenoid coil defective Check for open or shorted coil Replace solenoid coil Unit will not g...

Page 39: ...43554 60 0 15310 98 0 6098 15 0 139576 23 0 42295 61 0 14921 99 0 5961 14 0 134956 24 0 41077 62 0 14544 100 0 5827 13 0 130506 25 0 39898 63 0 14177 101 0 5697 12 0 126219 26 0 38757 64 0 13820 102...

Page 40: ...s air noise cabinet duct or motor noise interview customer if necessary Air noise High static creating high blower speed Is airflow set properly Does removing filter cause blower to slow down Check f...

Page 41: ...ion d Add a drip loop to the cables so that water cannot enter the motor by draining down the cables Refer to Figure 26 The installation is now complete Reapply the AC power to the HVAC equipment and...

Page 42: ...of refrigerant listed on the serial plate AHRI capacity and efficiency ratings were determined by testing with this refrigerant charge quantity Reference Table 8 The following pressure tables show nom...

Page 43: ...w Side High Side 126 382 129 404 132 427 134 451 137 477 139 504 141 533 143 563 145 594 85 DB 72 WB Low Side High Side 130 395 134 418 137 442 139 467 142 494 144 522 146 552 148 583 150 615 Q48H2 75...

Page 44: ...Cooling Mode Unoccupied 1 X X X X X X X Cooling Mode Occupied 1 X X X X X 1st Stage Heating Occupied 2 X X X X X X X X X 1st Stage Heating Unoccupied 2 X X X X X X X 2nd Stage Heating Occupied 3 X X...

Reviews: