Operation

See Figures 22 and 23 on page 24 for overviews of th-
Tune buttons and icons. 

On/Off

Press and hold power button for 2 seconds to turn th-
Tune on or off.

Heat/Cool Operation

Auto Mode

During Auto mode, the unit will start heating or cooling 
when room temperature falls below or rises above a 
user-defined deadband called the comfort range (see 
Figure 18). This can be changed using the TEC-EYE 
hand-held diagnostic tool—see 

Comfort Range

 on 

page 23. By default, this comfort range is 5°F. For 
example, when room temperature rises above the 
upper limit of the comfort range, a cooling call will be 
activated. This cooling call will remain active until the 
indoor temperature reaches a half degree below the 
setpoint. This operation works in the opposite direction 
for heating. If a room temperature reaches below the 
lower limit of the comfort range, a heating call will be 
activated. Once the indoor temperature rises a half 
degree above the setpoint, the heating call will be 
satisified and heating operations will stop.

Heat Mode

During Heat mode, the unit will only operate heating 
functions to maintain room temperature around the 
setpoint. The comfort range setting will still determine 
the on temperature and the off temperature will be a 
half degree above setpoint.

Cool Mode

During Cool mode, the unit will only operate cooling 
functions (including economizer) to maintain room 
temperature around the setpoint. The comfort range 
setting will still determine the on temperature and the 
off temperature will be a half degree below setpoint.

Staging of Free Cooling and Mechanical Cooling

When connected to the th-Tune, all mechanical 
cooling and free cooling operation (with the exception 
of staging) work as described in MULTI-TEC Service 
Instructions manual 2100-665. When a cooling call 
is first activated, the lowest form of available cooling 
will start. (If free cooling is available, the economizer 
will open and free cooling will begin. If free cooling is 
not available, the first stage of mechanical cooling will 
begin.) At this point, if the indoor temperature begins 
to drop, no additional cooling stages will be activated. 
If the indoor temperature continues to rise or stays 
constant, the next stage of cooling will be turned on. As 
an additional safety measure, if the indoor temperature 
rises 2°F above the comfort range, all available stages 
of cooling will become active to avoid overheating the 
room.

Changing the Setpoint

To change the setpoint, turn the knob (see Figure 19)
on the front of the th-Tune until the desired setpoint is 
reached. Once this is complete, the th-Tune will load 
the new setpoint after the knob has stopped turning for 
3 seconds.

Changing the Clock

To change the time or day of the week, press and hold 
the clock button for 5 seconds. Turn and press the 
knob to set the time and/or day of the week.

Changing to Celsius

Changing to Celsius must be done in the MULTI-TEC 
unit using the TEC-EYE.

Blower Operation

There are two modes of blower operation available while 
using the th-Tune. The first mode operates the blower 
during active heating and cooling calls. The second 
mode operates the blower continuously to continuously 
circulate the air.

FIGURE 18

Comfort Range 

(Examples Shown: A setpoint of 72

˚

 with a 5˚ Range and a 7˚ Range)

Temperature

68˚F

69˚F

70˚F

71˚F

72˚F

73˚F

74˚F

75˚F

76˚F

Heating Operation
Cooling Operation
Comfort Range (5)
Heating Operation
Cooling Operation
Comfort Range (7)

ON  HEATING OFF

OFF COOLING  ON

COMFORT RANGE

ON  HEATING OFF

OFF COOLING  ON

COMFORT RANGE

NOTE:

 

The setpoint is the middle point of the comfort range

Manual 2100-678
Page 

22 of 24

Summary of Contents for MULTI-TEC W18AAPA

Page 1: ...4AAPC W30AAPA W30AAPB W30AAPC W36AAPA W36AAPB W36AAPC W42AAPA W42AAPB W42AAPC W48AAPA W48AAPB W48AAPC W48AAPQ W60AAPA W60AAPB W60AAPC W60AAPQ W18LAPA W24LAPA W24LAPB W30LAPA W30LAPB W30LAPC W36LAPA W3...

Page 2: ...g 23 FIGURES AND TABLES Figure 1 MULTI TEC Model Nomenclature 5 Figure 2 Dimensions 7 Figure 3 Outdoor Sensor Installation 8 Figure 4A W18A W18L W24A W24L Mounting Instructions 9 Figure 4B W30A W30L W...

Page 3: ...attaching the supply and return ducts These instructions explain the recommended method to install the air cooled self contained unit and the electrical wiring connections to the unit These instructio...

Page 4: ...ppropriate to this level is also involved CAUTION Indicate s a hazardous situation which if not avoided could result in minor or moderate injury CAUTION signs without a safety alert symbol may be used...

Page 5: ...ker box see Tables 1 and 2 on pages 17 and 18 High voltage wire of various gauges see Tables 1 and 2 Communication wire 3 wire 20 gauge shielded cable Miscellaneous electrical supplies including rigid...

Page 6: ...that the recirculation and obstruction of condenser discharge air does not occur Recirculation of condenser discharge air can be from either a single unit or multiple units Any object such as shrubber...

Page 7: ...models 1 F G W 5 88 Electric Heat MIS 3889 Electrical Entrances Optional Supply Air Opening Side Wall Mounting Built In Shipping Location Brackets Return Air Opening Top Rain Flashing Bottom Installat...

Page 8: ...walls the wall construction must be strong and rigid enough to carry the weight of the unit without transmitting any unit vibration All walls must be thoroughly inspected to insure that they are capab...

Page 9: ...L DUCT RAIN FLASHING HEATER ACCESS MIS 3157 A Wall Opening and Hole Location View Right Side View RETURN AIR TOP FLASHING AT TIME OF INSTALLATION OPENING THE SIDE MOUNTING FLANGES AND UNDER SEAL WITH...

Page 10: ...BUSTABLE MATERIALS RAIN FLASHING TOP SUPPLY AIR OPENING Right Side View HEATER ACCESS TOP FLASHING AT TIME OF INSTALLATION SEAL WITH BEAD IT IS RECOMMENDED THAT A BEAD OF WALL Wall Opening and Hole Lo...

Page 11: ...RUCTURE 1 SUPPLY AIR IT IS RECOMMENDED THAT A BEAD OF OPENING Right Side View RAIN FLASHING SILICONE CAULKING BE PLACED BEHIND RECOMMENDED 1 CLEARANCE FROM THE SIDE MOUNTING FLANGES AND UNDER TOP FLAS...

Page 12: ...ED DIMENSIONS TO MAINTAIN OPENING COMBUSTIBLE MATERIALS B D E PANEL AIR DUCT IS REQUIRED 32 10 1 2 Right Side View SUPPLY AIR RECOMMENDED 1 CLEARANCE FROM MIS 3789 RAIN FLASHING REQUIRED DIMENSIONS TO...

Page 13: ...L BEFORE MOUNT ON UNIT OPENING BEFORE INSTALLATION BOTTOM MOUNTING CONCRETE BLOCK WALL INSTALLATION BRACKET MOUNT ON OPENING WOOD OR STEEL SIDING OPENING INSTALLING UNIT RETURN AIR WALL STRUCTURE RETU...

Page 14: ...MENSIONS 2 x 4 S 2 x 6 S OR STRUCTURAL STEEL ATTACH TO TOP 1 000 CLEARANCE 1 000 CLEARANCE PLATE OF WALL C SEE UNIT DIMENSIONS FIGURE 1 2 OPENING RETURN DUCT 2 x 6 ATTACH TO BOTTOM OVER FRAME PLATE OF...

Page 15: ...CEILING RAIN FLASHING RAIN FLASHING SUPPLY DUCT MAY BE LOCATED IN AN ATTIC OR BELOW CEILING RAFTERS AS SHOWN FINISHEDCEILING WALL CLOSETWALL SURFACE SLEEVE SUPPLY DUCT MAY BE LOCATED IN AN ATTIC OR B...

Page 16: ...hand corner of the disconnect opening under the disconnect access panel straight out This tab will now line up with the slot in the door When shut a padlock may be placed through the hole in the tab...

Page 17: ...1 or 2 32 32 58 84 110 50 50 60 90 125 8 8 6 4 2 10 10 10 8 6 58 58 26 52 60 60 30 60 6 6 10 6 10 10 10 10 W42AAPB00 B0Z B06 B09 B15 B18 230 208 3 1 1 1 1 1 25 25 33 51 60 35 35 35 60 60 8 8 8 6 6 10...

Page 18: ...4 35 35 50 60 90 8 8 8 6 4 10 10 10 10 8 58 26 60 30 6 10 10 10 W30LAPB00 B0Z B09 B15 230 208 3 1 1 1 19 33 51 20 35 60 12 8 6 12 10 10 W30LAPC00 C0Z C09 C15 460 3 1 1 1 9 17 26 15 20 30 14 12 10 14 1...

Page 19: ...ower will not run until the wall unit is turned back ON by the TEC EYE To turn the unit on or off with TEC EYE 1 Connect the TEC EYE diagnostic tool to the control board located in the unit 2 Press ME...

Page 20: ...point of attachment and separate cover from base FIGURE 13 Remove Cover A1 Remove this screw Press here Power and Communications Wiring Power Wiring For the power wiring use standard 18 gauge twisted...

Page 21: ...ommunications Connections Communications Power If power is connected to these terminals the th Tune will be damaged 24V m GND Tx Rx WALL UNIT G G0 Tx Rx Rx Tx Rx Tx GND TH TUNE MIS 3912 see Figure 5 F...

Page 22: ...ing work as described in MULTI TEC Service Instructions manual 2100 665 When a cooling call is first activated the lowest form of available cooling will start If free cooling is available the economiz...

Page 23: ...ll icon will flash for 10 seconds accompanied by an audible tone alarm After 10 seconds the bell icon will stop flashing and become solid and the audible tone alarm will be silenced If any alarm is pr...

Page 24: ...ect temperature setpoint FIGURE 23 th Tune Icons Overview Rotating Display Area This area displays the following information in the following order and rotates through them every 5 seconds 1 Clock Day...

Reviews: