Manual 2100-677B 

Page 

2 of 2

Execute a run test on each unit to verify the equipment is 

functioning correctly (TEC-EYE)

1.  Use UP or DOWN keys to scroll to 

Run Test A11 

(MULTI-TEC units) or 

Run Test A10

 (WR Series units).

2.  Press ENTER key to scroll to 

Run Test Enable

 

parameter.

3.  Use UP or DOWN key to change value to 

ON

. The run 

test will begin.

See Installation Instructions 2100-676 if additional 
information on run testing units is needed.

Clear unit alarm logs (TEC-EYE)

To clear the wall-mount unit alarm logs:
1.  Press MENU key to go to the Main Menu screen.
2.  Use UP or DOWN keys and ENTER key to enter 

password 1313.

3.  Press UP or DOWN keys to scroll to 

Settings

; press 

ENTER key.

4.  Press UP or DOWN keys to scroll to 

Initialization

; press 

ENTER key.

5.  Press ENTER key to scroll to 

Delete Alarm Logs? 

(MULTI-TEC units) or 

Clear Alarm Logs?

 (WR Series).

6.  Press UP or DOWN key to value to 

YES

; press ENTER key.

After first unit has been set up and configured, follow the 
above steps to set up and configure the remaining units.

Set LC Controller Timezone and Date/Time  

(LC Controller)

1.  Press MENU key to access the Main Menu screen.
2.  Use UP or DOWN keys and ENTER key to enter 

password 1313.

3.  Press the UP or DOWN keys to scroll to the 

Settings

 

menu; press ENTER key.

4.  Press UP or DOWN keys to scroll to 

Date/Time

 menu; 

press ENTER key.

5.  Press ENTER key to scroll to the desired value to be 

changed.

6.  Press UP or DOWN keys to change the value.
7.  Press ENTER key to save.
8.  Press the ESCAPE key several times to return to Main 

Menu screen. 

Configure sensors (LC Controller)

The LC is capable of utilizing four temperature sensors and 
three humidity sensors. The controller must be configured 
to match the sensors for the shelter. The available sensors 
are Zone 1 Indoor Humidity, Zone 2 Indoor Humidity, Zone 
3 Indoor Humidity, Zone 1 Indoor Temperature, Zone 1 
Remote Temperature, Zone 2 Remote Temperature and Zone 
3 Remote Temperature.
The Zone 1 Indoor Humidity and Zone 1 Indoor Temperature 
sensors are enabled by default. The additional indoor humidity 
and indoor temperature sensors are disabled by default.
See Installation Instructions 2100-676 if information is 
needed on configuring (enabling/disabling) sensors.

If necessary, the sensors can be calibrated at this time too. For 
information on calibrating the sensors, see manual 2100-676.
See LC6000 Service Instructions manual 2100-669 for 
information on setting up the smoke, hydrogen and generator 
relays (if applicable).

Enter total number of units (LC Controller)

1.  Press MENU key to go to the Main Menu screen.
2.  Use UP or DOWN keys and ENTER key to enter 

password 1313.

3.  Press UP or DOWN keys to scroll to 

Sys Config

; press 

ENTER key.

4.  Press UP or DOWN keys to scroll to 

General

; press 

ENTER key.

5.   Press ENTER key to scroll to 

Total Units

.

6.  Press UP or DOWN keys to adjust value to correct 

number of units.

7.  Press ENTER key to save.

Verify units are online (LC Controller)

Once a unit is uniquely addressed, communication can be 
verified at the LC controller.
With the correct number of units set at the LC controller, 
each unit can be remotely viewed from the LC controller 
Information screens.
To view these screens:
1. Press 

ESCAPE key to view the Status screen. (May need 

to be pressed more than once.)

2.  Press UP or DOWN key until the Quick Menu in the 

lower right corner of the screen displays the Information 
icon (         ); press ENTER key.

3.  Press UP or DOWN keys to scroll through the Information 

screens until the desired unit Information screen appears.

 

In addition to being able to remotely view the units, an 
alarm will be generated on the LC controller for units not 
communicating.

Clear controller alarm logs (LC Controller)

To clear the LC controller alarm logs:
1.  Press MENU key to go to the Main Menu screen.
2.  Use UP or DOWN keys and ENTER key to enter 

password 1313.

3.  Press UP or DOWN keys to scroll to 

Settings

; press 

ENTER key.

4.  Press UP or DOWN keys to scroll to 

Initialization

; press 

ENTER key.

5.  Press ENTER key to scroll to 

Delete Alarm Logs?

6.  Press UP or DOWN key to value to 

YES

; press ENTER key.

7.  Press ESCAPE key several times to return to Main Menu 

screen.

Once all the installation steps have been completed, all 
alarms and alarm logs have been cleared and system 
verification and run test results were satisfactory, the 
installation can now be considered “complete”.