MULTI-TEC

®

/WR Series/LC6000 Free Cooling Unit System

Quick Start Guide

This quick start guide is designed to lead the installer 
through the steps necessary for setting up MULTI-TEC and/or 
WR Series wall-mount units with an LC6000 controller. See 
the latest versions of MULTI-TEC/WR Series/LC6000 System 
Installation Instructions 2100-676, MULTI-TEC Service 
Instructions 2100-665, WR Series Service Instructions 
2100-688 and LC6000 Service Instructions 2100-669 for 
more detailed information on the installation, service and 
maintenance of the MULTI-TEC/WR Series/LC6000 system.
The LC6000 controller and TEC-EYE

TM

 hand-held diagnostic 

tool will both be used in this installation. The TEC-EYE 
diagnostic tool is shipped inside the controller.

6.  Press UP or DOWN keys to change address to value 

between 1 and 14.

 

NOTE:

  Each unit must have a unique address for the 

communication to work properly. Bard also 

recommends labeling each unit for ease in 

identification.

7.  Press ENTER key to save and scroll to 

Unit Zone

8.  If desired, press UP or DOWN keys to change the value 

to the desired zone.

9.  Press ENTER key to scroll to 

UOM

.

10. Press UP or DOWN keys to change the value from 

USA

 

to 

SI

NC

,

 LON

CAN

 or 

UK

. Units are preconfigured for 

each selection.

11.  Press ENTER key to save.

WR Series Units: Address each wall unit and select unit of 

measure (UOM), unit zone and economizer type.

The address of the unit being looked at will be listed in the 
upper right hand corner on the status screen. The available 
addresses are 1-14.
1.  Connect TEC-EYE to wall-mount unit.
2.  Press MENU key to access the Main Menu screen. 
3.  Press UP or DOWN keys and ENTER key to enter 

password 1313.

4.  Press UP or DOWN keys to scroll to 

Sys Config

; press 

ENTER key.

5.  Press ENTER key to scroll to 

Controller Address

.

6.  Press UP or DOWN keys to change address to value 

between 1 and 14.

 

NOTE:

  Each unit must have a unique address for the 

communication to work properly. Bard also 

recommends labeling each unit for ease in 

identification.

7.  Press ENTER key to scroll to 

UOM

.

8.   Press UP or DOWN keys to change the value from 

USA

 

to 

SI

NC

,

 LON

CAN

 or 

UK

. Units are preconfigured for 

each selection.

9.  Press ENTER key to save and scroll to 

Unit Zone

10.  If desired, press UP or DOWN keys to change the value 

to the desired zone.

11.  Press ENTER key to save and move the cursor back to 

the top left position. 

12.  Press DOWN key to navigate to 

Economizer Setup (A2)

 

screen.

13.  Press ENTER key to scroll to 

Type

.

14.  Press UP or DOWN keys to change economizer type to 

None

Drybulb

Temperature and Humidity

 or 

Enthalpy

.

15.  Press ENTER key to save.

Manual 2100-677B 

Date 4-6-18

It is important to check the software version during 

installation to ensure that the latest version has 

been installed. Current software versions, change 

log and installation instructions are available on 

the Bard website at 

http://www.bardhvac.com/

software-download/

NOTICE

SYSTEM SET-UP

S

et up and configuration must be done to each wall-mount 

unit (MULTI-TEC or WR Series) using the TEC-EYE hand-
held diagnostic tool. Use the LC6000 controller for the 
remaining steps.

IMPORTANT:

 

When working with circuit board components, 

Bard recommends the use of an anti-static 

wrist strap to prevent static electricity shorts to 

electronic controls.

NOTE: 

The first step in the set-up process, addressing each 

wall unit and selecting unit zone and unit of measure, 

are slightly different in the MULTI-TEC and WR Series 

wall-mount units. Follow the appropriate steps for the 

unit being set up.

MULTI-TEC Units: Address each wall unit and select unit 

zone and unit of measure (UOM)

The address of the unit being looked at will be listed in the 
upper right hand corner on the status screen. The available 
addresses are 1-14.
1.  Connect TEC-EYE to wall-mount unit.
2.  Press MENU key to access the Main Menu screen. 
3.  Press UP or DOWN keys and ENTER key to enter 

password 1313.

4.  Press UP or DOWN keys to scroll to 

Sys Config

; press 

ENTER key.

5.  Press ENTER key to scroll to 

Unit Address

.