Bard ERVF-A3 Installation Instructions Manual Download Page 12

Manual 2100-512B
Page 

12 of 15

Control Wiring

The ERVF-*3/CHERV-*3 comes from the factory with 
the low voltage control wires not wired into the wall 
mount low voltage terminal strip. Care must be taken 
when deciding how to control the operation of the 
ventilator. When designing the control circuit for the 
ventilator the following requirements must be met.

Control Requirements

1.  Indoor blower motor must be run whenever the 

ERVF-*3/CHERV-*3 is run.

2.  Select the correct motor speed tap in the  

ERVF-*3/CHERV-*3. Using Table 1 to determine 
the motor speed needed to get the desired amount 
of ventilation air needed. For instance, do not use 
the high speed tap on a ERVF-A3 if only 250 CFM 
of ventilation air is needed; use the low speed 
tap. Using the high speed tap would serve no 
useful purpose and significantly affect the overall 
efficiency of the air conditioning system. System 
operating cost would also increase.

3.  Run the ERVF-*3/CHERV-*3 only during periods 

when the conditioned space is occupied. Running 
the ERVF-*3/CHERV-*3 during unoccupied periods 
wastes energy, decreases the expected life of 
the ERVF-*3/CHERV-*3 and can result in a large 
moisture buildup in the structure.  The ERVF-*3/
CHERV-*3 removes 60 to 70% of the moisture 
in the incoming air, not 100% of it. Running 
the ERVF-*3/CHERV-*3 when the structure is 
unoccupied allows moisture to build up in the 
structure because there is little or no cooling load. 
Thus, the air conditioner is not running enough to 
remove the excess moisture being brought in. Use 
a control system that in some way can control the 
system based on occupancy.

Recommended Control Sequences

Several possible control scenarios are listed below:
1.  Use a programmable electronic thermostat 

with auxiliary terminal to control the ERVF-*3/
CHERV-*3 based on daily programmed occupance 
periods. Bard markets and recommends the Bard 
Part No. 8403-060 programmable electronic 
thermostat for air conditioner and heat pump 
applications.

The units are set from the factory with the exhaust 
blower on the low speed and the intake blower on 
medium speed. Moving the speed taps located in the 
control panel can change the blower speed of the 
intake and exhaust.  See Figure 6A on page 11.

TABLE 1

2.  Use a motion sensor in conjunction with a 

mechanical thermostat to determine occupancy in 
the structure. Bard markets the CS2000A for this 
use.

3.  Use a DDC control system to control the ERVF-*3/

CHERV-*3 based on a room occupancy schedule to 
control the ERVF-*3/CHERV-*3.

4.  Tie the operation of the ERVF-*3/CHERV-*3 into 

the light switch. The lights in a room are usually on 
only when occupied.

5.  Use a manual timer that the occupants turn to 

energize the ERVF-*3/CHERV-*3 for a specific 
number of hours.

6.  Use a programmable mechanical timer to energize 

the ERVF-*3/CHERV-*3 and indoor blower during 
occupied periods of the day.

Ventilation Airflow

The ERVF-*3 and CHERV-*3 are equipped with a 
3-speed motor to provide the capability of adjusting 
the ventilation rates to the requirements of the specific 
application by simply changing motor speeds.

IMPORTANT

Operating the ERVF-*3/CHERV-*3 during 

unoccupied periods can result in a build up of 

moisture in the structure.

!

WARNING

Open disconnect to shut all power OFF before 

making adjustments to the speed taps. Failure 

to do so could result in injury or death due to 

electric shock.

Ventilation Air (CFM)

Model

High

Speed

(Black)

Medium

Speed

(Blue)

Low

Speed

(Red)

ERVF-A3

CHERV-A3

ERVF-C3

CHERV-C3

400

325

250

Summary of Contents for ERVF-A3

Page 1: ...ENERGY RECOVERY VENTILATOR WITH EXHAUST For Use with Bard 2 1 2 through 3 Ton Wall Mount Air Conditioners and Heat Pumps INSTALLATION INSTRUCTIONS Bard Manufacturing Company Inc Bryan Ohio 43506 www...

Page 2: ...Control Wiring 12 Control Requirements 12 Recommended Control Sequences 12 Ventilation Airflow 12 Energy Recovery Ventilator Maintenance 13 Figures Figure 1 Removing Access Panels 6 Figure 2 Removing...

Page 3: ...mer and winter conditions Provides required ventilation to meet the requirements of ASHRAE 62 1 standard Electrical Specifications NOTE During operation below 5 F outdoor temperature freezing of moist...

Page 4: ...6862 5400 5400 5400 12150 6525 1462 0 0 11407 7751 4460 3510 3510 3510 7897 4241 950 0 0 90 80 75 70 65 60 28080 19080 10980 6480 6480 6480 21600 12600 4500 0 0 17690 12020 6917 4082 4082 4082 13608 7...

Page 5: ...ese 24 volt control wires control the starting and stopping of the energy recovery ventilator and can be independently controlled by an energy management control or timer See separate section on Contr...

Page 6: ...vent option panel Refer to the Control Wiring Section for suggested control schemes After wiring replace all panels 16 Replace the vent option access panel with the new panel provided Attach air intak...

Page 7: ...Manual 2100 512B Page 7 of 15 FIGURE 2 Removing Filter and Grille REMOVE DISCARD...

Page 8: ...Manual 2100 512B Page 8 of 15 FIGURE 3 Running Wiring FIGURE 3 INSET SIDE VIEW SEE STEP 5 OF INSTRUCTIONS...

Page 9: ...Page 9 of 15 MIS 2641 INSTALL 1 480701 0 CAP AS SHOWN AND WIRE PER WIRING DIAGRAM FROM HEAT RECOVERY ASSEMBLY LOW VOLTAGE WIRES TEMPORARY CONNECTION FOR TESTING SEE RECOMMENDED CONTROL SEQUENCES FIGUR...

Page 10: ...Manual 2100 512B Page 10 of 15 FIGURE 5 Replacing Access Panel...

Page 11: ...Manual 2100 512B Page 11 of 15 FIGURE 6 Airflow Diagram FIGURE 6A Speed Tap Label...

Page 12: ...l possible control scenarios are listed below 1 Use a programmable electronic thermostat with auxiliary terminal to control the ERVF 3 CHERV 3 based on daily programmed occupance periods Bard markets...

Page 13: ...grease tars and dirt that can impede performance or generate odors Washing of the desiccant surfaces is required to remove contaminate buildups that can reduce adsorption of water molecules The contin...

Page 14: ...evaporator coil cleaner or alkaline detergent solution such as 409 NOTE Do not use acid based cleaners aromatic solvents temperatures in excess of 170 F or steam Damage to the wheel may result Do not...

Page 15: ...Manual 2100 512B Page 15 of 15 FIGURE 8 Hub Assembly with Ball Bearings...

Reviews: