Installation
Disconnect all power to wall-mount unit. Remove
control panel outer and inner covers, right side
condenser inlet grille and front service access panel.
1. Mount outdoor thermostat 910-2110 in the control
panel with screws provided as shown in Figure 1.
2. Route wires through the wire channel in the control
panel to the compressor control module and the
compressor contactor as shown in Figure 2.
3. Route thermostat bulb through bushing in
condenser partition and mount to the fan shroud
with the clamp and screw provided as shown in
Figure 1.
4. Recheck wiring. Refer to Figure 2 and the unit
wiring diagram. Set thermostat to the desired
cutout temperature for the compressor. 0º or above
is recommended.
5. Attach “CMA-43” label to the inner control panel
cover above the unit wiring diagrams.
6. Replace all panels and covers. This completes the
installation.
MIS-4112
ATTACH THE END OF THE
CAPILLARY TUBE TO CABLE
CLAMP PART #7950-020
AT THE MIDDLE SCREW ON
THE FAN SHROUD. CLAMP
SHOULD GO ON LEFT SIDE
OF SCREW.
OUTDOOR T-STAT
PART #8408-028
RUN THE CAPILLARY COPPER TUBE
DOWN TO THE CONDENSOR SECTION
FIGURE 1