SEQUENCE OF OPERATION

COOLING STAGE 1

  –  Circuit R-Y makes at thermostat 

pulling in compressor contactor, starting the compressor and 
outdoor motor.  The G (indoor motor) circuit is automatically 
completed on any call for cooling operation or can be energized 
by manual fan switch on subbase for constant air circulation.

COOLING STAGE 2

  –  Circuit R-Y1 makes at the thermostat 

energizing the 2nd stage solenoid in the compressor.  Default 
position is not energized.  Compressor will run at low capacity 
until this solenoid is energized.

HEATING STAGE 1

  – A 24V solenoid coil on reversing 

valve controls heating cycle operation.  Two thermostat options, 
one allowing “Auto” changeover from cycle to cycle and the 
other constantly energizing solenoid coil during heating season 
and thus eliminating pressure equalization noise except during 
defrost, are to be used.  On “Auto” option a circuit is completed 
from R-B and  R-Y on each heating “on” cycle, energizing 
reversing valve solenoid and pulling in compressor contactor 
starting compressor and outdoor motor.  R-G also make 
starting indoor blower motor.  Heat pump heating cycle now 
in operation.  The second option has no “Auto” changeover 
position, but instead energizes the reversing valve solenoid 
constantly whenever the system switch on subbase is placed in 
“Heat” position, the “B” terminal being constantly energized 
from R.  A thermostat demand for Stage 1 heat completes R-Y 
circuit, pulling in compressor contactor starting compressor and 
outdoor motor.  R-G also make starting indoor blower motor.

HEATING STAGE 2

  – Circuit R-Y2 makes at the thermostat 

energizing the 2nd stage solenoid in the compressor.

PRESSURE SERVICE PORTS

High and low pressure service ports are installed on all units 
so that the system operating pressures can be observed.  
Pressure tables can be found later in the manual covering all 
models.  It is imperative to match the correct pressure table to 
the unit by model number.  See Tables 5A & 5B.

DEFROST CYCLE

The defrost cycle is controlled by temperature and time on the 
solid state heat pump control.
When the outdoor temperature is in the lower 40°F temperature 
range or colder, the outdoor coil temperature is 32°F or below.  
This coil temperature is sensed by the coil temperature sensor 
mounted near the bottom of the outdoor coil.  Once coil 
temperature reaches 30°F or below, the coil temperature sensor 
sends a signal to the control logic of the heat pump control and 
the defrost timer will start accumulating run time.
After 30, 60 or 90 minutes of heat pump operation at 30°F 
or below, the heat pump control will place the system in the 
defrost mode.
During the defrost mode, the refrigerant cycle switches back 
to the cooling cycle, the outdoor motor stops, electric heaters 
are energized, and hot gas passing through the outdoor coil 
melts any accumulated frost.  When the temperature rises to 
approximately 57°F, the coil temperature sensor will send a 
signal to the heat pump control which will return the system to 
heating operations automatically.
If some abnormal or temporary condition such as a high wind 
causes the heat pump to have a prolonged defrost cycle, the 
heat pump control will restore the system to heating operation 
automatically after 8 minutes.

The heat pump defrost control board has an option of 30, 60 
or 90-minute setting.  By default, this unit is shipped from 
the factory with the defrost time on the 60 minute pin.  If 
circumstances require a change to another time, remove the 
wire from the 60-minute terminal and reconnect to the desired 
terminal.  Refer to Figure 8.
There is a cycle speed up jumper on the control.  This can be 
used for testing purposes to reduce the time between defrost 
cycle operation without waiting for time to elapse.
Use a small screwdriver or other metallic object, or another 
¼ inch QC, to short between the 

SPEEDUP 

terminals to 

accelerate the HPC timer and initiate defrost.
Be careful not to touch any other terminals with the instrument 
used to short the 

SPEEDUP

 terminals.  It may take up to 10 

seconds with the 

SPEEDUP

 terminals shorted for the speedup 

to be completed and the defrost cycle to start.

As soon as the defrost cycle kicks in remove the shorting 
instrument from the SPEEDUP terminals. 

 Otherwise the 

timing will remain accelerated and run through the 1-minute 
minimum defrost length sequence in a matter of seconds and 
will automatically terminate the defrost sequence.
There is an initiate defrost jumper (sen jump) on the control 
that can be used at any outdoor ambient during the heating 
cycle to simulate a 0° coil temperature.
This can be used to check defrost operation of the unit without 
waiting for the outdoor ambient to fall into the defrost region.
By placing a jumper across the 

SEN JMP

 terminals (a ¼ inch 

QC terminal works best) the defrost sensor mounted on the 
outdoor coil is shunted out & will activate the timing circuit.  
This permits the defrost cycle to be checked out in warmer 
weather conditions without the outdoor temperature having to 
fall into the defrost region.
In order to terminate the defrost test the 

SEN JMP

 jumper must 

be removed.  If left in place too long, the compressor could 
stop due to the high pressure control opening because of high 
pressure condition created by operating in the cooling mode 
with outdoor fan off.  Pressure will rise fairly fast as there is 

likely no actual frost on the outdoor coil in this artificial test 

condition.
There is also a 5-minute compressor time delay function built into 
the HPC.  This is to protect the compressor from short cycling 
conditions.  The board’s LED will have a fast blink rate when in 
the compressor time delay.  In some instances, it is helpful to the 
service technician to override or speed up this timing period, and 
shorting out the 

SPEEDUP

 terminals for a few seconds can do this.

Low Pressure Switch Bypass Operation

 - The control has a 

selectable (SW1) low pressure switch bypass set up to ignore 

the low pressure switch input during the first (30, 60, 120 or 180 

seconds) of “Y” operation.
After this period expires, the control will then monitor the low 
pressure switch input normally to make sure that the switch is 
closed during “Y” operation.

High Pressure Switch Operation

 - The control has a built-in lockout 

system that allows the unit to have the high pressure switch trip up 
to two times in one hour and only encounter a “soft” lockout.  A 
“soft” lockout shuts the compressor off and waits for the pressure 
switch to reset, which at that point then allows the compressor to 
be restarted as long as the 5-minute short cycle timer has run out.  
If the high pressure switch trips a third time within one hour, the 
unit is in “hard” lockout indicating something is certainly wrong 
and it will not restart itself.

Summary of Contents for C24H1

Page 1: ...RUCTIONS WALL MOUNTED PACKAGE HEAT PUMPS MODELS C24H1 C30H1 C36H1 C42H1 C48H1 C60H1 Manual 2100 586B Supersedes 2100 586A File Volume III Tab 17 Date 11 27 13 Bard Manufacturing Company Inc Bryan Ohio...

Page 2: ...ications C H 22 Table 7 Indoor Blower Performance 23 Getting Other Information and Publications 3 Wall Mount General Information Wall Mount Model Nomenclature 4 Shipping Damage 4 General 4 Duct Work 5...

Page 3: ...ter and Summer Air Conditioning Duct Design for Residential ACCA Manual D Winter and Summer Air Conditioning and Equipment Selection FOR MORE INFORMATION CONTACT THESE PUBLISHERS ACCA Air Conditioning...

Page 4: ...o methods of Air Conditioning Contractors of America ACCA The air duct should be installed in accordance with the Standards of the National Fire Protection Association for the Installation of Air Cond...

Page 5: ...t is used Contact distributor or factory for ordering information If using a return air filter grille filters must be of sufficient size to allow a maximum velocity of 400 fpm NOTE If no return air du...

Page 6: ...to front right of supply flange for shipping under back bend of top 6 Position unit in opening and secure with 5 16 lag bolts use 7 8 inch diameter flat washers on the lag bolts 7 Secure rain flashing...

Page 7: ...S S M 44 L Q P S N O E R S S B Bottom Installation Bracket optional use for direct mount not used when unit installed with curb FIGURE 2 All dimensions are in inches Dimensional drawings are not to s...

Page 8: ...LEARANCE ON ALL RAIN FLASHING COMBUSTIBLE MATERIALS DUCT TOP FLASHING AT TIME OF INSTALLATION 1 4 MIN CLEARANCE FROM REQUIRED DIMENSIONS TO MAINTAIN OPENING ENTIRE LENGTH OF TOP MATERIALS NOTES OF CAU...

Page 9: ...TURE 1 SUPPLY AIR IT IS RECOMMENDED THAT A BEAD OF OPENING Right Side View RAIN FLASHING SILICONE CAULKING BE PLACED BEHIND RECOMMENDED 1 CLEARANCE FROM THE SIDE MOUNTING FLANGES AND UNDER TOP FLASHIN...

Page 10: ...This is required for the first 3 feet of ducting It is important to insure that the 1 4 inch minimum spacing is maintained at all points Failure to do this could result in overheating the combustible...

Page 11: ...IR FACTORY SUPPLIED RAIN FLASHING SUPPLY AIR MIS 548 A SIDE VIEW I A C K E 1 000 B 1 000 SUPPLY DUCT OVER FRAME INTERIOR FINISHED WALL ALL AROUND DUCT FRAMING MATERIAL EXTERIOR FINISH WALL OPENING FOR...

Page 12: ...WALL OPENING W GRILLE SUPPLY DUCT MAYBE LOCATED IN AN ATTIC OR BELOW CEILING RAFTERS AS SHOWN CEILING RAIN RETURN AIR SLEEVE WALL SUPPLY AIR DUCT RAFTERS RAFTERS RETURN AIR OPENING W GRILLE RAIN FALSE...

Page 13: ...ccess panel straight out This tab will now line up with the slot in the door When shut a padlock may be placed through the hole in the tab preventing entry See Start Up section for important informati...

Page 14: ...tiple leaks and recharges R 410A refrigerant is close to being an azeotropic blend it behaves like a pure compound or single component refrigerant The remaining refrigerant charge in the system may be...

Page 15: ...However reverse operation for over one hour may have a negative impact on the bearing due to oil pump out NOTE If compressor is allowed to run in reverse rotation for several minutes the compressor s...

Page 16: ...heat pump defrost control board has an option of 30 60 or 90 minute setting By default this unit is shipped from the factory with the defrost time on the 60 minute pin If circumstances require a chang...

Page 17: ...25 120 SW 1 SW 2 TIME SEC OFF OFF ON ON OFF ON OFF ON 30 60 180 MIS 2668 A OFF LOW PRESSURE BYPASS TIMER SWITCH FACTORY SETTING 120 SECONDS ACCUMULATED DEFROST TIME TIMER FACTORY SETTING 60 MIN ON FIG...

Page 18: ...between RV C and B C 1 Check control circuit wiring 2 Replace heat pump control Reversing valve solenoid coil defective Check for open or shorted coil Replace solenoid coil Unit will not go into defr...

Page 19: ...8 36 29157 74 10762 112 4464 1 88139 37 28355 75 10501 113 4367 0 85371 38 27577 76 10247 114 4274 1 82699 39 26823 77 10000 115 4182 2 80121 40 26092 78 9760 116 4093 3 77632 41 25383 79 9526 117 400...

Page 20: ...th this refrigerant charge quantity The following pressure tables show nominal pressures for the units Since many installation specific situations can affect the pressure readings this information sho...

Page 21: ...GH SIDE 133 302 133 321 133 341 134 365 136 391 137 418 138 449 141 481 143 516 146 553 80 DB 67 WB LOW SIDE HIGH SIDE 142 310 142 329 142 350 143 374 145 401 146 429 148 460 151 493 153 529 156 567 8...

Page 22: ...60 1 1 22 30 10 10 A04 1 42 50 8 10 AS8 1 48 50 8 10 AF8 1 or 2 63 70 6 8 22 42 30 45 10 8 10 10 C24H1 B0Z 230 208 60 3 1 15 20 12 12 B06 1 33 35 8 10 B09 1 42 45 8 10 C30H1 A0Z 230 208 60 1 1 23 30...

Page 23: ...hese units are equipped with a variable speed ECM indoor motor that automatically adjusts itself to maintain approximately the same rate of indoor airflow in both heating cooling dry wet coil conditio...

Page 24: ...it s air noise cabinet duct or motor noise interview customer if necessary Air noise High static creating high blower speed Is airflow set properly Does removing filter cause blower to slow down Check...

Page 25: ...is correct for your application Refer to the manufacturer s authorized replacement list USING THE WRONG CONTROL WILL RESULT IN IMPROPER OR NO BLOWER OPERATION Orient the control module so that the 3 w...

Reviews: