Bard BrightStat  8403-081 Installation And Application Instructions Download Page 14

Manual 2100-680 

Page 

14 of 18

Example of Non-Recommended Deployment 

The illustration below shows four room controllers (two 
for each room) installed in non-ideal locations for the 
two rooms.
The examination room shows one room controller 
installed in a low traffic area near the door, and a 
second room controller installed on the wall directly 
opposite the door. For the room controller installed 
in the corner wall, the PIR could be blocked by the 
opened door, while occupant traffic could also be 
minimal in this area of the room. For the second room 
controller installed opposite the door, the PIR detection 
could fall outside the specified detection zone, while 
at the same time most occupant movement would not 
be lateral to the PIR, thereby not respecting optimal 
crossing patterns for PIR detection. 

Non-Recommended Installation

The waiting room shows one room controller installed 
in the corner of the room, and a second room controller 
installed beside the reception area. For the room 
controller installed in the corner, the opening/closing of 
the door creates high probability that the PIR would get 
blocked, and therefore, occupancy going undetected. 
For the room controller installed beside the reception 
area, occupant traffic could fall outside the detection 
zone, and the receptionist would often be below the 
5' recommended installation height for the room 
controller. 

Examination Room

Waiting Room

Summary of Contents for BrightStat 8403-081

Page 1: ...f 18 Bard Manufacturing Company Inc Bryan Ohio 43506 www bardhvac com Manual 2100 680 Supersedes NEW Date 8 29 18 INSTALLATION AND APPLICATION INSTRUCTIONS BrightStat Air Conditioner Heat Pump Room Co...

Page 2: ...roller Electronic controls are static sensitive devices Discharge yourself correctly before manipulating and installing room controller A short circuit or wrong wiring may permanently damage controlle...

Page 3: ...Manual 2100 680 Page 3 of 18...

Page 4: ...htStat Controller Models Bard Part Number Description Part Number Found on Back of Controller 8403 081 With Humidity and Motion Sensors VT8650U5500B 8403 082 With Motion Sensor VT8600U5500B 8403 083 W...

Page 5: ...duration determined by ToccTime parameter Options Wireless adapter modules for BACnet models are available Three 3 universal inputs can be used and configured for advanced functionality as required b...

Page 6: ...FIGURE 2 Install Base FIGURE 3 Re Install Cover 3 Read FCC ID and IC label installed in cover before installing any wireless product 4 Ensure correct side of base faces up 5 Pull cables 6 15 cm out f...

Page 7: ...ternal sensor Remote mount temperature sensors inputs use 10K type 2 NTC thermistors Features Each sensor can be configured for various averaging combinations See Advanced Programming User Interface S...

Page 8: ...Interface Shown What is displayed is dependent on the User Home Menu and Interface HMI selected during the setup process See BrightStat Advance Programming User Interface Setup Guide 2100 681 Time Sy...

Page 9: ...ice configuration components Controller is shipped without password protection Discover Mode The controller becomes discoverable on the wireless ZigBee network for 1 minute this button is hidden if Zi...

Page 10: ...updated or reset completely The following table gives an indication of the expected clock performance after a power outage TABLE 4 Expected Clock Performance After Power Outage Outage Duration Room Co...

Page 11: ...ble parameter the room switches to Unoccupied mode and uses its Unoccupied setpoints 140O Top view Side view Lateral movement Forward movement 15 O 15 O 20 ft 6 m 20 ft 16 ft Top view 20 ft 6 m 140 O...

Page 12: ...points in unoccupied zones during scheduled periods Typical Savings of 10 30 0 5 10 15 20 25 30 35 40 45 50 55 60 65 70 75 80 85 0 2 4 6 8 10 12 14 16 18 20 22 24 Time of Day EST Energy Usage KWh 0 10...

Page 13: ...ontrollers installed in ideal locations for two rooms The examination room shows one room controller installed adjacent to the door In this area of the room occupant traffic is high and ensures the oc...

Page 14: ...ction could fall outside the specified detection zone while at the same time most occupant movement would not be lateral to the PIR thereby not respecting optimal crossing patterns for PIR detection N...

Page 15: ...otes Wiring should be daisy chained Respect polarity If using 2 conductor shielded wires connect the shield of each feed together on the back of the controller ONLY ground the shield at one location D...

Page 16: ...l Stand by cool 72 F 76 F 80 F Movement detected Stand by timer reset Into Stand by mode Unoccupied timer reset Stand by time Unoccupied time Into Unoccupied mode Next movement detected 70 F 62 F Unoc...

Page 17: ...llow for advanced functions such as central reservation and occupancy functions Up to 10 different ZigBee motion sensors can be used with a BrightStat room controller No tools are required for commiss...

Page 18: ...Manual 2100 680 Page 18 of 18 Hidden switch Hidden switch Hidden switch LED LED LED SED WMS SED CMS SED WDS...