Bard 8620-343 Supplemental Instructions Download Page 4

Manual 7960-918
Page 

4 of 9

Installation

Field-supplied tools needed:

• 

Appropriate personal protection equipment, 
including gloves and safety glasses

• 

Electrical meter to verify power status

• Drill

• 

Phillips head screwdriver

• 

5/16" nut driver

• 

7/8" drill bit (optional)

Installation Procedure

1.  Disconnect all power to HVACR unit. Use the meter 

to verify that power has been disconnected.

2.  Remove outer and inner control panel covers.

3.  Remove blower housing cover (large upper panel).

4.  Attach two (2) magnetic clips to the UV light 

assembly (see 

Dimensions

 drawing on page 2).

5.  Install UV light assembly onto the blower partition 

on the inside of the front flange as shown in 
Figure 1. UV light should be directed over blower 

FIGURE 1

Install UV Light Assembly and Route Wires

outlets, facing evaporator coil. (Models may have air 
deflector or control box mounted to blower partition; 
however, UV light can still be installed as shown.) 

6.  Route wires into control panel through bushing in 

blower partition or copper grommet or wire bushing, 
then into control panel as shown in Figure 1.

 

NOTE:

 Not all models will have bushing in blower 

partition. A 7/8" hole can be drilled and 
supplied bushing can be installed.

7. 

Kit 8620-343 (460V-3PH Units) Only:

 460V 

stepdown transformer can be installed in any of 
these four locations: In control panel assembly, on 
side flange of control panel, on blower partition or 
under blower partition (see Figure 2).

8.  Connect red wire from UV light assembly to 

“NO” contact on the relay assembly (see 

Field 

Installation Diagram

 on page 9).

9.  Determine unit supply voltage—located on the 

unit serial plate. Connect black wire from UV light 
assembly to:

 

(230V-1PH) − “L2” 

 

(230V-3PH) − “L3” 

 

(460V-3PH) − Black Wire-Transformer

 See 

Field Installation Diagram

 on page 9.

MIS-4328

CONTROL PANEL
BUSHING

(WITH MAGNETIC CLIPS)

UV LIGHT ASSEMBLY

ROUTE WIRES
THROUGH BUSHING

Summary of Contents for 8620-343

Page 1: ...ng locations that prevent exposure to vulnerable components If mounting locations are limited protect components with UV resistant material such as aluminum foil aluminum duct tape metallic shields et...

Page 2: ...sumption 15W Frequency 50 60Hz Dimensional Specs Unit Dimensions 15 1 8 L x 3 4 H x 1 D Weight 1 lb Performance Irradiance 170 W cm2 UL Listing and Certifications Compliance and Certifications UL 1598...

Page 3: ...rlock Safety Device 1 E 113 908 Bracket WH Q TEC Q H A4 Units 1 F 113 909 Bracket I TEC Units 1 G 113 913 Bracket Q TEC Units 1 H 7961 963 UV C Warning Label 1 I Per Model Supplemental Instructions Ma...

Page 4: ...tor or control box mounted to blower partition however UV light can still be installed as shown 6 Route wires into control panel through bushing in blower partition or copper grommet or wire bushing t...

Page 5: ...2 Kit 8620 343 460V Stepdown Transformer Installation Locations MIS 4336 TRANSFORMER COVER NOT REQUIRED IN UNIT CONTROL PANEL ON BOTTOM BLOWER PARTITION TRANSFORMER COVER REQUIRED ON TOP BLOWER PARTI...

Page 6: ...or light 13 Control panel assemblies vary due to available control options Find unused space on control panel and install relay and indicator light assemblies in control panel using self drilling scre...

Page 7: ...R SWITCH ASSEMBLY LOCATION WHEN NO DEFLECTOR IS USED DOOR SWITCH ASSEMBLY USE BRACKET 113 908 ROUTE WIRES BEHIND DEFLECTOR AND THROUGH BUSHINGS TO CONTROL PANEL SHOWN WITH DEFLECTOR INSTALLED 1 3 4 IN...

Page 8: ...stalled Label 7961 622 0375 to unit serial plate Serial plate is silver and located on the exterior of the unit cabinet or on a service panel with 5253 039 XXXX printed in the lower right corner 20 No...

Page 9: ...CK WHITE BLACK WHITE ORANGE RED BLACK RED ORANGE BLACK WHITE NO COM T2 T1 L2 DOOR PANEL SWITCH UNIT SUPPLY VOLTAGE 460 VOLT 3 PHASE 230 VOLT 3 PHASE UNIT SUPPLY VOLTAGE UNIT SUPPLY VOLTAGE 230 VOLT 1...

Reviews: