8. Primary pump unit
8.4
Installing the primary pump unit
Necessary tools
•
Flat screwdriver
•
Phillips screwdriver PH2
•
Nut spanner 5.5 mm
•
Nut spanner 8 mm
•
Cutting pliers (for cable ties)
•
Cable ties
•
glue
This procedure assumes that power has been switched off. Unless otherwise stated, power must be off prior
to start with this procedure. To switch off power, see procedure "Switching off power and locking the switch",
page 15.
How to install the primary pump unit?
1. Mount the primary pump unit:
a) Tilt the front side of the primary pump unit inwards the left side of the chiller and move to the front for 10 cm.
Image 8-14
Installing the primary pump unit — step 1 of 2
b) Move the primary pump unit towards the rear of the chiller until the two screws at the rear of the chiller are engaged in the
slots of the primary pump unit base.
Image 8-15
Installing the primary pump Unit — step 1 of 2
2. Install the two screws (reference 1 image 8-16) (front side of the chiller) using the nut spanner 8 mm.
R5906015 ULC-30A 01/02/2018
43
Summary of Contents for ULC-30A
Page 1: ...ULC 30A Service manual R5906015 01 01 02 2018...
Page 4: ......
Page 6: ...Table of contents Index 97 2 R5906015 ULC 30A 01 02 2018...
Page 10: ...1 Safety 6 R5906015 ULC 30A 01 02 2018...
Page 24: ...5 Covers 20 R5906015 ULC 30A 01 02 2018...
Page 28: ...6 Fan unit 24 R5906015 ULC 30A 01 02 2018...
Page 40: ...7 Coolant procedures 36 R5906015 ULC 30A 01 02 2018...
Page 70: ...10 Refrigeration unit 66 R5906015 ULC 30A 01 02 2018...
Page 92: ...11 Electronics Unit 88 R5906015 ULC 30A 01 02 2018...