INSTALLATION-
FREESTANDINGMODELONLY
Location
Select a location for your wood heater with
greatcare.
*
Donotplaceyourheaterinareasofhigh
traffic,nearfurnitureordraperies.
*
Check that the intended location will not
interferewithceilingjoists,rafters,valleys
andridges.
HearthRequirements
Ifyourwoodheateristobeinstalledoncarpet,
timberoranyothercombustiblematerial,you
must place a hearth (also known as a floor
protector) underneath the heater. Please
observethefollowing:
*
Thehearthmustconsistofatleast7.5mm
thickcompressedfibrecementsheetwitha
thermalconductivitynotgreaterthan0.33
W/m°K
*
Thetopsurfaceofthehearthmustbeno
lessthan40mmabovethefloor.
*
Thehearthmustbenolessthan1150mm
wide
*
Itisnotrecommendedthatyoumakeyour
ownhearth
*
Thehearthandheaterassemblymustbe
placedonafirmandlevelsurface.
HearthClearances
It is necessary to ensure that the heater is
positionedonthehearthsothatthefollowing
requirementsareobserved:
*
Thefrontofthehearthshouldextendpast
thefrontoftheheaterby400mm.
*
Thesideofthehearthshouldextendpast
thefireboxopeningbyminimum200mmon
eachside.
HeaterClearances
Itisvitalthattheheaterbeinstalledtheproper
distancefromcombustiblesurfaceslikewood,
gyprock and curtains. These minimum
distances,whichyouneedtoobserveforyour
particular heater are stated below. The
diagrams show both parallel and corner
installations.
Pleasenotetheheaterclearancesaretothe
upperbodyoftheheaterandnottothebench.
Failuretomaintaintheseminimumdistances
mayresultinafireforwhichyourinsurermay
refusetocover.
ReducedClearances
Theseclearancescanbereducedwithproper
heat shielding. Basically a noncombustible
surfaceisplacedbetweentheheaterandthe
combustible wall. It is vital that an
unobstructedairflowbemaintainedbetween
thetwosurfacestoremoveexcessheat.
A
B
ParallelInstallation
CornerInstallation
HearthClearances
C
D
E
Clearances
Aura
withMaxiheatIronbarkfluekit(MXFKT3K),includesdoubleshield(1
inner+1outer)
withMaxiheatDecromeshDefaultfluekitwithinner(MXRSISS)
betweenactiveanddecromeshandouter(MXRSOB)shieldonrear
E
D
C
B
A
Alldimensionsareinmillimetres
2 0
0
10
350
200
200
10
375
175
400