background image

Setting the pressure points for operating mode: Pressure filling - Type Regulating mode  

(further operating modes you find in the operating manual.)

 

 

The drive box PCS is delivered in the selected mode Pressure filling - Type R with the set 
values:  
 

 

P1 = 6,5 bar 

 

 

Pe_1

 

 

H1 = 2,5 bar 

 

 

Pe_1

U

 = 4 bar 

 

The pressure points P2 is not needed for this mode. However, the following values must be 
entered: 

 

 

P2 = 1,0 bar

 

 

Pe_2

 

H2 = 0,5 bar

 

 

Pe_2

U

 = 0,5 bar 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

         

 

 

 

 

 

 

 

 

           Counter nut

 

 

 

 

 

 

 

 

 

 

Pressure regulator

  

 

 

Adjusting the control pressure for the actuator

 

The air supply being connected, the control pressure can be adjusted on the pressure regulator 
For this purpose, loosen the lock nut and adjust with an Allen key the pressure regulator.  
The control pressure can be read on the pressure gauge.  
 
The opening speed of the actuator can be set to the supply air throttle (4), while the closing speed 
 can be adjusted on the externally mounted discharge air throttle (5).

 

 

 

 

 

 

 

 

 

 

Compressed air connection 

 
 

  

 

 

 

 

 

 

 

Pressure gauge for  the control pressure  

Adjustment of switch points for PCS-E-… 

1. Open the cover of the PCS-E. 
2. Press with the thumb on the position indicator (a) and pull the plastic disc (b) upwards. The trip cam turn automatically to the initial position. 
    The device is now ready for automatic self-adjustment.  
3. Switch the rotary actuator in each direction 1x each. 
4. The switch points are now adjusted.  
5. Check if the position indicator matches the valve position. If not, remove the position indicator (a) carefully upwards and put it in the correct position back 

into the seating. 

6. Check electrically if the signals are present in the end positions of the actuator at the terminals. If not, repeat steps 1-5 and check all electrical connections. 
7. Close the cover, check the correct position of the cover gasket and tighten the screws for securing the cover.

 

 

 

 

 

 

 

 

bar pneumatische Steuerungssysteme GmbH 
Auf der Hohl 1 
53547 Dattenberg  
 
Contact 

 

+49 2644 9607-0 

 

+49 2644 9607-35 

 

[email protected]

 

 

www.bar-gmbh.de

 

 

Subject to further development and change of data. © by bar GmbH – 02/2016

 

 

Attention: 

After each change of the end positions and after modifications to the actuator, steps 1 - 9 must always be performed. 

 

Note

 

This leaflet does not replace the valid operating manual! 

Reviews: