background image

17616_ins_wireless_temp_hum_xmtr

Installation and Operating Instructions

Wireless Room Temperature and Humidity Transmitter

(

Units without Temperature Setpoint or Override) 

Building Automation Products, Inc., 750 North Royal Avenue, Gays Mills, WI  54631 USA

Tel:+1-608-735-4800 • Fax+1-608-735-4804 • E-mail:[email protected] • Web:www.bapihvac.com

Specifications subject to change without notice.

rev. 06/27/14

5 of 5

Wireless System Diagnostics

Possible Solutions:

-  Check for proper wiring and connections from the output modules to the controller.
-  Check to see if the controller’s software is configured properly.
- Check for proper power to the receiver, repeater (if used) and output modules.
- Retrain the Analog Output Module.
- Check that the associated transmitter is transmitting (the LED will flash about once 

every 10 seconds when it transmits). If not, replace the batteries. Check that the 

associated receiver is receiving the tranmissions (its LED will blink right after the 

transmitter LED if it receives that transmission.) If it is not receiving the transmissions, 

move it closer to the transmitter or reposition the antenna for maximum reception. 

Note:

 The receiver will receive transmissions from all transmitters that are within 

range, not just the one you are testing.

- Retrain the Analog Output Module.

-  Check for proper wiring and connections from the output modules to the controller.
-  Check to see if the controller’s software is configured properly.
- Check to see if the correct output module is connected to the correct controller.

Analog Output Module Default Status when Wireless Transmission is Interrupted:

If an output module does not receive data from its assigned transmitter for 15 minutes, the red LED on the top of the module will 

blink rapidly.  If this happens, the individual Analog Output Modules will react as follows:

• Resistance Output Modules (BA/ROM) calibrated for temperature will output the highest resistance in their output range.

• Voltage Output Modules (BA/VOM) calibrated for temperature will set their output to 0 volts. 

• Current Output Modules (BA/COM) calibrated for temperature will set their output to 4 mA.

• Voltage Output Modules (BA/VOM) calibrated for humidity will set their output to their highest voltage (5 or 10 volts).

• Current Output Modules (BA/COM) calibrated for humidity will set their output to 20 mA.

• Setpoint Output Modules (BA/SOM) will hold their last value indefinitely.

• Relay Output Modules (BA/RYOM Units Only) will go to their default state (example: open for a normally open unit).

When a transmission is received, the output modules will revert to normal operation in 60 seconds or less.

Possible Problems:

Temperature or Humidity is reading 

its low limit or high limit, or the LED 

at the top of the Analog Output Mod-

ule is blinking rapidly:

Temperature or Humidity reading is 

coming out the wrong output module

Temperature or Humidity reading is 

incorrect 

Extending the RS485 Network between the Receiver and the Analog Output Modules

The Analog Output Modules may be mounted up to 4,000 feet away from the receiver. The total length of all the shielded, twisted 

pair (TSP) cables shown in Fig 13 is 4,000 feet (1,220 meters).  Connect the terminals together as shown in Fig 13.  If the dis-

tance from the receiver to the group of Analog Output Modules is greater than 100 feet (30 meters), provide a separate power 

supply for that group of 

Output Modules.  BAPI’s 

VC350A-EZ Voltage 

Conv. and a small 

transformer are a perfect 

solution.

Fig. 13: 

Extended RS485 Network between the Receiver and the Analog Output Modules

 BAPI 

VC350A 

EZ Voltage 

Converter

Transformer

Receiver

RS485 TSP Wiring

RS485 TSP Wiring

Analog Output Modules

Analog Output Modules

  BAPI 

VC350A 

EZ Voltage 

Converter

Transformer

  BAPI 

VC350A 

EZ Voltage 

Converter

Transformer

Note:

 This configuration 

requires one or more 

Pluggable Terminal 

Block Kits for the extra 

wire terminations on the 

left and right side of the 

Output Modules. Each kit 

includes 4 connectors.

Pluggable Terminal Block 

Kit (BA/AOM-CONN) 

Reviews: