background image

Installation and Operating Instructions

Delta Style Room Humidity Transmitter with Optional Temp. Sensor 

BA/#-Hxxx-R

Building Automation Products, Inc., 750 North Royal Avenue, Gays Mills, WI  54631 USA

Tel:+1-608-735-4800 • Fax+1-608-735-4804 • E-mail:[email protected] • Web:www.bapihvac.com

27417_ins_Delta_RH

2 of 4

rev. 04/15/14

BAPI recommends using twisted pair of at least 22AWG and sealant filled connectors for all wire connections. Larger gauge wire 

may be required for long runs. All wiring must comply with the National Electric Code (NEC) and local codes. Do NOT run this 

device’s wiring in the same conduit as AC power wiring. 
BAPI’s tests show that fluctuating and inaccurate signal levels are possible when AC power wiring is present in the same conduit 

as the signal lines.  BAPI does not recommend wiring the sensor with power applied as accidental arcing may damage the 

product and will void the warranty.

Fig. 4: 

Circuit Board (shown with 

optional temperature sensor)

4 to 20mA Humidity Output Termination

TERMINAL LEGEND 

FUNCTION

GND .................................... 4 to 20mA Loop Humidity Signal (To analog input of controller) 
V+ ....................................... Main DC Power (See power requirements in specifications)
V OUT ................................. Not Used (No termination)
TEMP +............................... Optional Passive Temp. Sensor (No polarity for RTDs or Thermistors)

 

   (“+” terminal is the 5 to 30 VDC bias voltage for Semiconductors)

TEMP - ............................... Optional Passive Temp. Sensor (No polarity for RTDs or Thermistors)

 

   (“-” terminal is the temperature signal for Semiconductors)

0 to 5VDC or 0 to 10VDC Humidity Output Termination

TERMINAL LEGEND 

FUNCTION

GND .................................... Ground for Power and Reference for the Humidity Voltage signal 
V+ ....................................... Main Power (See power requirements in specifications)
V OUT ................................. Humidity Voltage Signal Output (0 to 5VDC or 0 to 10 VDC)
TEMP +............................... Optional Passive Temp. Sensor (No polarity for RTDs or Thermistors)

 

   (“+” terminal is the 5 to 30 VDC bias voltage for Semiconductors)

TEMP - ............................... Optional Passive Temp. Sensor (No polarity for RTDs or Thermistors)

 

   (“-” terminal is the temperature signal for Semiconductors)

Notes:

  1.  Transmitter is common ground (CG) for voltage outputs

 

2.  “TEMP +” and “TEMP -” terminals are isolated to only the temperature sensor.

Termination

Optional Communication Jack Wiring

C35 Comm. 

Jack on 

Delta Style 

Unit Base 

(Front View)

Fig. 5:

 C35 Comm Jack 

(3.5mm plug shown for clarity)

C35 Comm. 

Jack on 

Delta Style 

Unit Base 

(Back View)

Norm: The sensor will operate normally

High: Sets the sensor value to the HIGH 

temperature (see table at right)

Low: Sets the sensor value to the LOW 

temperature (see table at right)

  Sensor Type 

Low Temp (40° F) 

High Temp (105° F)

 

 

Resistance Value 

Resistance Value

 

1000Ω RTD 

1.02KΩ (41.2°F) 

1.15KΩ (101.5°F)

 3000Ω Thermistor 

7.87KΩ (39.5°F) 

1.5KΩ (106.8°F)

  10K-2 Thermistor 

30.1KΩ (39.2°F) 

4.75KΩ (105.8°F)

  10K-3 Thermistor 

26.7KΩ (35.9°F) 

5.11KΩ (108.4°F)

 10K-3(11K) Thermistor 

7.32KΩ (43.7°F) 

3.65KΩ (105.2°F)

Optional Test and Balance Switch (SW1) Operation

T&B Switch (SW1) Position and Sensor Output

BAPI does not recommend wiring the sensor with power applied as accidental arcing may damage the product 

and will void the warranty.