background image

Installation & Operating Instructions

Temperature Sensor Transmitters

 

 

 

 

BA/(T100, T1K, T10K) Temperature Transmitters

Building Automation Products, Inc., 750 North Royal Avenue, Gays Mills, WI  54631 USA

Tel:+1-608-735-4800 • Fax+1-608-735-4804 • E-mail:[email protected] • Web:www.bapihvac.com

Specifications subject to change without notice.

rev. 04/18/13

22199_ins_T1K_T100_XMTR

3 of 4

BAPI recommends using twisted pair of at least 22AWG and sealant filled connectors for all wire connections. Larger gauge wire may 

be required for long runs. All wiring must comply with the National Electric Code (NEC) and local codes. Do NOT run this device’s 

wiring in the same conduit as high or low voltage AC power wiring. BAPI’s tests show that inaccurate signal levels are possible when 

AC power wiring is present in the same conduit as the sensor wires.

6

Wiring & Termination

Fig. 16: 

Typical RTD 4 to 20 mA Transmitter with Flying Leads

Fig. 18: 

Typical Thermistor 4 to 20mA Transmitter

Fig. 17:

 Typical RTD 4 to 20mA Transmitter with Terminals

Fig. 19:

 Typical Thermistor Voltage Transmitter

Diagnostics

Voltage Temperature Equation

 

T = T

Low

 + (V x T

Span

)

 

     V

Span

= Temperature at sensor

T

Low 

= Low temperature of span 

T

High

 

 

= High temperature of span

T

Span 

= T

High

 - T

Low

V

Low

 

= Low transmitter voltage

 

   usually=(0, 1 or 2v)

V

High 

= High transmitter voltage

 

   usually=(5 or 10v)

V

Span

  = V

High

 - V

Low

= Signal reading in volts

4-20mA Temperature Equation

 

T = T

Low

 + (A -4) x (T

Span

)

 

16

= Temperature at sensor

T

Low 

= Low temperature of span 

T

High

 

 

= High temperature of span

T

Span 

= T

High

 - T

Low

  = Signal reading in mA

Possible Problems: 

Possible Solutions:

• Unit will not operate. 

- Measure the power supply voltage by placing a voltmeter across the transmitter’s (+) and 

(-) terminal. Make sure that it matches the drawings above and power requirements in the 

specifications.

 

- Check if the RTD wires are physically open or shorted together and are terminated to the 

transmitter.

 

- Measure the physical temperature at the temperature sensor’s   location using an accurate 

temperature standard. Disconnect the temperature sensor wires and measure the 

temperature sensor’s resistance with an ohmmeter. Compare the temperature sensor’s 

resistance to the appropriate temperature sensor table on the BAPI web site.

• The reading is incorrect in the controller.

 

- Determine if the input is set up correctly in the controllers and BAS software.

 

- For a 4-20mA current transmitter measure the transmitter current by placing an ammeter 

in series  with the controller input. The current should read according to the “4-20mA 

Temperature Equation” shown below.

 

- For a voltage transmitter, measure the signal with a volt meter (Orange or Orange/Black to 

Black). The signal should read according to the “Voltage Temperature Equation” shown below.

Reviews: