AD592/592-10K Room Sensors
9557_ins_592_Room
Sensor Termination and Troubleshooting
Building Automation Products, Inc., 750 North Royal Avenue, Gays Mills, WI 54631 USA
Tel:+1-608-735-4800 • Fax+1-608-735-4804 • E-mail:[email protected] • Web:www.bapihvac.com
Specifications subject to change without notice.
rev.
3/14/05
Troubleshooting
Problems:
Temperature sensor in front end software is
reading high
Temperature sensor in front end software is
reading low
Possible Solutions:
-
Confirm the input is set up correctly in the front
end software
-
Check wiring for proper termination
-
Verify the “Sensor” output is correct from Pin 2 to
Pin 3. Refer to table below for proper reading
-
Determine if the semiconductor appears physi-
cally shorted
-
Check wiring for proper termination
-
Verify the “Sensor” output is correct from Pin 2 to
Pin 3. Refer to table below for proper reading