9557_ins_592_Room

AD592/592-10K Room Sensors

Sensor Termination and Troubleshooting

Building Automation Products, Inc., 750 North Royal Avenue, Gays Mills, WI  54631 USA

Tel:+1-608-735-4800 • Fax+1-608-735-4804 • E-mail:[email protected] • Web:www.bapihvac.com

Specifications subject to change without notice.

3/14/05

rev.

Termination

Therm Reading_______

The actual temperature reading
according to a thermometer that is
certified traceable to recognized
standards by the National Institute of
Standards and Technology (NIST).

Sensor Reading ______

The temperature reading according to
the AD592 sensor, using the output
in either mA or mV and converting
the output to a Fahrenheit tempera-
ture.

Offset_______

The difference between the
Thermometer Reading and the
Sensor Reading

To correct the Sensor Reading, simply add the offset value to the sensor reading so that it equals the thermometer
reading.

e.g.

Therm Reading  74.6

Sensor Reading  73.0

Offset  +1.6

Correction:  Add (+1.6) °F to the sensor for an accurate reading:  73 + 1.6 = 74.6°F

e.g.

Therm Reading  75.4

Sensor Reading  77.2

Offset  -1.8

Correction:  Add (-1.6) °F to the sensor for an accurate reading:  77.2 + (-1.8) = 75.4°F

All BA592 sensors will have the following information provided on a label:

BA/592-10K (3 Wire) sensors

1. All BA/592-10K (3 wire) sensors have a 10K

0.1% resistor built in.

2. Connect the Ground (terminal 3) wire first.

3. Connect the Sensor Output wire second.

4. Connect the 5 to 30 VDC wire last.

BA/592 (2 Wire) sensors

1. Install a 10K 0.1% resistor between the sensor

Output (terminal 2) and Ground (GND).

 2. Make sure that the resistor is connected

between the analog input (A.I.) point and
Ground.

 3.  Connect the sensor Output to the A.I. point.

4.  Connect the 5 to 30 VDC wire last.

Offsetting

R2

R1

SENS

1
2
3

+5 to +30 VDC

[To Power of Controller or Supply]

Sensor output (1mV/°K)

[To Analog Input of Controller]

GND(Common)

[To GND(Common) of Controller]

+5 to +30 VDC

[To Power of Controller or Supply]

Sensor output (1mV/°K)

[To Analog Input of Controller]

 10K 0.1%

GND(Common)

[To GND(Common) of Controller]

R2

R1

SENS

1
2
3

BAPI recommends using twisted pair of at least 22AWG and sealant filled connectors for all wire connections. Larger

gauge wire may be required for long runs. All wiring must comply with the National Electric Code (NEC) and local codes.
Do NOT run this device’s wiring in the same conduit as AC power wiring of NEC class1 or NEC class 2, NEC class 3 or with
wiring used to supply highly inductive loads such as motors, contactors and relays.

BAPI’s tests show that fluctuating and inaccurate signal levels are possible when AC power wiring is present in the

same conduit as the signal lines.  If you are experiencing any of these difficulties, please contact your BAPI representative.

BAPI does not recommend wiring the sensor with
power applied as accidental arcing may damage
the product and will void the warranty