3. Apply power to all devices.
4. Form the wireless network by binding the Nodes to the Gateway. If the binding instructions are not included in the datasheet, refer to

the product manual for binding instructions.

5. Observe the LED behavior to verify the devices are communicating with each other.
6. Conduct a site survey between the Gateway and Nodes. If the site survey instructions are not included in this datasheet, refer to the

product manual for detailed site survey instructions.

7. Install your wireless sensor network components. If installation instructions are not included in this datasheet, refer to the product

manual for detailed installation instructions.

For additional information, including installation and setup, weatherproofing, device menu maps, troubleshooting, and a list of accesso-
ries, refer to one of the following product manuals.

• SureCross Wireless I/O Network Manual: 

132607

• Web Configurator Manual (used with "Pro" and DX83 models): 

134421

• Host Configuration Manual 

132114

Configuring the DIP Switches

Before making any changes to the DIP switch positions, disconnect the power. DIP switch changes will not be recognized if power isn't
cycled to the device.

Accessing the Internal DIP Switches

To access the internal DIP switches, follow these steps:

1. Unscrew the four screws that mount the cover to the bottom housing.
2. Remove the cover from the housing without damaging the ribbon cable or the pins the cable plugs into.
3. Gently unplug the ribbon cable from the board mounted into the bottom housing.
4. Remove the black cover plate from the bottom of the device's cover.

The DIP switches are located behind the rotary dials.

After making the necessary changes to the DIP switches, place the black cover plate back into position and
gently push into place. Plug the ribbon cable in after verifying that the blocked hole lines up with the missing
pin. Mount the cover back onto the housing.

DIP Switch Settings (RTD)

Switches

Device Settings

1

2

3

4

5

6

7

8

Rotary dial address mode

OFF*

Extended address mode

ON

Modbus or UCT configured (overrides DIP switches)

OFF*

DIP switch configured

ON

Temp °Fahrenheit

OFF*

Temp °Celsius

ON

High resolution (0.1 degree) **

OFF*

Low resolution (1 degree)

ON

Platinum, 100 ohm (European, DIN 43760)

OFF*

OFF*

OFF*

Copper, 10 ohm (alpha = 0.00427)

OFF

ON

OFF

* Default configuration
** In high resolution mode, the temperature = (Modbus register value) ÷ 20. In low resolution mode, the temperature is (Modbus register
value) ÷ 2.

 

 

SureCross DX99 FlexPower RTD Node (Polycarbonate Housing)

2

www.bannerengineering.com - tel: 763-544-3164

P/N 142499 Rev. E

Summary of Contents for SureCross DX99 FlexPower DX99N9X2S0N0R4X0A0

Page 1: ...ineer ing com surecross Model Frequency I O DX99N9X2S0N0R4X0A0 900 MHz ISM Band Inputs Four 3 wire RTD DX99N2X2S0N0R4X0A0 2 4 GHz ISM Band Internal antenna models are also available For more informati...

Page 2: ...sing the Internal DIP Switches To access the internal DIP switches follow these steps 1 Unscrew the four screws that mount the cover to the bottom housing 2 Remove the cover from the housing without d...

Page 3: ...ge C Pt100 DIN 0 00385 328 to 900 F 200 to 482 C Cu 10 Ohm alpha 0 00427 328 to 500 F 200 to 260 C For the copper RTD the best accuracy is when measuring between 50 to 150 C 58 to 302 F Below this ran...

Page 4: ...TD 3 F C 1638 3 1638 4 32768 32767 A3 A3 DI1 6 6 6 Node 16 RTD 4 F C 1638 3 1638 4 32768 32767 A4 A4 DI2 7 7 7 Node 16 Reserved 8 8 8 Node 16 Device Message 15 15 15 Node 16 Control Message 16 16 16 N...

Page 5: ...ate 16 seconds Accuracy 0 1 of full scale Resolution 0 1 C 15 bit Refer to the SureCross DX80 Wireless I O Network Product Man ual p n 132607 for installation and waterproofing instructions Op erating...

Page 6: ...point ground system to ensure no ground loops are created No surge suppressor can absorb all lightning strikes do not touch the SureCross device or any equipment connected to the SureCross device duri...

Page 7: ...ICULAR PURPOSE AND WHETHER ARISING UNDER COURSE OF PERFORMANCE COURSE OF DEALING OR TRADE USAGE This Warranty is exclusive and limited to repair or at the discretion of Banner Engineering Corp replace...

Reviews: