SureCross Performance Node
6
www.bannerengineering.co.kr
P/N 158215-KR
Rev. C
Terminal Blocks and Wiring (12 Sourcing I/O Models)
IP67 Wiring Board (-P8 Models)
IP20 Wiring Board (-P8C Models)
PWR
GND
IO7
IO8
IO9
PWR
GND
IO6
IO5
IO4
IO1
IO2
IO3
IO4
IO5
IO6
IO12
IO11
IO10
IO9
IO8
IO7
IO10 IO3
IO11 IO2
IO12 IO1
V+ Tx/+
V- Rx/-
V- V+
IOx. Input or output (depending on configuration)
GND. Ground/dc common connection.
PWR. Power, 10 to 30V dc power connection.
RX/-. Serial comms line for Gateways and DX85s only. No con-
nection for Nodes.
TX/+. Serial comms line for Gateways and DX85s only. No con-
nection for Nodes
V+. Power, 10 to 30V dc power connection.
V-. Ground/dc common connection.
When using the DIP switches to configure the input and output selection, wire the inputs beginning with IO1. After all inputs are wired,
begin using the remaining IOx as outputs. For example, if you are using 10 inputs and 2 outputs, use terminals IO1 through 10 for the
inputs and terminals IO 11 and 12 for the outputs.
For the default configuration of 6 IN and 6 OUT, use IO 1 through 6 to wire the inputs and IO 7 through 12 to wire the outputs.
Discrete Input Wiring for PNP Sensors Discrete Output Wiring (PNP)
10-30V dc
PWR
DIx
PWR
DOx
GND
Load
10-30V dc
dc common
The DIx and DOx of these wiring diagrams
correspond to the IOx on the terminal
block.
DX80...C Wiring
Wiring power to the DX80...C models varies depending the power requirements of the model. Connecting dc power to the communication
pins (Tx/Rx) causes permanent damage. For FlexPower devices, do not apply more than 5.5V to the B+ terminal.
Terminal Label Gateway, DX85
10 to 30V dc Powered Nodes
Battery Powered Nodes
V+
10 to 30V dc
10 to 30V dc
Tx/+
RS485 / D1 / B / +
V-
dc common (GND)
dc common (GND)
dc common (GND)
Rx/-
RS485 / D0 / A / -
B+
3.6 to 5.5V dc
LED Behavior for the Nodes
After powering up and binding the Gateway and its Nodes, verify all devices are communicating properly. A Node will not sample its
inputs until it is communicating with its Gateway. When testing communication between the Gateway and Node, all radios and antennas
should be at least two meters apart or the communications may fail.