RS-485 Communication Specifications
Communication Hardware (MultiHop RS-485)
Interface: 2-wire half-duplex RS-485
Baud rates: 9.6k, 19.2k (default), or 38.4k via DIP switches; 1200 and 2400 via the MultiHop Configuration Software
Data format: 8 data bits, no parity, 1 stop bit
Environmental Specifications
Operating Conditions
–40 °C to +85 °C (–40 °F to +185 °F) (Electronics); –20 °C to +80 °C (–4 °F to +176 °F)
(LCD)
95% maximum relative humidity (non-condensing)
Radiated Immunity: 10 V/m (EN 61000-4-3)
Shock and Vibration
IEC 68-2-6 and IEC 68-2-27
Shock: 30g, 11 millisecond half sine wave, 18 shocks
Vibration: 0.5 mm p-p, 10 to 60 Hz
Environmental Ratings
IEC IP67; NEMA 6
Refer to the Sure Cross
®
MultiHop Product Instruction Manual (p/n
installation and waterproofing instructions.
Operating the devices at the maximum operating conditions for extended
periods can shorten the life of the device.
Included with Device
• BWA-HW-001: Mounting Hardware Kit, containing four M5-0.8 x 25mm SS screws, four M5-0.8 x 16mm SS screws, four M5-0.8mm SS hex
nuts, and four #8-32 x 3/4" SS bolts
• BWA-9O2-C (900 MHz) or BWA-2O2-C (2.4 GHz): Antenna, 2 dBd Omni, Rubber Swivel RP-SMA Male. (Not included with Internal antenna
models)
• Quick Start Guide (128185 for DX80 Gateways or 152653 for MultiHop models)
Accessories
Sensors with a Serial Interface
The following sensors are designed to be used with any of the 1-Wire Serial Interface Nodes.
K50UX1RA U-GAGE Ultrasonic Sensor
•
1-wire serial interface
•
M12FTH4Q Temperature and Humidity Sensor
•
±2% Accuracy, 1-wire serial interface
•
(Requires a 5-pin threaded M12/Euro-style double-ended
cordset less than 3 meters long, such as model
DEE2R-5
xD.)
•
Datasheet:
M12FT4Q Temperature Sensor
•
1-wire serial interface
•
(Requires a 5-pin threaded M12/Euro-style double-ended
cordset less than 3 meters long, such as model
DEE2R-5
xD.)
•
Datasheet:
QM30VT1 Vibration and Temperature Sensor
•
Aluminum housing
•
2.09 m (6.85 ft) cable with a 5-pin M12/Euro-
style male quick disconnect (QD)
•
QM30VT1-QP Vibration and Temperature Sensor
•
Aluminum housing
•
150 mm (6 in) cable with a 5-pin M12/Euro-Style
male quick disconnect (QD)
•
QM30VT1-SS Vibration and Temperature Sensor
•
Stainless steel housing
•
2.09 m (6.85 ft) cable with a 5-pin M12/Euro-
style male quick disconnect (QD)
•
QS30WEQ WORLD-BEAM Photoelectric Emitter, QS30
•
Max Range: 100 feet, 10x excess gain at 50 feet, 1-
wire serial interface
•
Datasheet:
QS30WRQ WORLD-BEAM Photoelectric Receiver, QS30
•
Max Range: 100 feet, 10x excess gain at 50 feet, 1-
wire serial interface
•
Datasheet:
Warnings
Install and properly ground a qualified surge suppressor when installing a remote antenna system. Remote antenna configurations installed without surge suppressors invalidate the manufacturer's warranty. Keep
the ground wire as short as possible and make all ground connections to a single-point ground system to ensure no ground loops are created. No surge suppressor can absorb all lightning strikes; do not touch
the Sure Cross
®
device or any equipment connected to the Sure Cross device during a thunderstorm.
Exporting Sure Cross
®
Radios. It is our intent to fully comply with all national and regional regulations regarding radio frequency emissions. Customers who want to re-export this product to a country other than
that to which it was sold must ensure the device is approved in the destination country. The Sure Cross wireless products were certified for use in these countries using the antenna that ships with the product.
When using other antennas, verify you are not exceeding the transmit power levels allowed by local governing agencies. This device has been designed to operate with the antennas listed on Banner
Engineering’s website and having a maximum gain of 9 dBm. Antennas not included in this list or having a gain greater that 9 dBm are strictly prohibited for use with this device. The required antenna impedance
is 50 ohms. To reduce potential radio interference to other users, the antenna type and its gain should be so chosen such that the equivalent isotropically radiated power (EIRP) is not more than that permitted for
successful communication. Consult with Banner Engineering Corp. if the destination country is not on this list.
Sure Cross
®
MultiHop H6 Data Radio
6
www.bannerengineering.com - Tel: + 1 888 373 6767
P/N 152725 Rev. J