background image

Discrete Inputs

Rating: 3 mA max current at 30 V dc

Sample Rate: 40 milliseconds

ON Condition (NPN): Less than 0.7 V

OFF Condition (NPN): Greater than 2 V or open

Thermocouple Inputs (MultiHop)

Sample Rate: 8 seconds

Accuracy: 0.1% of full scale r 0.8 °C

0.1 °C, 24-bit A/D converter

Thermistor Input (MultiHop)

Model: Omega’s 44006 or 44031 family of 10 kOhm thermistors

Sample Rate: 1 second

Accuracy: 0.4 °C (10 °C to 50 °C); Up to 0.8 °C (−40 °C to 85 °C)

Thermocouple Notes

Each thermocouple input must be isolated from ground and shielded for proper

operation.

Discrete Outputs

ON Condition: Less than 0.7 V

OFF Condition: Open

Discrete Output Rating (MultiHop NMOS)

Less than 1 A max current at 30 V dc

ON-State Saturation: Less than 0.7 V at 20 mA

Certifications

Environmental Specifications for the E Housing

Operating Conditions

–40 °C to +85 °C (–40 °F to +185 °F) (Electronics); –20 °C to +80 °C (–4 °F to +176 °F)

(LCD)

95% maximum relative humidity (non-condensing)

Radiated Immunity: 10 V/m (EN 61000-4-3)

Shock and Vibration

IEC 68-2-6 and IEC 68-2-27

Shock: 30g, 11 millisecond half sine wave, 18 shocks

Vibration: 0.5 mm p-p, 10 to 60 Hz

Environmental Ratings

IEC IP65

Refer to the Sure Cross

®

 MultiHop Product Instruction Manual (p/n 

151317

) for

installation and waterproofing instructions.

Operating the devices at the maximum operating conditions for extended

periods can shorten the life of the device.

Accessories

Thermistor Probes

BWA-THERMISTOR-PROBE-001

Temperature sensor with thermistor PS103G2

Beta Value(K) 0 ~50°C: 3575

Base thermistor accuracy of 0.2%

Operating Temperature Range: –20 °C to +105 °C

Maximum Power Rating: 30 mW at 25 °C; derated to 1 mW at 125 °C

Dissipation Constant: 1 mW/°C

Plated nickel finish; PVC insulation

( 3.2 )

35 mm

6 mm

( 4)

20  mm

72 mm

Tube

Included with the DX80..E Models

• Mounting hardware kit
• BWA-HW-003: PTFE tape
• BWA-9O2-C (900 MHz) or BWA-2O2-C (2.4 GHz): Antenna, 2 dBd Omni, Rubber Swivel RP-SMA Male. (Not included with Internal antenna

models)

• BWA-BATT-001: Replacement battery, 3.6 Volt, "D" Lithium Cell
• BWA-HW-032: Access Hardware for "E" Housing (One each of 1/2-inch plug, 1/2-inch gland)
• Product datasheet and product family Quick Start Guide (

128185

 for DX80 Gateways or 

152653

 for MultiHop models)

Warnings

Install and properly ground a qualified surge suppressor when installing a remote antenna system. Remote antenna configurations installed without surge suppressors invalidate the manufacturer's warranty. Keep

the ground wire as short as possible and make all ground connections to a single-point ground system to ensure no ground loops are created. No surge suppressor can absorb all lightning strikes; do not touch

the Sure Cross

®

 device or any equipment connected to the Sure Cross device during a thunderstorm.

Exporting Sure Cross

®

 Radios. It is our intent to fully comply with all national and regional regulations regarding radio frequency emissions. Customers who want to re-export this product to a country other than

that to which it was sold must ensure the device is approved in the destination country. A list of approved countries appears in the 

Radio Certifications

 section of the product manual. The Sure Cross wireless

products were certified for use in these countries using the antenna that ships with the product. When using other antennas, verify you are not exceeding the transmit power levels allowed by local governing

agencies. Consult with Banner Engineering Corp. if the destination country is not on this list.

Sure Cross

®

 MultiHop H3E-NB-KR Data Radio

 

 

P/N 209529 Rev. A

www.bannerengineering.com - Tel: + 1 888 373 6767

7

Summary of Contents for Sure Cross MultiHop H3E-NB-KR

Page 1: ...ergized off output condition Important Electrostatic discharge ESD sensitive device ESD can damage the device Damage from inappropriate handling is not covered by warranty Use proper handling procedures to prevent ESD damage Proper handling procedures include leaving devices in their anti static packaging until ready for use wearing anti static wrist straps and assembling units on a grounded stati...

Page 2: ...and enable the receiver slots select for switches 1 2 ON ON Transmit power 900 MHz radios 1 00 Watt 30 dBm 2 4 GHz radios 0 065 Watts 18 dBm and 60 ms frame OFF Transmit power 900 MHz radios 0 25 Watts 24 dBm 2 4 GHz radios 0 065 Watts 18 dBm and 40 ms frame ON Application mode Modbus OFF Application mode Transparent ON MultiHop radio setting Repeater OFF OFF MultiHop radio setting Master OFF ON M...

Page 3: ...nected to the BAT terminal When powering the device from the integrated battery the BAT connection must remain open Integrated battery RS 485 for P1E M H1E M H12E and P16E Models Integrated battery RS 232 for P3E P4E M H3E and M H4E Models 1 2 3 4 BAT 1 10 V dc to 30 V dc optional 10 V dc to 30 V dc optional 2 RS 485 D1 B RS 232 Tx 3 dc common GND dc common GND 4 RS 485 D0 A RS 232 Rx Terminal Blo...

Page 4: ...an RS 485 to USB adapter cable with a wall plug that can power your 1 Watt MultiHop radio while you configure it The adapter cable is not required when connecting to a DXM Controller Download the most recent software revision from the Wireless Reference Library on Banner Engineering s website www bannerengineering com Installing Your Sure Cross Radios Please refer to one of the following instructi...

Page 5: ...t configuration is set to a Type B thermocouple 0 Value Thermocouple Type Value Thermocouple Type Value Thermocouple Type 0 B 5 J 10 P 1 C 6 K 11 R 2 D 7 L 12 S 3 E 8 M 13 T 4 G 9 N 14 U Modbus Addressing Convention All Modbus addresses refer to Modbus holding registers When writing your own Modbus scripts use the appropriate commands for interfacing to holding registers Parameter description head...

Page 6: ...s these are a fire explosion and severe burn hazard Do not burn or expose them to high temperatures Do not recharge crush disassemble or expose the contents to water For hazardous or non hazardous locations the replacement battery model number is BWA BATT 001 Xeno model number XL 205F For non hazardous locations only the replacement battery model number is BWA BATT 011 For pricing and availability...

Page 7: ...ckel finish PVC insulation 3 2 35 mm 6 mm 4 20 mm 72 mm Tube Included with the DX80 E Models Mounting hardware kit BWA HW 003 PTFE tape BWA 9O2 C 900 MHz or BWA 2O2 C 2 4 GHz Antenna 2 dBd Omni Rubber Swivel RP SMA Male Not included with Internal antenna models BWA BATT 001 Replacement battery 3 6 Volt D Lithium Cell BWA HW 032 Access Hardware for E Housing One each of 1 2 inch plug 1 2 inch gland...

Page 8: ...NTIAL OR SPECIAL DAMAGES RESULTING FROM ANY PRODUCT DEFECT OR FROM THE USE OR INABILITY TO USE THE PRODUCT WHETHER ARISING IN CONTRACT OR WARRANTY STATUTE TORT STRICT LIABILITY NEGLIGENCE OR OTHERWISE Banner Engineering Corp reserves the right to change modify or improve the design of the product without assuming any obligations or liabilities relating to any product previously manufactured by Ban...

Reviews: