background image

Sure Cross

®

 User Configuration Tool

The User Configuration Tool (UCT) offers an easy way to link I/O points in your wireless network, view I/O register values

graphically, and set system communication parameters when a host system is not part of the wireless network.

The User Configuration Tool (UCT) software runs on any computer with the Windows

7, Windows 8, or Windows 10 operating system. Use a USB to RS-485 adapter cable

to connect a standalone DX80 Gateway to the computer. For DXM Controllers with

an internal DX80 radio, connect a computer to the DXM Controller using a USB or

Ethernet connection. Download the most recent revisions of the UCT software from

Banner Engineering's website: 

http://www.bannerengineering.com/wireless

.

The USB to RS-485 adapter cable is not required for the DXM Controller. For

standalone DX80 Gateway devices use:

USB to RS-485 adapter cable model BWA-UCT-900 for 1 Watt radios

USB to RS-485 adapter cable model BWA-HW-006 for all other radios

Setting Up Your Wireless Network

To set up and install your wireless network, follow these steps.

Disconnect the power from your Sure Cross devices.
1. Configure the DIP switches of all devices.
2. If your device has I/O, connect the sensors to the Sure Cross devices. If your device does not have I/O, skip this step.
3. Refer to the wiring diagrams to apply power to all devices.

For two LED models, the Gateway's LED 1 is solid green and the Node's LED 2 flashes red to indicate there is no

radio link to the Gateway.

For one LED models, the Gateway's LED is solid green and the Node's LED flashes red to indicate there is no radio

link to the Gateway.

4. Form the wireless network by binding the Nodes to the Gateway. If the binding instructions are not included in the

datasheet, refer to the product manual for binding instructions.

5. Observe the LED behavior to verify the devices are communicating with each other.

For two LED models, the Gateway's LED 1 is solid green and the Node's LED 1 flashes green to indicate it is

communicating with the Gateway.

For one LED models, the Gateway's LED is solid green and the Node's LED flashes green to indicate it is

communicating with the Gateway.

6. Conduct a site survey between the Gateway and Nodes. If the site survey instructions are not included in this

datasheet, refer to the product manual for detailed site survey instructions.

7. Install your wireless sensor network components. If installation instructions are not included in this datasheet, refer to

the product manual for detailed installation instructions.

For additional information, including installation and setup, weatherproofing, device menu maps, troubleshooting, and a

list of accessories, refer to one of the following product manuals.

Sure Cross

®

 Quick Start Guide: 

128185

Sure Cross

®

 Wireless I/O Network Instruction Manual: 

132607

Web Configurator Instruction Manual (used with "Pro" and DX83 models): 

134421

Host Controller Systems Instruction Manual: 

132114

Configure the DIP Switches

Before making any changes to the DIP switch positions, disconnect the power. DIP switch changes will not be recognized if

power isn't cycled to the device.

For parameters not set via DIP switches, use the User Configuration Tool (UCT) to make configuration changes. For

parameters set using the DIP switches, the DIP switch positions override any changes made using the User Configuration

Tool.

Accessing the Internal DIP Switches

To access the internal DIP switches, follow these steps:
1. Unscrew the four screws that mount the cover to the bottom housing.

 

 

Sure Cross

®

 Performance Node

2

www.bannerengineering.com - Tel: +1-763-544-3164

P/N 155862 Rev. G

Summary of Contents for Sure Cross DX80N2X6S-P2

Page 1: ...P2 900 MHz ISM Band IP67 NEMA 6 Inputs Four selectable discrete two 0 to 20 mA default or 0 to 10 V user configurable Outputs Four sourcing discrete two 0 to 20 mA DX80N2X6S P2 2 4 GHz ISM Band DX80 C...

Page 2: ...nstructions are not included in the datasheet refer to the product manual for binding instructions 5 Observe the LED behavior to verify the devices are communicating with each other For two LED models...

Page 3: ...A input allows you to determine when you have an error condition with the sensor A normal input reading between 4 and 20 mA indicates a functioning sensor whereas a value below 4 mA indicates an error...

Page 4: ...Refer to the Modbus Register table for the I O number for each analog input Writing a four 4 to the Units parameter defines the units as 0 to 10V Writing a two 2 to the Units parameter defines the un...

Page 5: ...x DOx Discrete OUT x GND Ground dc common connection PWR 10 to 30 V dc power connection RX Serial communication line for the Gateway No connection for Nodes TX Serial communication line for the Gatew...

Page 6: ...t damage Do not exceed analog input ratings for analog inputs Only connect sensor outputs to analog inputs Analog Input Wiring 10 30 V dc Power Analog Input Wiring 4 20 mA 2 Wire Externally Powered Se...

Page 7: ...de 16 Discrete IN 4 0 1 0 1 5 5 5 Node 16 Analog IN 1 mA V 0 0 0 0 20 0 10 0 0 65535 6 6 6 Node 16 Analog IN 2 mA V 0 0 0 0 20 0 10 0 0 65535 7 7 7 Node 16 Reserved 8 8 8 Node 16 Device Message 9 9 9...

Page 8: ...ications Certifications for DX8x C External Wiring Terminal and DX8x E Models CSA Class I Division 2 Groups ABCD Class I Zone 2 AEx Ex nA II T4 Certificate 1921239 ATEX II 3 G Ex nA IIC T4 Gc Group II...

Page 9: ...tion country is not on this list Any misuse abuse or improper application or installation of this product or use of the product for personal protection applications when the product is identified as n...

Reviews: