background image

Wire the Gateway's I/O

PWR

GND
DO6

DO5
DO4

DO3
DO2

DO1

PWR

GND
DI6

DI5
DI4

DI3
DI2

DI1

Wire the

Gateway’s I/O

DI1
DI2
DI3
DI4
DI5
DI6

V-
V-

V+

V+

DO6

DO5

DO1
DO2
DO3
DO4

Tx/+
Rx/-

DI

x

. Discrete IN 

x

DO

x

. Discrete OUT 

x

GND. Ground/DC common connection
PWR. 10 to 30 V DC power connection

RX/-. Serial communication line for the Gateway. No connection

for Nodes
TX/+. Serial communication line for the Gateway; no connection

for Nodes
V+. 10 to 30 V DC power connection
V–. Ground/DC common connection

Discrete Input Wiring for PNP Sensors

Discrete Output Wiring (PNP)

Discrete IN

PWR

10-30V dc

Discrete OUT

GND

PWR

10-30V dc

Load

dc common

Modbus Register Table for the Gateway with Switch-Based Mapping

I/O

Modbus Holding

Register (Gateway)

I/O Type

I/O Range

Holding Register

Representation

Terminal Block

Labels

Min.

Max.

Min. (Dec.)

Max. (Dec.)

1

1

Discrete IN 1

0

1

0

1

DI1

2

2

Discrete IN 2

0

1

0

1

DI2

3

3

Discrete IN 3

0

1

0

1

DI3

4

4

Discrete IN 4

0

1

0

1

DI4

5

5

Discrete IN 5

0

1

0

1

DI5

6

6

Discrete IN 6

0

1

0

1

DI6

7

7

Reserved

8

8

Device Message

9

9

Discrete OUT 1

0

1

0

1

DO1

10

10

Discrete OUT 2

0

1

0

1

DO2

11

11

Discrete OUT 3

0

1

0

1

DO3

12

12

Discrete OUT 4

0

1

0

1

DO4

13

13

Discrete OUT 5

0

1

0

1

DO5

14

14

Discrete OUT 6

0

1

0

1

DO6

15

15

Control Message

16

16

Reserved

Sure Cross

®

 DX80 Gateway for Wireless Q45 Sensors

 

 

P/N 161862 Rev. E

www.bannerengineering.com - Tel: + 1 888 373 6767

5

Summary of Contents for Sure Cross DX80

Page 1: ...ned conditions For additional information updated documentation and a list of accessories refer to Banner Engineering s website www bannerengineering com WARNING Do not use this device for personnel p...

Page 2: ...red mode use the User Configuration Software or a Modbus command to change the device parameters DIP switch positions 3 through 8 are ignored In DIP Switch Configured mode use the DIP switches to conf...

Page 3: ...loss Q45 1 Gateway OUT 1 Link loss alarm for Q45 1 Gateway OUT 2 Q45 2 Gateway OUT 3 Link loss alarm for Q45 2 Gateway OUT 4 Q45 3 Gateway OUT 5 Link loss alarm for Q45 3 Gateway OUT 6 Three Wireless...

Page 4: ...6 Node 2 OUT 3 Three Nodes to One Gateway DIP Switches 6 ON 7 ON 8 OFF Gateway Node 01 Node 02 Node 03 Three SureCross DX80 Nodes each with 2 inputs and 2 outputs Node 1 IN 1 Gateway OUT 1 Gateway IN...

Page 5: ...PWR 10 30V dc Load dc common Modbus Register Table for the Gateway with Switch Based Mapping I O Modbus Holding Register Gateway I O Type I O Range Holding Register Representation Terminal Block Labe...

Page 6: ...23 Node 22 Node 21 Node 20 Node 19 Node 18 Node 17 Node 16 6693 Node 47 Node 46 Node 45 Node 44 Node 43 Node 42 Node 41 Node 40 Node 39 Node 38 Node 37 Node 36 Node 35 Node 34 Node 33 Node 32 Inputs O...

Page 7: ...it For example to assign your DX80 to Node 10 set the Gateway s left dial to 1 and the right dial to 0 Valid Node addresses are 01 through 47 3 On the Q45 Loosen the clamp plate on the top of the DX80...

Page 8: ...o conduct a Site Survey with another Node and repeat steps 2 through 6 8 To end the Site Survey double click the Gateway s button 2 9 Change the Gateway s rotary dials back to 0 The LCD displays the d...

Page 9: ...Greater than 8 V OFF Condition PNP Less than 5 V Discrete Outputs Update Rate 125 milliseconds ON Condition Supply minus 2 V OFF Condition Less than 2 V Output State Following Timeout OFF Discrete Ou...

Page 10: ...y product of its manufacture which at the time it is returned to the factory is found to have been defective during the warranty period This warranty does not cover damage or liability for misuse abus...

Reviews: