Banner SSA-ISD-TCA Instruction Manual Download Page 21

Product

Directive

SSA-ISD Connect with Indication

Machinery Directive 2006/42/EC

Representative in EU: Peter Mertens, Managing Director, Banner Engineering BV. Address: Park Lane, Culliganlaan 2F, bus

3,1831 Diegem, Belgium.

5.4   Information Available Using ISD

Obtain the following information from the ISD chain and a diagnostic unit or an ISD-enabled Safety Controller.

Cyclic Data about the Chain

Short Name

Data Format

Description

Count mismatch

1/0

The number of devices in chain does not match configuration

Order mismatch

1/0

The order of devices in the chain does not match the configuration

No ISD data detected

1/0

No (or corrupted) ISD data being transmitted (being received by diagnostic device)

Incompatible device

1/0

The chain or a unit in the chain has data but not ISD data

ISD detected not configured

1/0

ISD data detected on inputs that are not configured as ISD input

Terminator missing

1/0

Terminator plug not present (or inputs to first device low)

Actuator not taught

1/0

Not applicable

Wrong actuator detected

1/0

Not applicable

Internal unit error

1/0

A unit in the chain has an internal error

Output fault detected

1/0

A unit in the chain has an output fault and will turn off after the switch off delay period

Individual Unit Data - Flags

Short Name

Data Format

Description

Actuator detected

1/0

Not applicable

Wrong actuator detected/Input
status

1/0

Input devices connect status

Sensor not paired

1/0

Not applicable

Output 1

1/0

Output 1 is on

Output 2

1/0

Output 2 is on

Marginal range/Input status

1/0

Input devices contact status

Input 1

1/0

ISD device input 1 is on

Input 2

1/0

ISD device input 2 is on

Local reset expected

1/0

An ISD device with the latch feature requires a reset

Operating voltage warning

1/0

Voltage to the ISD device is at the limit of specifications

ISD data error

1/0

ISD error bit, corrupted data was received from the SI-RF ISD chain of switches.

Safety input fault

1/0

The system detected a fault on a safety input of an ISD device, power cycle required

Output error

1/0

ISD Device detects an output short to voltage or ground. This starts the "switch-off timer"
counter.

Operating voltage error

1/0

Voltage to the ISD Device is above (over 30 V DC) or below (less than 19.2 V DC) limit of range.

Power cycle required

1/0

ISD Device detects a fault, a power cycled required.

 

 

SSA-ISD Connect with Indication

 

www.bannerengineering.com - Tel: + 1 888 373 6767

21

Summary of Contents for SSA-ISD-TCA

Page 1: ...SSA ISD Connect with Indication Instruction Manual Original Instructions 215320 Rev B 1 February 2021 Banner Engineering Corp All rights reserved 215320 ...

Page 2: ... Stops 7 2 5 2 Wire the SSA ISD Connect in a Chain of ISD Interlocks 8 2 5 3 Wiring Additional Power Supplies 9 2 6 Checkout 11 2 7 In Series Diagnostic ISD Information 12 3 Specifications 13 3 1 Dimensions 14 4 Accessories 15 4 1 Cordsets 15 4 2 Adapters and Other Accessories 18 4 3 Safety Controllers 18 4 4 ISD Connect Compatible Devices 18 5 Product Support and Maintenance 20 5 1 Maintenance an...

Page 3: ...oughly familiar with all applicable standards some of which are listed within the specifications Banner Engineering Corp makes no claim regarding a specific recommendation of any organization the accuracy or effectiveness of any information provided or the appropriateness of the provided information for a specific application WARNING Not a safeguarding device Failure to follow these instructions c...

Page 4: ...ily manipulated by an operator to defeat the safety function s for example ensure the operator cannot remove a device from the chain 2 2 Installation Requirements The device is intended for indoor use only and must not be affected by environmental conditions Do not expose the device to excessive shocks and vibrations otherwise the device may be deformed or damaged causing malfunction or operation ...

Page 5: ...nnot be suspended overridden or defeated unless accomplished in a manner of the same or greater degree of safety as the machine s safety related control system that includes the SSA ISD Connect An ISD compatible Banner Safety Controller such as the SC10 2ro provides a series connection of redundant contacts that form protective stop circuits for use in either single channel or dual channel control...

Page 6: ...e Banner SC10 2ro Safety Controller WARNING The SSA ISD Connect does not have external device monitoring EDM If EDM is required for the application it must be implemented in the external control 2 4 1 Fault Tolerant Output Feature Faults that do not immediately compromise the safe operation of the SSA ISD Connect for example safety output to external potential crosswire short safety output result ...

Page 7: ...in 4 Black CH2b Pin 5 Gray 2 5 1 Wire the SSA ISD Connect in a Chain of ISD E Stops When connecting emergency stop units in series simplify the wiring by using special t adapters low cost unshielded four wire double ended cables and the SSA ISD Connect with Indication A configuration of three lighted ISD e stops and a panel mount e stop is shown The SSA EB1PLx 0Dx E stops SI RFD switches and the S...

Page 8: ...2 of the t adapter Connect the female end of the double ended cable to the next series connection t adapter SI RFA TS or the SSA ISD Connect 5 At the end of the line install a terminating plug SI RFA P to properly truncate the system 6 Wire the wired end of the 4 pin M12 cable from step 1 directly to a Safety Monitoring Device such as an ISD enabled Banner Safety Controller model SC10 2roe You may...

Page 9: ...e to the female 4 pin M12 of the t adapter Connect the female end of the double ended cable to the next series connection t adapter SI RFA TS or the SSA ISD Connect 5 At the end of the line install a terminating plug SI RFA P to properly truncate the system 6 Wire the wired end of the 4 pin M12 cable from step 1 directly to a Safety Monitoring Device such as an ISD enabled Banner Safety Controller...

Page 10: ...s an SI RFA TS connector the SI RFA TK cannot be connected to an SSA ISD TCA Figure 7 Option 2 Replace the terminator with a power supply The OSSD1 and OSSD2 wires at power supply 2 must be connected to 24 V DC If available set the power supplies for parallel output 1 E Stops with ISD E Stop without ISD 8 SI RFA TS SI RFA TS SI RFA TS SI RFA TS SI RFA TS Power Safety Monitoring Module 24Vdc 0Vdc O...

Page 11: ... A Designated Person should check the safety point for proper operation physical damage button looseness and excessive environmental contamination This should take place on a periodic schedule determined by the user based on the severity of the operating environment and the frequency of switch actuations Adjust repair or replace components as needed If inspection reveals contamination on the switc...

Page 12: ...tics the following information can be transmitted among others Safety Device Status on off or faulted Under voltages in the series connection chain Attempts to remove a device from the chain Wrong order of devices in the chain At this time this information can be refined using the following interfaces USB Displays device information on the PC requires using the SI RF DM1 or SC10 2roe IO Link Bus i...

Page 13: ...voltage Ue 3 V Protection Sustained short circuit and overload protection thermal digital clocking Test pulse duration 70 us Test pulse rate 1 s Input Device Requirements Accepts two normally closed NC contacts Simultaneity Requirement Three seconds Indication Red 618 nm Green 525 nm Housing connectors Housing Polyvinyl Chloride PVC Black Connector Nuts Nickel plating on Cu Zn allow Power Up Delay...

Page 14: ...3 1 Dimensions All measurements are listed in millimeters unless noted otherwise SSA ISD Connect with Indication 14 www bannerengineering com Tel 1 888 373 6767 ...

Page 15: ...Length Style Dimensions Pinout Female MQDC1 501 5 0 5 m 1 5 ft Straight 44 Typ ø 14 5 M12 x 1 2 3 4 1 5 1 Brown 2 White 3 Blue 4 Black 5 Gray MQDC1 506 2 m 6 5 ft MQDC1 515 5 m 16 4 ft MQDC1 530 9 m 29 5 ft MQDC1 506RA 2 m 6 5 ft Right Angle 32 Typ 1 26 30 Typ 1 18 ø 14 5 0 57 M12 x 1 MQDC1 515RA 5 m 16 4 ft MQDC1 530RA 9 m 29 5 ft 4 Pin Threaded Male M12 Euro Style Cordsets Single Ended Model Len...

Page 16: ...515 5 04 m 16 5 ft MQDMC 530 9 04 m 29 7 ft MQDMC 506RA 2 m 6 56 ft Right Angle 31 8 mm 1 25 31 mm 1 22 M12X1 Ø13 5 mm 0 53 MQDMC 515RA 5 m 16 4 ft MQDMC 530RA 9 m 29 5 ft 4 Pin Threaded M12 Euro Style Cordsets Double Ended Model Length Style Dimensions Pinout MQDEC 401SS 0 31 m 1 ft Male Straight Female Straight 40 Typ 1 58 ø 14 5 0 57 M12 x 1 44 Typ 1 73 ø 14 5 0 57 M12 x 1 Female 2 3 4 1 Male 1...

Page 17: ...SS 3 66 m 12 ft 5 Pin Threaded M12 Euro Style Cordsets Double Ended Model Length Style Dimensions Pinout Male Pinout Female MQDEC 501RS 0 31 m 1 02 ft Male Right angle Female Straight 44 Typ 1 73 ø 14 5 0 57 M12 x 1 32 Typ 1 26 30 Typ 1 18 ø 14 5 0 57 M12 x 1 1 4 5 3 2 2 3 4 1 5 MQDEC 503RS 0 91 m 2 99 ft 1 Brown 2 White 3 Blue 4 Black 5 Gray MQDEC 506RS 1 83 m 6 ft MQDEC 512RS 3 66 m 12 ft 5 Pin ...

Page 18: ...2d XS26 2d 26 convertible I O and 2 Redundant Solid State Safety Outputs with Display SC26 2e XS26 2e 26 convertible I O and 2 Redundant Solid State Safety Outputs with Ethernet SC26 2de XS26 2de 26 convertible I O and 2 Redundant Solid State Safety Outputs with Display and Ethernet SC10 2roe 10 Inputs 2 redundant relay safety outputs 3 contacts each ISD compatible 4 4 ISD Connect Compatible Devic...

Page 19: ... LM40KHE Q5A 4 Limit Switch Metal 2 NC CH1 pin 1 2 CH2 pin 4 5 SI LS83E Q5A 4 Limit Switch Plastic 2 NC CH1 pin 1 2 CH2 pin 4 5 SI LS100F Q5A 4 Limit Switch Plastic 2 NC 1 NO CH1 pin 1 2 CH2 pin 4 5 SI QM90E Q5A 4 Limit Switch Plastic 2 NC CH1 pin 1 2 CH2 pin 4 5 SI HG63FQDL Hinge Stainless Steel 2 NC 1 NO SI HGZ63FQDL Hinge Zinc Diecast 2 NC 1 NO SI HG63FQDR Hinge Stainless Steel 2 NC 1 NO SI HGZ...

Page 20: ...te red or green Figure 9 SSA ISD Connect status indicators Input Device Status Indicator on both sides Rotate 180 ISD Status Indicator on both sides Input Device Status Two NC Contact Status OSSD Inputs SSA ISD Connect Status OSSD Outputs Input Device LED ISD Status LED Run State closed On Normal On Green Green Run State closed Off Normal Off Green Red Off State open On Normal Off Red Green Off St...

Page 21: ...ternal error Output fault detected 1 0 A unit in the chain has an output fault and will turn off after the switch off delay period Individual Unit Data Flags Short Name Data Format Description Actuator detected 1 0 Not applicable Wrong actuator detected Input status 1 0 Input devices connect status Sensor not paired 1 0 Not applicable Output 1 1 0 Output 1 is on Output 2 1 0 Output 2 is on Margina...

Page 22: ...les the device has experienced Output switch off time number The delay counter for certain output faults 0 inactive 20 to 1 remaining minutes to device lockout state Range warning count number Not applicable Supply voltage number The actual input voltage detected by the ISD device Internal temperature number The internal temperature of the ISD device C Actuator distance number Not applicable Expec...

Page 23: ...EQUENTIAL OR SPECIAL DAMAGES RESULTING FROM ANY PRODUCT DEFECT OR FROM THE USE OR INABILITY TO USE THE PRODUCT WHETHER ARISING IN CONTRACT OR WARRANTY STATUTE TORT STRICT LIABILITY NEGLIGENCE OR OTHERWISE Banner Engineering Corp reserves the right to change modify or improve the design of the product without assuming any obligations or liabilities relating to any product previously manufactured by...

Reviews: