Discrete Device Amber LEDs
Indication
Status
Off
Discrete OUT is inactive
Solid Amber
Discrete OUT is active
IO-Link Communication Amber LED
Indication
Status
Off
IO-Link communications are not present
Flashing Amber (900 ms On, 100 ms Off)
IO-Link communications are active
Power Indicator Green LED
Indication
Status
Off
Power off
Solid Green
Power on
Specifications
Supply Voltage
18 V DC to 30 V DC at 400 mA maximum
Power Pass-Through Current
500 mA per port maximum
Discrete Output Load Rating
100 mA
Supply Protection Circuitry
Protected against reverse polarity and transient voltages
Leakage Current Immunity
400 µA
Indicators
Green: Power
Amber: IO-Link communications
Amber: Discrete OUT status
Connections
(8) Integral 4-pin M12 female quick disconnect
(1) Integral 4-pin M12 male quick-disconnect connector
Construction
Coupling Material: Nickel-plated brass
Connector Body: PVC translucent black
Vibration and Mechanical Shock
Meets IEC 60068-2-6 requirements (Vibration: 10 Hz to 55 Hz, 0.5 mm amplitude, 5
minutes sweep, 30 minutes dwell)
Meets IEC 60068-2-27 requirements (Shock: 15G 11 ms duration, half sine wave)
Certifications
Banner Engineering Europe Park Lane,
Culliganlaan 2F bus 3, 1831 Diegem,
BELGIUM
Turck Banner LTD Blenheim House,
Blenheim Court, Wickford, Essex SS11
8YT, Great Britain
Environmental Rating
IP65, IP67, IP68
NEMA/UL Type 1
Operating Conditions
Temperature: –40 °C to +70 °C (–40 °F to +158 °F)
90% at +70 °C maximum relative humidity (non-condensing)
Storage Temperature: –40 °C to +80 °C (–40 °F to +176 °F)
Required Overcurrent Protection
WARNING: Electrical connections must be made by
qualified personnel in accordance with local and
national electrical codes and regulations.
Overcurrent protection is required to be provided by end product application per the
supplied table.
Overcurrent protection may be provided with external fusing or via Current Limiting,
Class 2 Power Supply.
Supply wiring leads < 24 AWG shall not be spliced.
For additional product support, go to www.bannerengineering.com.
Supply Wiring (AWG)
Required Overcurrent Protection (Amps)
20
5.0
22
3.0
24
2.0
26
1.0
28
0.8
30
0.5
R95C 8-Port Discrete Bimodal to IO-Link Hub
4
www.bannerengineering.com - Tel: + 1 888 373 6767
P/N 227446 Rev. A