Banner R95C Series Manual Download Page 1

Instruction Manual

• Compact bimodal to IO-Link device converter that connects discrete inputs and sends

the value to the IO-Link Master

• Enabled Delay Modes: ON/OFF Delay, ON/OFF One-shot, ON/OFF/Retriggerable One-

shot, ON/OFF Pulse-stretcher and Totalizer

• Measurement Metrics: Count, Events Per Minute (EPM), and Duration

• Discrete Mirroring: Discrete signals (In/Out) from all eight ports can be mirrored to any

of the eight ports, Discrete Out, or the host white wire output

• Outputs a discrete value as received from IO-Link Master Process Data Out

• Discrete input/output can be independently configured as NPN or PNP

• Rugged over-molded design meets IP65, IP67, and IP68

• Connects directly to a sensor or anywhere in-line for ease of use

• R95C IO-Link hubs are a quick, easy, and economical way to integrate non-IO-Link

devices into an IO-Link system

Models

 

C = Converter

8B21 = 8-port, 
bimodal, 2
inputs, 1 output  

K = IO-Link

Q = M12 integral 
quick disconnect

Function

Converter

Control

C

Housing

R95

K

Connector

Q

8B21

 

Overview

The R95C-8B21-KQ hub connects two discrete channels to each of the eight unique ports, providing access to monitoring and configuring those

ports with an IO-Link master. Host mirroring is available where a selected port input/output discrete signal can be routed to Pin 2 (male) on the PLC/

Host connection.

Configuration

For more information, see P/N 227447 

R95C-8B21-KQ IO-Link Data Reference Guide and P/N 227506 R95C-8B21-KQ IODD Files.

Figure 1. Logic Flow

Input State

Delay Mode
• Disabled
• On/Off Delay
• On/Off/Retriggerable One-shot
• On/Off Pulse Stretcher
• Totalizer

Host

Mirroring

Enable

Host Mirroring

Process Data

Input

Measurement

Statistics

Mirroring

Enabled

Enabled

Input

Disabled

Ouput

Process Data In

Measurement Statistics

Mirroring - Discrete 2 Output

• Discrete 1 and 2 Input State (active/inactive)
• Selected Measurements [1]..[4]

Process Data

Input

Process Data In

• Discrete 2 Output State (active/inactive)
• Discrete 1 Input State (active/inactive)
• Selected Measurements [1]..[4]

• Count
• RPM
• Duration

• Port/Channel selected state driven to Pin 2 (F)

Process Data

Output

Process Data Out - Discrete 2 Output
• Process Data Out selected state driven to Pin 2 (F)

Host Mirroring - Discrete Host Out
• Port/Channel selected state driven to Pin 2 (M)

Discrete 2

Selection

Mirroring

Enable

Table 1: Measurements – Female Pins

Port 1-Port 8 Pin Number: Description

IO Metric

Description

Pin 4 – Discrete 1

Count Value

Running count of the received input pulses

Duration Value

Duration of the last input pulse in µs with 500 µs granularity

Events per Minute Value

Running count of the number of pulses received averaged over one

minute

Range: 1 to 37,500

Reset Metrics

Do Not Reset

Reset

Pin 2 – Discrete 2

Count Value

Running count of the received input pulses

Duration Value

Duration of the last input pulse in µs with 500 µs granularity

R95C 8-Port Discrete Bimodal to IO-Link Hub

 

 

Original Document

227446 Rev. A

15 December 2022

227446