Banner ES-FA-11AA Instruction Manual Download Page 11

Output Configuration

Low Current Rating: The 5 

μ

m gold-plated contacts allow

the switching of low current/low voltage. In these low-

power applications, multiple contacts can also be switched

in series (e.g., “dry switching”). To preserve the gold

plating on the contacts, do not exceed the following max.

values at any time:

Minimum

Maximum

Voltage

1 V ac/dc

60 V

Current

5 mA ac/dc

300 mA

Power

5 mW (5 mVA)

7 W (7 VA)

High Current Rating: If higher loads must be switched

through one or more of the contacts, the minimum and

maximum values of the contact(s) changes to:

Minimum

Maximum

Voltage

15 V ac/dc

250 V ac/dc

Current

30 mA ac/dc

ES-FA-9AA: 6A

ES-FA-11AA: 7A

Power

0.45 W (0.45 VA)

ES-FA-9AA: 200 W (1,500 VA)

ES-FA-11AA: 200 W (1,750 VA)

Mechanical life

> 20,000,000 operations

Electrical life (switching cycles of the output contacts, resistive

load)

150,000 cycles at 1,500 VA; 1,000,000 cycles at 450 VA; 2,000,000

cycles at 250 VA; 5,000,000 cycles at 125 VA

Output Response Time

25 milliseconds typical

Note

Transient suppression is recommended when switching inductive loads.

Install suppressors across load. Never install suppressors across output

contacts (see Wiring of Arc Suppressors warning in 

Auxiliary Monitor

Contact (Model ES-FA-11AA Only) 

on page 8).

Input Requirements

Safety input switch: Dual-Channel (contacts) hookup – 10 to 20 mA

steady state at 12 V dc. NOTE: Inputs are designed with a brief

contact-cleaning current of 100 mA when initially closed.
Safety input switch: Single-Channel hookup – 40 to 100 mA at 24 V

ac/dc +/- 10%; 50/60 Hz
Reset switch: 20 mA at 12 V dc, hard contact only

Minimum OFF-State Recovery Time

250 ms

Design Standards

Cat. 4 PL e per EN ISO 13849-1; SIL 3 per IEC 61508 and IEC 62061

Certifications

Dimensions

118.0 mm

(4.65")

84.0 mm

(3.31")

22.5 mm

(0.89")

Machine

Safety

ES-FA-9AA

Power

S21

A1

S33

S11

S22

S34

S12

13

23

33

14

24

34

A2

K1

K2

1

2

CH.

CH.

ES-FA-9AA and ES-FA-11AA E-Stop Safety Module

 

 

P/N 60606 Rev. G

www.bannerengineering.com - Tel: +1-763-544-3164

11

Summary of Contents for ES-FA-11AA

Page 1: ...and or hard guards to protect personnel from hazardous machinery Failure to install point of operation guards on hazardous machinery can result in a dangerous condition which could lead to serious inj...

Page 2: ...vel of risk of harm These safety related functions can prevent initiation or they can stop or remove a hazard The failure of a safety related function or its associated safety circuit usually results...

Page 3: ...turn to the closed contact armed position The switch must be a positive opening or direct opening type as described by IEC 60947 5 1 Standards ANSI NFPA 79 ANSI B11 19 IEC EN60204 1 and ISO 13850 spec...

Page 4: ...ble local standards and codes Lockout tagout procedures may be required Refer to OSHA 29CFR1910 147 ANSI Z244 1 ISO 14118 or the appropriate standard for controlling hazardous energy It is not possibl...

Page 5: ...rs associated with the operation of the machine to recognize and immediately correct such failures If you have any questions about your intended use please contact a Banner applications engineer Conne...

Page 6: ...rdous area Reset switches must also be out of reach from within the safeguarded space and must be protected against unauthorized or inadvertent operation for example through the use of rings or guards...

Page 7: ...Interfacing MSCs Warning MSC Monitor Contacts or Jumper A2 A1 S34 S33 S21 S11 S12 S22 dc common V ES FA 9AA 24V ac dc Auto Reset Manual Reset A2 No Connection Reset A1 S34 S11 S33 MSC1 MSC2 MSC3 S22...

Page 8: ...evice A transformer with isolated windings A distribution system with multiple branch circuits capable of diverting energy of surges A capacitance capable of absorbing energy of surges A resistance or...

Page 9: ...sed contact state e g arm the E stop switch to close its contacts Automatic reset Ch1 K1 and Ch2 K2 indicators should come ON and the safety output contacts should close Manual reset From an open cond...

Page 10: ...the Module is not immediately replaced or repaired multiple simultaneous failures may accumulate such that the safety function can not be guaranteed Specifications Power General Supply Voltage and Cur...

Page 11: ...VA 2 000 000 cycles at 250 VA 5 000 000 cycles at 125 VA Output Response Time 25 milliseconds typical Note Transient suppression is recommended when switching inductive loads Install suppressors acro...

Page 12: ...CULAR PURPOSE AND WHETHER ARISING UNDER COURSE OF PERFORMANCE COURSE OF DEALING OR TRADE USAGE This Warranty is exclusive and limited to repair or at the discretion of Banner Engineering Corp replacem...

Reviews: