Modbus Configuration Registers for the Universal Inputs
Each input or output on the I/O base board has associated Modbus registers that configure its operation.
Universal Input Parameters Registers
Universal Inputs
1
2
3
4
Enable Full Scale Registers
3303
3323
3343
3363
Temperature °C/°F Registers
3304
3324
3344
3364
Input Type Registers
3306
3326
3346
3366
Threshold Registers
3308
3328
3348
3368
Hysteresis Registers
3309
3329
3349
3369
Enable Rising Registers
4908
4928
4948
4968
Enable Falling Registers
4909
4929
4949
4969
High Register for Counter Registers
4910
4930
4950
4970
Low Register for Counter Registers
4911
4931
4951
4971
Modbus Configuration Registers for the Analog Output
The I/O base board has two analog outputs that are selectable as 0 to 20 mA (factory default) or 0 to 10 V. To change the
analog output characteristic, physical jumpers must be change on the I/O board and a parameter Modbus register must be
changed.
For step by step instructions on changing the output characteristics see
Analog (DAC) Outputs for the B1 and S1 Models
on
page 14.
Parameters for Analog Output 1 start at 4001 through 4008. Parameters for Analog Output 2 start at 4021 through 4028.
Table 3: Registers for analog output (4xxxx) parameters
Analog output
1
Analog output
2
Description
Values
4001
4021
Maximum Analog Value
4002
4022
Minimum Analog Value
4003
4023
Enable Register Full Scale
0 = Store readings in unit-specific data
1 = Linear rate from 0 to 65535
4004
4024
Hold Last State Enable
0 = Disables Hold Last State and uses the Default Output State setting during an
error condition
1 = Sets the output to its last known value
4005
4025
Default Output State
4008
4028
Analog Output Type
0 to 20 mA or 0 to 10 V DC output (I/O board jumper selectable)
Accuracy: 0.1% of full scale +0.01% per °C
Resolution: 12-bit
After changing the jumper position, write the appropriate value to the Modbus
registers to define your analog output to match the setting selected by the jumper.
2 = 0 to 20 mA output (default)
3 = 0 to 10 V output
2952
Enable Default
Communication Timeout
0 = Disable
1 = Enable
2953
Communication Default I/O
Timeout (100 ms/Count)
Number of 100 ms periods
2954
Enable Default on Power Up
0 = Disable
1 = Sends device outputs to their default condition
Analog Output Type
—The analog outputs may be configured as either 0 to 20 mA outputs (default) or 0 to 10 V outputs. To
change the analog output type change the hardware jumper position and write to the Modbus register that defines the analog
output type. For analog output 1, write to Modbus register 4008, for analog output 2 write to Modbus register 4028. Write a
value of 2 (default) to select 0 to 20 mA; write a value of 3 to select 0 to 10 V.
Sure Cross
®
DXM100-Sx Wireless Modbus Slave
www.bannerengineering.com - Tel: + 1 888 373 6767
25